AXMK 1-core

Download product group datasheet

Aluminium power cable for fixed installations indoors and outdoors. May be buried directly in soil. Installations must be in accordance with national regulations and rules of installations. The cable is flame-retardant according to CPR-class Eca.

Standards SFS 4879, SS 424 14 18, HD 603 5 D & O
Reaction to fire Eca
CPR - DoP 2017037_DOP.pdf
Conductor Circular stranded aluminium, EN/IEC 60228 class 2
Insulation UV-protected XLPE
Core Identification (all color combinations in the cable family) black
Inner covering Plastic tape
Oversheath UV-protected PVC compound
Colour of the oversheath Black

1x300

Electric number Size Packaging Voltage

1x300

Nominal diameter of complete cable mm 28
Nominal weight of cable kg/km 1174
Conductor material Aluminum
Nominal cross-sectional area of conductor mm2 300
Nominal thickness of insulation mm 1.8
Number of wires 1
Min. bending radius
During handling and installation, cable mm 331
In final installation, cable mm 231
During handling and installation, cable cm 33
In final installation, cable cm 23
During handling and installation, cable m 0.33
In final installation, cable m 0.23
Max. pulling force
Pulling-eye kN 4.5
Pulling-stocking kN 4.5
Resistance 20 °C Ω/km 0.100
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006262007
Reka code 1116020
Nominal diameter of complete cable mm 28
Nominal weight of cable kg/km 1174
Conductor material Aluminum
Nominal cross-sectional area of conductor mm2 300
Nominal thickness of insulation mm 1.8
Number of wires 1
Min. bending radius
During handling and installation, cable mm 331
In final installation, cable mm 231
During handling and installation, cable cm 33
In final installation, cable cm 23
During handling and installation, cable m 0.33
In final installation, cable m 0.23
Max. pulling force
Pulling-eye kN 4.5
Pulling-stocking kN 4.5
Resistance 20 °C Ω/km 0.100
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006262021
Reka code 1116020