AXMK 1-core

Download product group datasheet

Aluminium power cable for fixed installations indoors and outdoors. The cable is not intended for underground installations. UV-protected oversheath and core insulation. Installations must be in accordance with national regulations and rules of installations. The cable is flame-retardant according to CPR-class Eca.

Standards SFS 4879, SS 424 14 18, HD 603 5 D & O
Reaction to fire Eca
CPR - DoP 2017037_DOP.pdf
Conductor Circular stranded aluminium, EN/IEC 60228 class 2
Insulation UV-protected cross-linked polyethylene XLPE
Core Identification (all color combinations in the cable family) Black
Yellowgreen, brown, black, grey
Yellowgreen, blue, brown, black, grey
Inner covering Plastic tape
Oversheath UV-protected PVC-compound
Colour of the oversheath Black

1x300

Electric number Size Packaging Voltage

1x300

Nominal diameter of complete cable mm 28
Nominal weight of cable kg/km 1174
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 300
Nominal thickness of insulation mm 1.8
Number of wires 1
Min. bending radius
During handling and installation, cable cm 42
In final installation, cable cm 29
During handling and installation, cable m 0.42
In final installation, cable m 0.29
Max. pulling force
Pulling-eye kN 4.5
Pulling-stocking kN 4.5
Resistance 20 °C Ω/km 0,100
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006262007
Reka code 1116020
Nominal diameter of complete cable mm 28
Nominal weight of cable kg/km 1174
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 300
Nominal thickness of insulation mm 1.8
Number of wires 1
Min. bending radius
During handling and installation, cable cm 42
In final installation, cable cm 29
During handling and installation, cable m 0.42
In final installation, cable m 0.29
Max. pulling force
Pulling-eye kN 4.5
Pulling-stocking kN 4.5
Resistance 20 °C Ω/km 0,100
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006262021
Reka code 1116020