AMCMK / AKKJ

Download product group datasheet

Aluminium power cable for fixed installations indoors and outdoors. May be buried directly in soil or cast concrete. Installations must be in accordance with national regulations and rules of installations. The cable is flame-retardant according to CPR-class Eca.

Standards SFS 4880, SS 424 14 18, HD 603 3 F & L
Reaction to fire Eca
CPR - DoP 2017081_DOP.pdf
2017080_DOP.pdf
Conductor 16 mm² circular solid aluminium, EN/IEC 60228 class 1
25 mm² circular stranded aluminium, EN/IEC 60228 class 2
35-300 mm² sector shaped, stranded aluminium, EN/IEC 60228 class 2
Insulation PVC-compound
Core Identification (all color combinations in the cable family) Brown, black, grey
Blue, brown, black, grey
Inner covering Plastic tape
Metal screen Copper wires and copper tape
Oversheath UV-protected PVC compound
Colour of the oversheath Black

3x16/10

Electric number Size Packaging Voltage

3x16/10

Nominal diameter of complete cable mm 19
Nominal weight of cable kg/km 439
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 16
Nominal thickness of insulation mm 1
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 10
During handling and installation, cable cm 23
In final installation, phase conductor cm 7
In final installation, cable cm 16
During handling and installation, cable m 0.23
In final installation, cable m 0.16
Max. pulling force
Pulling-eye kN 1.4
Pulling-stocking kN 0.7
Resistance 20 °C Ω/km 1,91
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,83
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223572
Reka code 1111210
Nominal diameter of complete cable mm 19
Nominal weight of cable kg/km 439
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 16
Nominal thickness of insulation mm 1
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 10
During handling and installation, cable cm 23
In final installation, phase conductor cm 7
In final installation, cable cm 16
During handling and installation, cable m 0.23
In final installation, cable m 0.16
Max. pulling force
Pulling-eye kN 1.4
Pulling-stocking kN 0.7
Resistance 20 °C Ω/km 1,91
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,83
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223473
Reka code 1111210

3x25/16

Electric number Size Packaging Voltage

3x25/16

Nominal diameter of complete cable mm 24
Nominal weight of cable kg/km 669
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 25
Nominal thickness of insulation mm 1.2
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 13
During handling and installation, cable cm 29
In final installation, phase conductor cm 9
In final installation, cable cm 20
During handling and installation, cable m 0.29
In final installation, cable m 0.2
Max. pulling force
Pulling-eye kN 1.1
Pulling-stocking kN 1.1
Resistance 20 °C Ω/km 1,20
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223480
Reka code 1111231
Nominal diameter of complete cable mm 24
Nominal weight of cable kg/km 669
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 25
Nominal thickness of insulation mm 1.2
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 13
During handling and installation, cable cm 29
In final installation, phase conductor cm 9
In final installation, cable cm 20
During handling and installation, cable m 0.29
In final installation, cable m 0.2
Max. pulling force
Pulling-eye kN 1.1
Pulling-stocking kN 1.1
Resistance 20 °C Ω/km 1,20
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223589
Reka code 1111231

3x35/16

Electric number Size Packaging Voltage

3x35/16

Nominal diameter of complete cable mm 24
Nominal weight of cable kg/km 763
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 35
Nominal thickness of insulation mm 1.2
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 18
During handling and installation, cable cm 28
In final installation, phase conductor cm 13
In final installation, cable cm 20
During handling and installation, cable m 0.28
In final installation, cable m 0.2
Max. pulling force
Pulling-eye kN 1.6
Pulling-stocking kN 1.6
Resistance 20 °C Ω/km 0,868
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223596
Reka code 1111312
Nominal diameter of complete cable mm 24
Nominal weight of cable kg/km 763
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 35
Nominal thickness of insulation mm 1.2
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 18
During handling and installation, cable cm 28
In final installation, phase conductor cm 13
In final installation, cable cm 20
During handling and installation, cable m 0.28
In final installation, cable m 0.2
Max. pulling force
Pulling-eye kN 1.6
Pulling-stocking kN 1.6
Resistance 20 °C Ω/km 0,868
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223497
Reka code 1111312

