AHXAMK-W 12/20 (24) kV 3-core

Download product group datasheet

Medium-voltage cable for fixed installations outdoors. May be buried directly in soil, also by ploughing. Cable is longitudinally and radially watertight and therefore it is suitable where wet soil and / or fresh water permanently occurs. Installations must be in accordance with national regulations and rules of installations. The cable is halogen-free, but without fire protection. The cable is not CPR-classified.

Standards HD 620 10 F, SFS 5636
Conductor Watertight, circular, stranded aluminium, EN/IEC 60228 class 2
Conductor screen Semiconducting cross-linked polyethylene XLPE
Insulation Cross-linked polyethylene XLPE
Insulation screen Semiconducting cross-linked polyethylene XLPE
Core Identification (all color combinations in the cable family) White phase numbering: L1, L2, L3
Cable lay up Three sheathed cores are laid up around a bare copper earth conductor
Inner covering Semiconducting waterswellable tape against longitudinal water penetration
Metal screen Polyethylene laminated aluminium foil, which acts also as a radial water barrier
Oversheath PE-plastic PELLD
Colour of the oversheath Black

3x50+35 Cu

Electric number Size Packaging Voltage

3x50+35 Cu

Nominal diameter of complete cable mm 59
Nominal weight of cable kg/km 2243
Conductor material Aluminium
Nominal diameter of conductor mm 8
Nominal cross-sectional area of conductor mm2 50
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 19.3
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 41
During handling and installation, cable cm 70
In final installation, phase conductor cm 28
In final installation, cable cm 49
During handling and installation, phase conductor m 0.41
During handling and installation, cable m 0.7
In final installation, phase conductor m 0.28
In final installation, cable m 0.49
Max. pulling force
Pulling-eye kN 7.5
Pulling-stocking kN 2.3
Resistance 20 °C Ω/km 0,641
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006224302
Reka code 1187002

3x70+35 Cu

Electric number Size Packaging Voltage

3x70+35 Cu

Nominal diameter of complete cable mm 62
Nominal weight of cable kg/km 2531
Conductor material Aluminium
Nominal diameter of conductor mm 9.5
Nominal cross-sectional area of conductor mm2 70
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 20.7
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 44
During handling and installation, cable cm 74
In final installation, phase conductor cm 30
In final installation, cable cm 52
During handling and installation, phase conductor m 0.44
During handling and installation, cable m 0.74
In final installation, phase conductor m 0.3
In final installation, cable m 0.52
Max. pulling force
Pulling-eye kN 10.5
Pulling-stocking kN 3.2
Resistance 20 °C Ω/km 0,443
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006224319
Reka code 1187003

3x95+35 Cu

Electric number Size Packaging Voltage

3x95+35 Cu

Nominal diameter of complete cable mm 66
Nominal weight of cable kg/km 2905
Conductor material Aluminium
Nominal diameter of conductor mm 11.1
Nominal cross-sectional area of conductor mm2 95
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 22.4
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 47
During handling and installation, cable cm 79
In final installation, phase conductor cm 33
In final installation, cable cm 55
During handling and installation, phase conductor m 0.47
During handling and installation, cable m 0.79
In final installation, phase conductor m 0.33
In final installation, cable m 0.55
Max. pulling force
Pulling-eye kN 14.3
Pulling-stocking kN 4.3
Resistance 20 °C Ω/km 0,320
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006224326
Reka code 1187004

3x120+35 Cu

Electric number Size Packaging Voltage

3x120+35 Cu

Nominal diameter of complete cable mm 68
Nominal weight of cable kg/km 3200
Conductor material Aluminium
Nominal diameter of conductor mm 12.6
Nominal cross-sectional area of conductor mm2 120
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 23.4
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 48
During handling and installation, cable cm 82
In final installation, phase conductor cm 34
In final installation, cable cm 57
During handling and installation, phase conductor m 0.48
During handling and installation, cable m 0.81
In final installation, phase conductor m 0.34
In final installation, cable m 0.57
Max. pulling force
Pulling-eye kN 18
Pulling-stocking kN 5.4
Resistance 20 °C Ω/km 0,253
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006224333
Reka code 1187005

