AHXAMK-W 19/33 (36) kV 3-core

Download product group datasheet

Medium-voltage cable DryRex Nordic Wind cables are designed especially to meet the requirements of 36 kV wind farms. May be buried directly in soil, also by ploughing. Installations must be in accordance with national regulations and rules of installations. Cable is longitudinally and radially watertight and therefore it is suitable where wet soil and / or fresh water permanently occurs. The cable is halogen-free, but without fire protection. The cable is not CPR-classified.

Standards HD 620 10 F, SFS 5636
Conductor Watertight, circular, stranded aluminium EN/IEC 60228 class 2
Conductor screen Semiconducting cross-linked polyethylene XLPE
Insulation Cross-linked polyethylene XLPE
Insulation screen Semiconducting cross-linked polyethylene XLPE
Cable lay up Three sheathed cores are laid up around a bare earth conductor
Inner covering Semiconducting waterswellable tape against longitudinal water penetration
Metal screen Aluminium/plastic laminate, which acts also as a radial water barrier.
Oversheath PE-plastic
Colour of the oversheath Black

3x95+35 Cu

Electric number Size Packaging Voltage

3x95+35 Cu

Nominal diameter of complete cable mm 76
Nominal weight of cable kg/km 3634
Conductor material Aluminum
Nominal diameter of conductor mm 11.1
Nominal cross-sectional area of conductor mm2 95
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 26.7
Number of wires 3
Nominal thickness of aluminium laminated foil mm 0.3
Nominal diameter of a sheathed phase conductor mm 35
Min. bending radius
During handling and installation, phase conductor cm 53
During handling and installation, cable cm 91
In final installation, phase conductor cm 37
In final installation, cable cm 64
During handling and installation, phase conductor m 0.53
During handling and installation, cable m 0.91
In final installation, phase conductor m 0.37
In final installation, cable m 0.64
Max. pulling force
Pulling-eye kN 14.3
Pulling-stocking kN 4.3
Resistance 20 °C Ω/km 0.320
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176306161
Reka code 1181895

3x150+35 Cu

Electric number Size Packaging Voltage

3x150+35 Cu

Nominal diameter of complete cable mm 82
Nominal weight of cable kg/km 4410
Conductor material Aluminum
Nominal diameter of conductor mm 13.9
Nominal cross-sectional area of conductor mm2 150
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 29.5
Number of wires 3
Nominal thickness of aluminium laminated foil mm 0.3
Nominal diameter of a sheathed phase conductor mm 38
Min. bending radius
During handling and installation, phase conductor cm 57
During handling and installation, cable cm 98
In final installation, phase conductor cm 40
In final installation, cable cm 69
During handling and installation, phase conductor m 0.57
During handling and installation, cable m 0.98
In final installation, phase conductor m 0.4
In final installation, cable m 0.69
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 6.8
Resistance 20 °C Ω/km 0.206
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176306185
Reka code 1181897

3x185+35 Cu

Electric number Size Packaging Voltage

3x185+35 Cu

Nominal diameter of complete cable mm 86
Nominal weight of cable kg/km 4927
Conductor material Aluminum
Nominal diameter of conductor mm 15.6
Nominal cross-sectional area of conductor mm2 185
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 31.2
Number of wires 3
Nominal thickness of aluminium laminated foil mm 0.3
Nominal diameter of a sheathed phase conductor mm 40
Min. bending radius
During handling and installation, phase conductor cm 60
During handling and installation, cable cm 103
In final installation, phase conductor cm 42
In final installation, cable cm 72
During handling and installation, phase conductor m 0.6
During handling and installation, cable m 1.03
In final installation, phase conductor m 0.42
In final installation, cable m 0.72
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.3
Resistance 20 °C Ω/km 0.164
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176306208
Reka code 1181899

3x240+35 Cu

Electric number Size Packaging Voltage

3x240+35 Cu

Nominal diameter of complete cable mm 92
Nominal weight of cable kg/km 5693
Conductor material Aluminum
Nominal diameter of conductor mm 18
Nominal cross-sectional area of conductor mm2 240
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 33.6
Number of wires 3
Nominal thickness of aluminium laminated foil mm 0.3
Nominal diameter of a sheathed phase conductor mm 43
Min. bending radius
During handling and installation, phase conductor cm 64
During handling and installation, cable cm 110
In final installation, phase conductor cm 45
In final installation, cable cm 77
During handling and installation, phase conductor m 0.64
During handling and installation, cable m 1.1
In final installation, phase conductor m 0.45
In final installation, cable m 0.77
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0.125
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176306222
Reka code 1181901

3x300+35 Cu

Electric number Size Packaging Voltage

3x300+35 Cu

Nominal diameter of complete cable mm 96
Nominal weight of cable kg/km 6468
Conductor material Aluminum
Nominal diameter of conductor mm 19.8
Nominal cross-sectional area of conductor mm2 300
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 35.4
Number of wires 3
Nominal thickness of aluminium laminated foil mm 0.3
Nominal diameter of a sheathed phase conductor mm 45
Min. bending radius
During handling and installation, phase conductor cm 67
During handling and installation, cable cm 115
In final installation, phase conductor cm 47
In final installation, cable cm 81
During handling and installation, phase conductor m 0.67
During handling and installation, cable m 1.15
In final installation, phase conductor m 0.47
In final installation, cable m 0.81
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0.100
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176306246
Reka code 1181903

3x300+70 Cu

Electric number Size Packaging Voltage

3x300+70 Cu

Nominal diameter of complete cable mm 96
Nominal weight of cable kg/km 6758
Conductor material Aluminum
Nominal diameter of conductor mm 19.8
Nominal cross-sectional area of conductor mm2 300
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 35.4
Number of wires 3
Nominal thickness of aluminium laminated foil mm 0.3
Nominal diameter of a sheathed phase conductor mm 45
Min. bending radius
During handling and installation, phase conductor cm 67
During handling and installation, cable cm 115
In final installation, phase conductor cm 47
In final installation, cable cm 81
During handling and installation, phase conductor m 0.67
During handling and installation, cable m 1.15
In final installation, phase conductor m 0.47
In final installation, cable m 0.81
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0.100
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176306253
Reka code 1181904