3x50/16

Electric number Size Packaging Voltage

3x50/16

Nominal diameter of complete cable mm 26
Nominal weight of cable kg/km 953
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 50
Nominal thickness of insulation mm 1.4
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 21
During handling and installation, cable cm 31
In final installation, phase conductor cm 15
In final installation, cable cm 22
During handling and installation, cable m 0.31
In final installation, cable m 0.22
Max. pulling force
Pulling-eye kN 2.3
Pulling-stocking kN 2.3
Resistance 20 °C Ω/km 0,641
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223602
Reka code 1111313
Nominal diameter of complete cable mm 26
Nominal weight of cable kg/km 953
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 50
Nominal thickness of insulation mm 1.4
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 21
During handling and installation, cable cm 31
In final installation, phase conductor cm 15
In final installation, cable cm 22
During handling and installation, cable m 0.31
In final installation, cable m 0.22
Max. pulling force
Pulling-eye kN 2.3
Pulling-stocking kN 2.3
Resistance 20 °C Ω/km 0,641
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223503
Reka code 1111313

3x70/21

Electric number Size Packaging Voltage

3x70/21

Nominal diameter of complete cable mm 29
Nominal weight of cable kg/km 1241
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 70
Nominal thickness of insulation mm 1.4
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 25
During handling and installation, cable cm 35
In final installation, phase conductor cm 17
In final installation, cable cm 24
During handling and installation, cable m 0.35
In final installation, cable m 0.24
Max. pulling force
Pulling-eye kN 3.2
Pulling-stocking kN 3.2
Resistance 20 °C Ω/km 0,443
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,868
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223619
Reka code 1111314
Nominal diameter of complete cable mm 29
Nominal weight of cable kg/km 1241
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 70
Nominal thickness of insulation mm 1.4
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 25
During handling and installation, cable cm 35
In final installation, phase conductor cm 17
In final installation, cable cm 24
During handling and installation, cable m 0.35
In final installation, cable m 0.24
Max. pulling force
Pulling-eye kN 3.2
Pulling-stocking kN 3.2
Resistance 20 °C Ω/km 0,443
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,868
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223510
Reka code 1111314

3x95/29

Electric number Size Packaging Voltage

3x95/29

Nominal diameter of complete cable mm 34
Nominal weight of cable kg/km 1683
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 95
Nominal thickness of insulation mm 1.6
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 29
During handling and installation, cable cm 41
In final installation, phase conductor cm 21
In final installation, cable cm 29
During handling and installation, cable m 0.41
In final installation, cable m 0.29
Max. pulling force
Pulling-eye kN 4.3
Pulling-stocking kN 4.3
Resistance 20 °C Ω/km 0,320
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,641
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223626
Reka code 1111315
Nominal diameter of complete cable mm 34
Nominal weight of cable kg/km 1683
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 95
Nominal thickness of insulation mm 1.6
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 29
During handling and installation, cable cm 41
In final installation, phase conductor cm 21
In final installation, cable cm 29
During handling and installation, cable m 0.41
In final installation, cable m 0.29
Max. pulling force
Pulling-eye kN 4.3
Pulling-stocking kN 4.3
Resistance 20 °C Ω/km 0,320
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,641
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223527
Reka code 1111315