3x150+35 Cu

Electric number Size Packaging Voltage

3x150+35 Cu

Nominal diameter of complete cable mm 71
Nominal weight of cable kg/km 3570
Conductor material Aluminium
Nominal diameter of conductor mm 13.9
Nominal cross-sectional area of conductor mm2 150
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 25.1
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 50
During handling and installation, cable cm 86
In final installation, phase conductor cm 35
In final installation, cable cm 60
During handling and installation, phase conductor m 0.5
During handling and installation, cable m 0.86
In final installation, phase conductor m 0.35
In final installation, cable m 0.6
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 6.8
Resistance 20 °C Ω/km 0,206
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006224340
Reka code 1187006

3x185+35 Cu

Electric number Size Packaging Voltage

3x185+35 Cu

Nominal diameter of complete cable mm 76
Nominal weight of cable kg/km 4091
Conductor material Aluminium
Nominal diameter of conductor mm 15.6
Nominal cross-sectional area of conductor mm2 185
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 27
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 53
During handling and installation, cable cm 91
In final installation, phase conductor cm 37
In final installation, cable cm 64
During handling and installation, phase conductor m 0.53
During handling and installation, cable m 0.91
In final installation, phase conductor m 0.37
In final installation, cable m 0.64
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.3
Resistance 20 °C Ω/km 0,164
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006224357
Reka code 1187007
Nominal diameter of complete cable mm 76
Nominal weight of cable kg/km 4091
Conductor material Aluminium
Nominal diameter of conductor mm 15.6
Nominal cross-sectional area of conductor mm2 185
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 27
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 53
During handling and installation, cable cm 91
In final installation, phase conductor cm 37
In final installation, cable cm 64
During handling and installation, phase conductor m 0.53
During handling and installation, cable m 0.91
In final installation, phase conductor m 0.37
In final installation, cable m 0.64
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.3
Resistance 20 °C Ω/km 0,164
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006224388
Reka code 1187007

3x240+35 Cu

Electric number Size Packaging Voltage

3x240+35 Cu

Nominal diameter of complete cable mm 82
Nominal weight of cable kg/km 4868
Conductor material Aluminium
Nominal diameter of conductor mm 17.8
Nominal cross-sectional area of conductor mm2 240
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 29.2
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 57
During handling and installation, cable cm 98
In final installation, phase conductor cm 40
In final installation, cable cm 69
During handling and installation, phase conductor m 0.57
During handling and installation, cable m 0.98
In final installation, phase conductor m 0.4
In final installation, cable m 0.69
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,125
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006224500
Reka code 1187018

3x240+70 Cu

Electric number Size Packaging Voltage

3x240+70 Cu

Nominal diameter of complete cable mm 82
Nominal weight of cable kg/km 5173
Conductor material Aluminium
Nominal diameter of conductor mm 17.8
Nominal cross-sectional area of conductor mm2 240
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 29.2
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 57
During handling and installation, cable cm 98
In final installation, phase conductor cm 40
In final installation, cable cm 69
During handling and installation, phase conductor m 0.57
During handling and installation, cable m 0.98
In final installation, phase conductor m 0.4
In final installation, cable m 0.69
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,125
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006224364
Reka code 1187008

3x300+35 Cu

Electric number Size Packaging Voltage

3x300+35 Cu

Nominal diameter of complete cable mm 86
Nominal weight of cable kg/km 5603
Conductor material Aluminium
Nominal diameter of conductor mm 19.8
Nominal cross-sectional area of conductor mm2 300
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 31
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 60
During handling and installation, cable cm 103
In final installation, phase conductor cm 42
In final installation, cable cm 72
During handling and installation, phase conductor m 0.6
During handling and installation, cable m 1.03
In final installation, phase conductor m 0.42
In final installation, cable m 0.72
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,100
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176300084
Reka code 1187019

3x300+70 Cu

Electric number Size Packaging Voltage

3x300+70 Cu

Nominal diameter of complete cable mm 86
Nominal weight of cable kg/km 5893
Conductor material Aluminium
Nominal diameter of conductor mm 19.8
Nominal cross-sectional area of conductor mm2 300
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 31
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 60
During handling and installation, cable cm 103
In final installation, phase conductor cm 42
In final installation, cable cm 72
During handling and installation, phase conductor m 0.6
During handling and installation, cable m 1.03
In final installation, phase conductor m 0.42
In final installation, cable m 0.72
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,100
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006224371
Reka code 1187009