AXMK/PE PoweRex PE

For fixed installations oudoors. Direct burial in soil is allowed, as long as the relevant national rules of installations are followed.

Standards SFS 5800:2017, SS 424 14 18:2007, HD 603 S1:1994/A3:2007 Part 5 Section E and O
Conductor 16...25 mm² circular stranded aluminium, EN/IEC 60228 class 2
35…300 mm² sector shaped, stranded aluminium, EN/IEC 60228 class 2
Insulation UV-protected XLPE
Core Identification (all color combinations in the cable family) Green/Yellow, brown, black, grey
Inner covering plastic tape
Oversheath UV-protected polyethylene compound
Colour of the oversheath Black

4x16 S PoweRex PE

Electric number Size Packing (m) Voltage

4x16 S PoweRex PE

Nominal diameter of complete cable (mm) 19
Nominal weight of cable (kg/km) 317
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 0.7
Bending radius
During handling and installation, cable (cm) 226
In final installation, cable (cm) 158
During handling and installation, cable (cm) 23
In final installation, cable (cm) 16
During handling and installation, cable (m) 0.23
In final installation, cable (m) 0.16
Pulling force
Pulling-eye (kN) 1
Pulling-stocking (kN) 1
Resistance 20 °C (ohm/km) 1.91
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 1.5
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300213
Reka code 1116040
Nominal diameter of complete cable (mm) 19
Nominal weight of cable (kg/km) 317
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 0.7
Bending radius
During handling and installation, cable (cm) 226
In final installation, cable (cm) 158
During handling and installation, cable (cm) 23
In final installation, cable (cm) 16
During handling and installation, cable (m) 0.23
In final installation, cable (m) 0.16
Pulling force
Pulling-eye (kN) 1
Pulling-stocking (kN) 1
Resistance 20 °C (ohm/km) 1.91
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 1.5
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300206
Reka code 1116040

4x25 S PoweRex PE

Electric number Size Packing (m) Voltage

4x25 S PoweRex PE

Nominal diameter of complete cable (mm) 22
Nominal weight of cable (kg/km) 458
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 0.9
Bending radius
During handling and installation, cable (cm) 267
In final installation, cable (cm) 187
During handling and installation, cable (cm) 27
In final installation, cable (cm) 19
During handling and installation, cable (m) 0.27
In final installation, cable (m) 0.19
Pulling force
Pulling-eye (kN) 1.5
Pulling-stocking (kN) 1.5
Resistance 20 °C (ohm/km) 1.2
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 2.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300237
Reka code 1116041
Nominal diameter of complete cable (mm) 22
Nominal weight of cable (kg/km) 458
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 0.9
Bending radius
During handling and installation, cable (cm) 267
In final installation, cable (cm) 187
During handling and installation, cable (cm) 27
In final installation, cable (cm) 19
During handling and installation, cable (m) 0.27
In final installation, cable (m) 0.19
Pulling force
Pulling-eye (kN) 1.5
Pulling-stocking (kN) 1.5
Resistance 20 °C (ohm/km) 1.2
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 2.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300220
Reka code 1116041

4x35 S PoweRex PE

Electric number Size Packing (m) Voltage

4x35 S PoweRex PE

Nominal diameter of complete cable (mm) 22
Nominal weight of cable (kg/km) 571
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 0.9
Bending radius
During handling and installation, cable (cm) 266
In final installation, cable (cm) 186
During handling and installation, cable (cm) 27
In final installation, cable (cm) 19
During handling and installation, cable (m) 0.27
In final installation, cable (m) 0.19
Pulling force
Pulling-eye (kN) 2.1
Pulling-stocking (kN) 2.1
Resistance 20 °C (ohm/km) 0.868
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 3.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300251
Reka code 1116042
Nominal diameter of complete cable (mm) 22
Nominal weight of cable (kg/km) 571
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 0.9
Bending radius
During handling and installation, cable (cm) 266
In final installation, cable (cm) 186
During handling and installation, cable (cm) 27
In final installation, cable (cm) 19
During handling and installation, cable (m) 0.27
In final installation, cable (m) 0.19
Pulling force
Pulling-eye (kN) 2.1
Pulling-stocking (kN) 2.1
Resistance 20 °C (ohm/km) 0.868
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 3.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300244
Reka code 1116042

4x50 S PoweRex PE

Electric number Size Packing (m) Voltage

4x50 S PoweRex PE

Nominal diameter of complete cable (mm) 26
Nominal weight of cable (kg/km) 765
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 1
Bending radius
During handling and installation, cable (cm) 312
In final installation, cable (cm) 218
During handling and installation, cable (cm) 31
In final installation, cable (cm) 22
During handling and installation, cable (m) 0.31
In final installation, cable (m) 0.22
Pulling force
Pulling-eye (kN) 3
Pulling-stocking (kN) 3
Resistance 20 °C (ohm/km) 0.641
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 4.8
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300275
Reka code 1116043
Nominal diameter of complete cable (mm) 26
Nominal weight of cable (kg/km) 765
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 1
Bending radius
During handling and installation, cable (cm) 312
In final installation, cable (cm) 218
During handling and installation, cable (cm) 31
In final installation, cable (cm) 22
During handling and installation, cable (m) 0.31
In final installation, cable (m) 0.22
Pulling force
Pulling-eye (kN) 3
Pulling-stocking (kN) 3
Resistance 20 °C (ohm/km) 0.641
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 4.8
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300268
Reka code 1116043