3x120/41

Electric number Size Packaging Voltage

3x120/41

Nominal diameter of complete cable mm 38
Nominal weight of cable kg/km 2090
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 120
Nominal thickness of insulation mm 1.6
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 32
During handling and installation, cable cm 45
In final installation, phase conductor cm 23
In final installation, cable cm 32
During handling and installation, cable m 0.45
In final installation, cable m 0.32
Max. pulling force
Pulling-eye kN 5.4
Pulling-stocking kN 5.4
Resistance 20 °C Ω/km 0,253
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,443
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223633
Reka code 1111316
Nominal diameter of complete cable mm 38
Nominal weight of cable kg/km 2090
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 120
Nominal thickness of insulation mm 1.6
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 32
During handling and installation, cable cm 45
In final installation, phase conductor cm 23
In final installation, cable cm 32
During handling and installation, cable m 0.45
In final installation, cable m 0.32
Max. pulling force
Pulling-eye kN 5.4
Pulling-stocking kN 5.4
Resistance 20 °C Ω/km 0,253
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,443
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223534
Reka code 1111316

3x150/41

Electric number Size Packaging Voltage

3x150/41

Nominal diameter of complete cable mm 41
Nominal weight of cable kg/km 2450
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 150
Nominal thickness of insulation mm 1.8
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 36
During handling and installation, cable cm 49
In final installation, phase conductor cm 25
In final installation, cable cm 34
During handling and installation, cable m 0.49
In final installation, cable m 0.34
Max. pulling force
Pulling-eye kN 6.8
Pulling-stocking kN 6.8
Resistance 20 °C Ω/km 0,206
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,443
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223565
Reka code 1111317
Nominal diameter of complete cable mm 41
Nominal weight of cable kg/km 2450
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 150
Nominal thickness of insulation mm 1.8
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 36
During handling and installation, cable cm 49
In final installation, phase conductor cm 25
In final installation, cable cm 34
During handling and installation, cable m 0.49
In final installation, cable m 0.34
Max. pulling force
Pulling-eye kN 6.8
Pulling-stocking kN 6.8
Resistance 20 °C Ω/km 0,206
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,443
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223640
Reka code 1111317

3x185/57

Electric number Size Packaging Voltage

3x185/57

Nominal diameter of complete cable mm 45
Nominal weight of cable kg/km 3048
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 185
Nominal thickness of insulation mm 2
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 39
During handling and installation, cable cm 54
In final installation, phase conductor cm 28
In final installation, cable cm 38
During handling and installation, cable m 0.54
In final installation, cable m 0.38
Max. pulling force
Pulling-eye kN 8.3
Pulling-stocking kN 8.3
Resistance 20 °C Ω/km 0,164
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,320
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223657
Reka code 1111318

3x240/72

Electric number Size Packaging Voltage

3x240/72

Nominal diameter of complete cable mm 51
Nominal weight of cable kg/km 3933
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 240
Nominal thickness of insulation mm 2.2
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 45
During handling and installation, cable cm 61
In final installation, phase conductor cm 31
In final installation, cable cm 43
During handling and installation, cable m 0.61
In final installation, cable m 0.43
Max. pulling force
Pulling-eye kN 10.8
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,125
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,253
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223664
Reka code 1111319

3x300/88

Electric number Size Packaging Voltage

3x300/88

Nominal diameter of complete cable mm 55
Nominal weight of cable kg/km 4802
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 300
Nominal thickness of insulation mm 2.4
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 51
During handling and installation, cable cm 66
In final installation, phase conductor cm 36
In final installation, cable cm 46
During handling and installation, cable m 0.66
In final installation, cable m 0.47
Max. pulling force
Pulling-eye kN 13.5
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,100
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,206
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223671
Reka code 1111320

4x16/10

Electric number Size Packaging Voltage

4x16/10

Nominal diameter of complete cable mm 21
Nominal weight of cable kg/km 520
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 16
Nominal thickness of insulation mm 1
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 10
During handling and installation, cable cm 25
In final installation, phase conductor cm 7
In final installation, cable cm 17
During handling and installation, cable m 0.25
In final installation, cable m 0.17
Max. pulling force
Pulling-eye kN 1.9
Pulling-stocking kN 1
Resistance 20 °C Ω/km 1,91
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,83
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223374
Reka code 1111410

