AXQJ-F TT D / AHXCAMK-HF D 12/20 (24) kV 1-core CAS

Download product group datasheet

Medium-voltage cable for fixed installations indoors and outdoors. May be buried directly in soil. Installations must be in accordance with national regulations and rules of installations. The cable is halogen-free and flame-retardant according to CPR-class Dca-s2,d2,a2.

Standards SS 424 14 16:2024, HD 622 S1 Section 4B:2023
Reaction to fire Dca-s2,d2,a2
CPR - DoP 2025004_DOP.pdf
Conductor Watertight, circular, stranded aluminium, EN/IEC 60228 class 2
Conductor screen Semiconducting cross-linked polyethylene XLPE
Insulation Cross-linked polyethylene XLPE
Insulation screen Semiconducting cross-linked polyethylene XLPE
Inner covering Semiconducting waterswellable tape
Metal screen Copper wires and aluminium foil (CAS). Polyethylene laminated aluminium foil acts as a part of the metallic screen and needs to be connected in cable joints and terminations
Radial watertightness Polyethylene laminated aluminium foil bonded to the sheath
Oversheath UV-protected halogen-free polyolefin compound
Colour of the oversheath Black

1x240/35 CAS

Electric number Size Packaging Voltage

1x240/35 CAS

Nominal diameter of complete cable mm 39
Nominal weight of cable kg/km 1793
Conductor material Aluminium
Nominal diameter of conductor mm 17.8
Nominal cross-sectional area of conductor mm2 240
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 29.2
Number of wires 1
Nominal size of metal screen mm2 35
Min. bending radius
During handling and installation, cable mm 575
In final installation, cable mm 402
During handling and installation, cable cm 57
In final installation, cable cm 40
During handling and installation, cable m 0.57
In final installation, cable m 0.4
Max. pulling force
Pulling-eye kN 7.2
Pulling-stocking kN 3.6
Resistance 20 °C Ω/km 0.125
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0.524
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176228159
Reka code 1181581
Nominal diameter of complete cable mm 39
Nominal weight of cable kg/km 1793
Conductor material Aluminium
Nominal diameter of conductor mm 17.8
Nominal cross-sectional area of conductor mm2 240
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 29.2
Number of wires 1
Nominal size of metal screen mm2 35
Min. bending radius
During handling and installation, cable mm 575
In final installation, cable mm 402
During handling and installation, cable cm 57
In final installation, cable cm 40
During handling and installation, cable m 0.57
In final installation, cable m 0.4
Max. pulling force
Pulling-eye kN 7.2
Pulling-stocking kN 3.6
Resistance 20 °C Ω/km 0.125
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0.524
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176228142
Reka code 1181581

1x300/35 CAS

Electric number Size Packaging Voltage

1x300/35 CAS

Nominal diameter of complete cable mm 41
Nominal weight of cable kg/km 2047
Conductor material Aluminium
Nominal diameter of conductor mm 19.8
Nominal cross-sectional area of conductor mm2 300
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 31
Number of wires 1
Nominal size of metal screen mm2 35
Min. bending radius
During handling and installation, cable mm 604
In final installation, cable mm 423
During handling and installation, cable cm 60
In final installation, cable cm 42
During handling and installation, cable m 0.6
In final installation, cable m 0.42
Max. pulling force
Pulling-eye kN 9
Pulling-stocking kN 4.5
Resistance 20 °C Ω/km 0.1
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0.524
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176228180
Reka code 1181582
Nominal diameter of complete cable mm 41
Nominal weight of cable kg/km 2047
Conductor material Aluminium
Nominal diameter of conductor mm 19.8
Nominal cross-sectional area of conductor mm2 300
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 31
Number of wires 1
Nominal size of metal screen mm2 35
Min. bending radius
During handling and installation, cable mm 604
In final installation, cable mm 423
During handling and installation, cable cm 60
In final installation, cable cm 42
During handling and installation, cable m 0.6
In final installation, cable m 0.42
Max. pulling force
Pulling-eye kN 9
Pulling-stocking kN 4.5
Resistance 20 °C Ω/km 0.1
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0.524
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176228173
Reka code 1181582

