AXQJ-F TT D / AHXCAMK-HF D 12/20 (24) kV 1-core CAS
Download product group datasheet
Medium-voltage cable for fixed installations indoors and outdoors. May be buried directly in soil. Installations must be in accordance with national regulations and rules of installations. The cable is halogen-free and flame-retardant according to CPR-class Dca-s2,d2,a2.
| Standards | SS 424 14 16:2024, HD 622 S1 Section 4B:2023 |
|---|---|
| Reaction to fire | Dca-s2,d2,a2 |
| CPR - DoP | 2025004_DOP.pdf |
| Conductor | Watertight, circular, stranded aluminium, EN/IEC 60228 class 2 |
| Conductor screen | Semiconducting cross-linked polyethylene XLPE |
| Insulation | Cross-linked polyethylene XLPE |
| Insulation screen | Semiconducting cross-linked polyethylene XLPE |
| Inner covering | Semiconducting waterswellable tape |
| Metal screen | Copper wires and aluminium foil (CAS). Polyethylene laminated aluminium foil acts as a part of the metallic screen and needs to be connected in cable joints and terminations |
| Radial watertightness | Polyethylene laminated aluminium foil bonded to the sheath |
| Oversheath | UV-protected halogen-free polyolefin compound |
| Colour of the oversheath | Black |
1x240/35 CAS
Electric number
Size
Packaging
Voltage
1x240/35 CAS
Nominal diameter of complete cable mm
39
Nominal weight of cable kg/km
1793
Conductor material
Aluminium
Nominal diameter of conductor mm
17.8
Nominal cross-sectional area of conductor mm2
240
Nominal thickness of insulation mm
5.5
Nominal diameter over the insulation without insulation screen mm
29.2
Number of wires
1
Nominal size of metal screen mm2
35
Min. bending radius
During handling and installation, cable mm
575
In final installation, cable mm
402
During handling and installation, cable cm
57
In final installation, cable cm
40
During handling and installation, cable m
0.57
In final installation, cable m
0.4
Max. pulling force
Pulling-eye kN
7.2
Pulling-stocking kN
3.6
Resistance 20 °C Ω/km
0.125
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0.524
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176228159
Reka code
1181581
Nominal diameter of complete cable mm
39
Nominal weight of cable kg/km
1793
Conductor material
Aluminium
Nominal diameter of conductor mm
17.8
Nominal cross-sectional area of conductor mm2
240
Nominal thickness of insulation mm
5.5
Nominal diameter over the insulation without insulation screen mm
29.2
Number of wires
1
Nominal size of metal screen mm2
35
Min. bending radius
During handling and installation, cable mm
575
In final installation, cable mm
402
During handling and installation, cable cm
57
In final installation, cable cm
40
During handling and installation, cable m
0.57
In final installation, cable m
0.4
Max. pulling force
Pulling-eye kN
7.2
Pulling-stocking kN
3.6
Resistance 20 °C Ω/km
0.125
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0.524
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176228142
Reka code
1181581
1x300/35 CAS
Electric number
Size
Packaging
Voltage
1x300/35 CAS
Nominal diameter of complete cable mm
41
Nominal weight of cable kg/km
2047
Conductor material
Aluminium
Nominal diameter of conductor mm
19.8
Nominal cross-sectional area of conductor mm2
300
Nominal thickness of insulation mm
5.5
Nominal diameter over the insulation without insulation screen mm
31
Number of wires
1
Nominal size of metal screen mm2
35
Min. bending radius
During handling and installation, cable mm
604
In final installation, cable mm
423
During handling and installation, cable cm
60
In final installation, cable cm
42
During handling and installation, cable m
0.6
In final installation, cable m
0.42
Max. pulling force
Pulling-eye kN
9
Pulling-stocking kN
4.5
Resistance 20 °C Ω/km
0.1
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0.524
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176228180
Reka code
1181582
Nominal diameter of complete cable mm
41
Nominal weight of cable kg/km
2047
Conductor material
Aluminium
Nominal diameter of conductor mm
19.8
Nominal cross-sectional area of conductor mm2
300
Nominal thickness of insulation mm
5.5
Nominal diameter over the insulation without insulation screen mm
31
Number of wires
1
Nominal size of metal screen mm2
35
Min. bending radius
During handling and installation, cable mm
604
In final installation, cable mm
423
During handling and installation, cable cm
60
In final installation, cable cm
42
During handling and installation, cable m
0.6
In final installation, cable m
0.42
Max. pulling force
Pulling-eye kN
9
Pulling-stocking kN
4.5
Resistance 20 °C Ω/km
0.1
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0.524
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176228173
Reka code
1181582
1x400/35 CAS
Electric number
Size
Packaging
Voltage
1x400/35 CAS
Nominal diameter of complete cable mm
43
Nominal weight of cable kg/km
2305
Conductor material
Aluminium
Nominal diameter of conductor mm
22.4
Nominal cross-sectional area of conductor mm2
400
Nominal thickness of insulation mm
5.5