4x25/16

Electric number Size Packaging Voltage

4x25/16

Nominal diameter of complete cable mm 26
Nominal weight of cable kg/km 798
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 25
Nominal thickness of insulation mm 1.2
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 13
During handling and installation, cable cm 31
In final installation, phase conductor cm 9
In final installation, cable cm 22
During handling and installation, cable m 0.31
In final installation, cable m 0.22
Max. pulling force
Pulling-eye kN 1.5
Pulling-stocking kN 1.5
Resistance 20 °C Ω/km 1,20
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223381
Reka code 1111411

4x35/16

Electric number Size Packaging Voltage

4x35/16

Nominal diameter of complete cable mm 26
Nominal weight of cable kg/km 929
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 35
Nominal thickness of insulation mm 1.2
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 17
During handling and installation, cable cm 31
In final installation, phase conductor cm 12
In final installation, cable cm 22
During handling and installation, cable m 0.31
In final installation, cable m 0.22
Max. pulling force
Pulling-eye kN 2.1
Pulling-stocking kN 2.1
Resistance 20 °C Ω/km 0,868
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223794
Reka code 1111412
Nominal diameter of complete cable mm 26
Nominal weight of cable kg/km 929
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 35
Nominal thickness of insulation mm 1.2
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 17
During handling and installation, cable cm 31
In final installation, phase conductor cm 12
In final installation, cable cm 22
During handling and installation, cable m 0.31
In final installation, cable m 0.22
Max. pulling force
Pulling-eye kN 2.1
Pulling-stocking kN 2.1
Resistance 20 °C Ω/km 0,868
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223688
Reka code 1111412

4x50/16

Electric number Size Packaging Voltage

4x50/16

Nominal diameter of complete cable mm 30
Nominal weight of cable kg/km 1203
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 50
Nominal thickness of insulation mm 1.4
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 20
During handling and installation, cable cm 36
In final installation, phase conductor cm 14
In final installation, cable cm 25
During handling and installation, cable m 0.36
In final installation, cable m 0.25
Max. pulling force
Pulling-eye kN 3
Pulling-stocking kN 3
Resistance 20 °C Ω/km 0,641
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223404
Reka code 1111413
Nominal diameter of complete cable mm 30
Nominal weight of cable kg/km 1203
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 50
Nominal thickness of insulation mm 1.4
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 20
During handling and installation, cable cm 36
In final installation, phase conductor cm 14
In final installation, cable cm 25
During handling and installation, cable m 0.36
In final installation, cable m 0.25
Max. pulling force
Pulling-eye kN 3
Pulling-stocking kN 3
Resistance 20 °C Ω/km 0,641
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223367
Reka code 1111413

4x70/21

Electric number Size Packaging Voltage

4x70/21

Nominal diameter of complete cable mm 33
Nominal weight of cable kg/km 1572
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 70
Nominal thickness of insulation mm 1.4
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 24
During handling and installation, cable cm 40
In final installation, phase conductor cm 17
In final installation, cable cm 28
During handling and installation, cable m 0.4
In final installation, cable m 0.28
Max. pulling force
Pulling-eye kN 4.2
Pulling-stocking kN 4.2
Resistance 20 °C Ω/km 0,443
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,868
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223817
Reka code 1111414
Nominal diameter of complete cable mm 33
Nominal weight of cable kg/km 1572
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 70
Nominal thickness of insulation mm 1.4
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 24
During handling and installation, cable cm 40
In final installation, phase conductor cm 17
In final installation, cable cm 28
During handling and installation, cable m 0.4
In final installation, cable m 0.28
Max. pulling force
Pulling-eye kN 4.2
Pulling-stocking kN 4.2
Resistance 20 °C Ω/km 0,443
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,868
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223800
Reka code 1111414