4x70 S PoweRex PE

Electric number Size Packing (m) Voltage

4x70 S PoweRex PE

Nominal diameter of complete cable (mm) 29
Nominal weight of cable (kg/km) 1056
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 1.1
Bending radius
During handling and installation, cable (cm) 353
In final installation, cable (cm) 247
During handling and installation, cable (cm) 35
In final installation, cable (cm) 25
During handling and installation, cable (m) 0.35
In final installation, cable (m) 0.25
Pulling force
Pulling-eye (kN) 4.2
Pulling-stocking (kN) 4.2
Resistance 20 °C (ohm/km) 0.443
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 6.7
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300299
Reka code 1116044
Nominal diameter of complete cable (mm) 29
Nominal weight of cable (kg/km) 1056
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 1.1
Bending radius
During handling and installation, cable (cm) 353
In final installation, cable (cm) 247
During handling and installation, cable (cm) 35
In final installation, cable (cm) 25
During handling and installation, cable (m) 0.35
In final installation, cable (m) 0.25
Pulling force
Pulling-eye (kN) 4.2
Pulling-stocking (kN) 4.2
Resistance 20 °C (ohm/km) 0.443
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 6.7
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300282
Reka code 1116044

4x95 S PoweRex PE

Electric number Size Packing (m) Voltage

4x95 S PoweRex PE

Nominal diameter of complete cable (mm) 33
Nominal weight of cable (kg/km) 1385
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 1.1
Bending radius
During handling and installation, cable (cm) 394
In final installation, cable (cm) 276
During handling and installation, cable (cm) 39
In final installation, cable (cm) 28
During handling and installation, cable (m) 0.39
In final installation, cable (m) 0.28
Pulling force
Pulling-eye (kN) 5.7
Pulling-stocking (kN) 5.7
Resistance 20 °C (ohm/km) 0.32
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 9
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300312
Reka code 1116045
Nominal diameter of complete cable (mm) 33
Nominal weight of cable (kg/km) 1385
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 1.1
Bending radius
During handling and installation, cable (cm) 394
In final installation, cable (cm) 276
During handling and installation, cable (cm) 39
In final installation, cable (cm) 28
During handling and installation, cable (m) 0.39
In final installation, cable (m) 0.28
Pulling force
Pulling-eye (kN) 5.7
Pulling-stocking (kN) 5.7
Resistance 20 °C (ohm/km) 0.32
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 9
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300305
Reka code 1116045

4x120 S PoweRex PE

Electric number Size Packing (m) Voltage

4x120 S PoweRex PE

Nominal diameter of complete cable (mm) 38
Nominal weight of cable (kg/km) 1743
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 1.2
Bending radius
During handling and installation, cable (cm) 453
In final installation, cable (cm) 317
During handling and installation, cable (cm) 45
In final installation, cable (cm) 32
During handling and installation, cable (m) 0.45
In final installation, cable (m) 0.32
Pulling force
Pulling-eye (kN) 7.2
Pulling-stocking (kN) 7.2
Resistance 20 °C (ohm/km) 0.253
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 11.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300336
Reka code 1116046
Nominal diameter of complete cable (mm) 38
Nominal weight of cable (kg/km) 1743
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 1.2
Bending radius
During handling and installation, cable (cm) 453
In final installation, cable (cm) 317
During handling and installation, cable (cm) 45
In final installation, cable (cm) 32
During handling and installation, cable (m) 0.45
In final installation, cable (m) 0.32
Pulling force
Pulling-eye (kN) 7.2
Pulling-stocking (kN) 7.2
Resistance 20 °C (ohm/km) 0.253
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 11.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300329
Reka code 1116046

4x150 S PoweRex PE

Electric number Size Packing (m) Voltage

4x150 S PoweRex PE

Nominal diameter of complete cable (mm) 42
Nominal weight of cable (kg/km) 2138
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 1.4
Bending radius
During handling and installation, cable (cm) 501
In final installation, cable (cm) 351
During handling and installation, cable (cm) 50
In final installation, cable (cm) 35
During handling and installation, cable (m) 0.5
In final installation, cable (m) 0.35
Pulling force
Pulling-eye (kN) 9
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.206
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 14.2
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300343
Reka code 1116047

4x185 S PoweRex PE

Electric number Size Packing (m) Voltage

4x185 S PoweRex PE

Nominal diameter of complete cable (mm) 46
Nominal weight of cable (kg/km) 2608
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 1.6
Bending radius
During handling and installation, cable (cm) 553
In final installation, cable (cm) 387
During handling and installation, cable (cm) 55
In final installation, cable (cm) 39
During handling and installation, cable (m) 0.55
In final installation, cable (m) 0.39
Pulling force
Pulling-eye (kN) 11.1
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.164
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 17.5
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300350
Reka code 1116048

4x240 S PoweRex PE

Electric number Size Packing (m) Voltage

4x240 S PoweRex PE

Nominal diameter of complete cable (mm) 53
Nominal weight of cable (kg/km) 3447
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 1.7
Bending radius
During handling and installation, cable (cm) 635
In final installation, cable (cm) 444
During handling and installation, cable (cm) 63
In final installation, cable (cm) 44
During handling and installation, cable (m) 0.63
In final installation, cable (m) 0.44
Pulling force
Pulling-eye (kN) 14.4
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.125
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 22.6
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300367
Reka code 1116049

4x300 S PoweRex PE

Electric number Size Packing (m) Voltage

4x300 S PoweRex PE

Nominal diameter of complete cable (mm) 57
Nominal weight of cable (kg/km) 4174
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 1.8
Bending radius
During handling and installation, cable (cm) 680
In final installation, cable (cm) 476
During handling and installation, cable (cm) 68
In final installation, cable (cm) 48
During handling and installation, cable (m) 0.68
In final installation, cable (m) 0.48
Pulling force
Pulling-eye (kN) 18
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.1
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 28.2
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300374
Reka code 1116050