Nominal diameter over the insulation without insulation screen mm
33.6
Number of wires
1
Nominal size of metal screen mm2
35
Min. bending radius
During handling and installation, cable mm
647
In final installation, cable mm
453
During handling and installation, cable cm
65
In final installation, cable cm
45
During handling and installation, cable m
0.65
In final installation, cable m
0.45
Max. pulling force
Pulling-eye kN
12
Pulling-stocking kN
6
Resistance 20 °C Ω/km
0.0778
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0.524
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176228210
Reka code
1181583
Nominal diameter of complete cable mm
43
Nominal weight of cable kg/km
2305
Conductor material
Aluminium
Nominal diameter of conductor mm
22.4
Nominal cross-sectional area of conductor mm2
400
Nominal thickness of insulation mm
5.5
Nominal diameter over the insulation without insulation screen mm
33.6
Number of wires
1
Nominal size of metal screen mm2
35
Min. bending radius
During handling and installation, cable mm
647
In final installation, cable mm
453
During handling and installation, cable cm
65
In final installation, cable cm
45
During handling and installation, cable m
0.65
In final installation, cable m
0.45
Max. pulling force
Pulling-eye kN
12
Pulling-stocking kN
6
Resistance 20 °C Ω/km
0.0778
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0.524
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176228203
Reka code
1181583
1x500/35 CAS
Electric number
Size
Packaging
Voltage
1x500/35 CAS
Nominal diameter of complete cable mm
47
Nominal weight of cable kg/km
2782
Conductor material
Aluminium
Nominal diameter of conductor mm
25.7
Nominal cross-sectional area of conductor mm2
500
Nominal thickness of insulation mm
5.5
Nominal diameter over the insulation without insulation screen mm
36.9
Number of wires
1
Nominal size of metal screen mm2
35
Min. bending radius
During handling and installation, cable mm
694
In final installation, cable mm
486
During handling and installation, cable cm
69
In final installation, cable cm
49
During handling and installation, cable m
0.69
In final installation, cable m
0.49
Max. pulling force
Pulling-eye kN
15
Pulling-stocking kN
7.5
Resistance 20 °C Ω/km
0.0605
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0.524
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176228241
Reka code
1181584
Nominal diameter of complete cable mm
47
Nominal weight of cable kg/km
2782
Conductor material
Aluminium
Nominal diameter of conductor mm
25.7
Nominal cross-sectional area of conductor mm2
500
Nominal thickness of insulation mm
5.5
Nominal diameter over the insulation without insulation screen mm
36.9
Number of wires
1
Nominal size of metal screen mm2
35
Min. bending radius
During handling and installation, cable mm
694
In final installation, cable mm
486
During handling and installation, cable cm
69
In final installation, cable cm
49
During handling and installation, cable m
0.69
In final installation, cable m
0.49
Max. pulling force
Pulling-eye kN
15
Pulling-stocking kN
7.5
Resistance 20 °C Ω/km
0.0605
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0.524
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176228234
Reka code
1181584
1x630/35 CAS
Electric number
Size
Packaging
Voltage
1x630/35 CAS
Nominal diameter of complete cable mm
51
Nominal weight of cable kg/km
3379
Conductor material
Aluminium
Nominal diameter of conductor mm
29.3
Nominal cross-sectional area of conductor mm2
630
Nominal thickness of insulation mm
5.5
Nominal diameter over the insulation without insulation screen mm
40.7
Number of wires
1
Nominal size of metal screen mm2
35
Min. bending radius
During handling and installation, cable mm
753
In final installation, cable mm
527
During handling and installation, cable cm
75
In final installation, cable cm
53
During handling and installation, cable m
0.75
In final installation, cable m
0.53
Max. pulling force
Pulling-eye kN
18.9
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0.0469
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0.524
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176228272
Reka code
1181585
Nominal diameter of complete cable mm
51
Nominal weight of cable kg/km
3379
Conductor material
Aluminium
Nominal diameter of conductor mm
29.3
Nominal cross-sectional area of conductor mm2
630
Nominal thickness of insulation mm
5.5
Nominal diameter over the insulation without insulation screen mm
40.7
Number of wires
1
Nominal size of metal screen mm2
35
Min. bending radius
During handling and installation, cable mm
753
In final installation, cable mm
527
During handling and installation, cable cm
75
In final installation, cable cm
53
During handling and installation, cable m
0.75
In final installation, cable m
0.53
Max. pulling force
Pulling-eye kN
18.9
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0.0469
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0.524
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176228265
Reka code
1181585