4x95/29

Electric number Size Packaging Voltage

4x95/29

Nominal diameter of complete cable mm 38
Nominal weight of cable kg/km 2105
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 95
Nominal thickness of insulation mm 1.6
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 28
During handling and installation, cable cm 46
In final installation, phase conductor cm 19
In final installation, cable cm 32
During handling and installation, cable m 0.46
In final installation, cable m 0.32
Max. pulling force
Pulling-eye kN 5.7
Pulling-stocking kN 5.7
Resistance 20 °C Ω/km 0,320
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,641
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223541
Reka code 1111415
Nominal diameter of complete cable mm 38
Nominal weight of cable kg/km 2105
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 95
Nominal thickness of insulation mm 1.6
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 28
During handling and installation, cable cm 46
In final installation, phase conductor cm 19
In final installation, cable cm 32
During handling and installation, cable m 0.46
In final installation, cable m 0.32
Max. pulling force
Pulling-eye kN 5.7
Pulling-stocking kN 5.7
Resistance 20 °C Ω/km 0,320
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,641
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223824
Reka code 1111415

4x120/41

Electric number Size Packaging Voltage

4x120/41

Nominal diameter of complete cable mm 42
Nominal weight of cable kg/km 2577
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 120
Nominal thickness of insulation mm 1.6
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 30
During handling and installation, cable cm 50
In final installation, phase conductor cm 21
In final installation, cable cm 35
During handling and installation, cable m 0.5
In final installation, cable m 0.35
Max. pulling force
Pulling-eye kN 7.2
Pulling-stocking kN 7.2
Resistance 20 °C Ω/km 0,253
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,443
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223831
Reka code 1111416

4x150/41

Electric number Size Packaging Voltage

4x150/41

Nominal diameter of complete cable mm 47
Nominal weight of cable kg/km 3093
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 150
Nominal thickness of insulation mm 1.8
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 34
During handling and installation, cable cm 56
In final installation, phase conductor cm 23
In final installation, cable cm 39
During handling and installation, cable m 0.56
In final installation, cable m 0.39
Max. pulling force
Pulling-eye kN 9
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,206
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,443
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223848
Reka code 1111417

4x185/57

Electric number Size Packaging Voltage

4x185/57

Nominal diameter of complete cable mm 51
Nominal weight of cable kg/km 3798
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 185
Nominal thickness of insulation mm 2
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 38
During handling and installation, cable cm 61
In final installation, phase conductor cm 27
In final installation, cable cm 43
During handling and installation, cable m 0.61
In final installation, cable m 0.43
Max. pulling force
Pulling-eye kN 11.1
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,164
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,320
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223855
Reka code 1111418

4x240/72

Electric number Size Packaging Voltage

4x240/72

Nominal diameter of complete cable mm 58
Nominal weight of cable kg/km 4958
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 240
Nominal thickness of insulation mm 2.2
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 44
During handling and installation, cable cm 69
In final installation, phase conductor cm 31
In final installation, cable cm 49
During handling and installation, cable m 0.69
In final installation, cable m 0.49
Max. pulling force
Pulling-eye kN 14.4
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,125
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,253
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223862
Reka code 1111419

4x300/88

Electric number Size Packaging Voltage

4x300/88

Nominal diameter of complete cable mm 64
Nominal weight of cable kg/km 6062
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 300
Nominal thickness of insulation mm 2.4
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 48
During handling and installation, cable cm 76
In final installation, phase conductor cm 33
In final installation, cable cm 53
During handling and installation, cable m 0.76
In final installation, cable m 0.53
Max. pulling force
Pulling-eye kN 18
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,100
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,206
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223879
Reka code 1111420
Nominal diameter of complete cable mm 64
Nominal weight of cable kg/km 6062
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 300
Nominal thickness of insulation mm 2.4
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 48
During handling and installation, cable cm 76
In final installation, phase conductor cm 33
In final installation, cable cm 53
During handling and installation, cable m 0.76
In final installation, cable m 0.53
Max. pulling force
Pulling-eye kN 18
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,100
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,206
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6410006223886
Reka code 1111420