1x400/35 CAS

Electric number Size Packaging Voltage

1x400/35 CAS

Nominal diameter of complete cable mm 43
Nominal weight of cable kg/km 2305
Conductor material Aluminium
Nominal diameter of conductor mm 22.4
Nominal cross-sectional area of conductor mm2 400
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 33.6
Number of wires 1
Nominal size of metal screen mm2 35
Min. bending radius
During handling and installation, cable mm 647
In final installation, cable mm 453
During handling and installation, cable cm 65
In final installation, cable cm 45
During handling and installation, cable m 0.65
In final installation, cable m 0.45
Max. pulling force
Pulling-eye kN 12
Pulling-stocking kN 6
Resistance 20 °C Ω/km 0.0778
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0.524
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176228210
Reka code 1181583
Nominal diameter of complete cable mm 43
Nominal weight of cable kg/km 2305
Conductor material Aluminium
Nominal diameter of conductor mm 22.4
Nominal cross-sectional area of conductor mm2 400
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 33.6
Number of wires 1
Nominal size of metal screen mm2 35
Min. bending radius
During handling and installation, cable mm 647
In final installation, cable mm 453
During handling and installation, cable cm 65
In final installation, cable cm 45
During handling and installation, cable m 0.65
In final installation, cable m 0.45
Max. pulling force
Pulling-eye kN 12
Pulling-stocking kN 6
Resistance 20 °C Ω/km 0.0778
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0.524
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176228203
Reka code 1181583

1x500/35 CAS

Electric number Size Packaging Voltage

1x500/35 CAS

Nominal diameter of complete cable mm 47
Nominal weight of cable kg/km 2782
Conductor material Aluminium
Nominal diameter of conductor mm 25.7
Nominal cross-sectional area of conductor mm2 500
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 36.9
Number of wires 1
Nominal size of metal screen mm2 35
Min. bending radius
During handling and installation, cable mm 694
In final installation, cable mm 486
During handling and installation, cable cm 69
In final installation, cable cm 49
During handling and installation, cable m 0.69
In final installation, cable m 0.49
Max. pulling force
Pulling-eye kN 15
Pulling-stocking kN 7.5
Resistance 20 °C Ω/km 0.0605
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0.524
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176228241
Reka code 1181584
Nominal diameter of complete cable mm 47
Nominal weight of cable kg/km 2782
Conductor material Aluminium
Nominal diameter of conductor mm 25.7
Nominal cross-sectional area of conductor mm2 500
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 36.9
Number of wires 1
Nominal size of metal screen mm2 35
Min. bending radius
During handling and installation, cable mm 694
In final installation, cable mm 486
During handling and installation, cable cm 69
In final installation, cable cm 49
During handling and installation, cable m 0.69
In final installation, cable m 0.49
Max. pulling force
Pulling-eye kN 15
Pulling-stocking kN 7.5
Resistance 20 °C Ω/km 0.0605
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0.524
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176228234
Reka code 1181584

1x630/35 CAS

Electric number Size Packaging Voltage

1x630/35 CAS

Nominal diameter of complete cable mm 51
Nominal weight of cable kg/km 3379
Conductor material Aluminium
Nominal diameter of conductor mm 29.3
Nominal cross-sectional area of conductor mm2 630
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 40.7
Number of wires 1
Nominal size of metal screen mm2 35
Min. bending radius
During handling and installation, cable mm 753
In final installation, cable mm 527
During handling and installation, cable cm 75
In final installation, cable cm 53
During handling and installation, cable m 0.75
In final installation, cable m 0.53
Max. pulling force
Pulling-eye kN 18.9
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0.0469
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0.524
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176228272
Reka code 1181585
Nominal diameter of complete cable mm 51
Nominal weight of cable kg/km 3379
Conductor material Aluminium
Nominal diameter of conductor mm 29.3
Nominal cross-sectional area of conductor mm2 630
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 40.7
Number of wires 1
Nominal size of metal screen mm2 35
Min. bending radius
During handling and installation, cable mm 753
In final installation, cable mm 527
During handling and installation, cable cm 75
In final installation, cable cm 53
During handling and installation, cable m 0.75
In final installation, cable m 0.53
Max. pulling force
Pulling-eye kN 18.9
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0.0469
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0.524
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176228265
Reka code 1181585