AXMK/PE LC Low Carbon

Download product group datasheet

Aluminium power cable for fixed installations outdoors. May be buried directly in soil, also by ploughing. UV-protected oversheath and core insulation. Installations must be in accordance with national regulations and rules of installations. The cable is halogen-free, but without fire protection. The cable is not CPR-classified. Made of low-carbon aluminum and up to 45% of the sheath material is recycled plastic.

Standards SFS 5800, HD 603 5 E
Product Environmental Profile (PEP) PEP NXNS-00650-V0101-EN.pdf
Conductor 25 mm² circular stranded aluminium, EN/IEC 60228 class 2
35-300 mm² sector shaped, stranded aluminium, EN/IEC 60228 class 2
Insulation UV-protected cross-linked polyethylene XLPE
Core Identification (all color combinations in the cable family) Yellow-green, brown, black, grey
Inner covering Plastic tape
Oversheath UV-protected polyethylene compound PELLD
Colour of the oversheath Black

4x25 S Low Carbon

Electric number Size Packaging Voltage

4x25 S Low Carbon

Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 25
Nominal thickness of insulation mm 0.9
Number of wires 4
Min. bending radius
During handling and installation, cable mm 267
In final installation, cable mm 187
During handling and installation, phase conductor cm 13
During handling and installation, cable cm 27
In final installation, phase conductor cm 8
In final installation, cable cm 19
During handling and installation, cable m 0.27
In final installation, cable m 0.19
Max. pulling force
Pulling-eye kN 1.5
Pulling-stocking kN 1.5
Resistance 20 °C Ω/km 1,20
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176310052
Reka code 1116150

4x35 S Low Carbon

Electric number Size Packaging Voltage

4x35 S Low Carbon

Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 35
Nominal thickness of insulation mm 0.9
Number of wires 4
Min. bending radius
During handling and installation, cable mm 266
In final installation, cable mm 186
During handling and installation, phase conductor cm 16
During handling and installation, cable cm 27
In final installation, phase conductor cm 11
In final installation, cable cm 19
During handling and installation, cable m 0.27
In final installation, cable m 0.19
Max. pulling force
Pulling-eye kN 2.1
Pulling-stocking kN 2.1
Resistance 20 °C Ω/km 0,868
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176310069
Reka code 1116151

4x50 S Low Carbon

Electric number Size Packaging Voltage

4x50 S Low Carbon

Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 50
Nominal thickness of insulation mm 1
Number of wires 4
Min. bending radius
During handling and installation, cable mm 312
In final installation, cable mm 218
During handling and installation, phase conductor cm 19
During handling and installation, cable cm 31
In final installation, phase conductor cm 13
In final installation, cable cm 22
During handling and installation, cable m 0.31
In final installation, cable m 0.22
Max. pulling force
Pulling-eye kN 3
Pulling-stocking kN 3
Resistance 20 °C Ω/km 0,641
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176310076
Reka code 1116152

4x70 S Low Carbon

Electric number Size Packaging Voltage

4x70 S Low Carbon

Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 70
Nominal thickness of insulation mm 1.1
Number of wires 4
Min. bending radius
During handling and installation, cable mm 350
In final installation, cable mm 245
During handling and installation, phase conductor cm 23
During handling and installation, cable cm 35
In final installation, phase conductor cm 16
In final installation, cable cm 25
During handling and installation, cable m 0.35
In final installation, cable m 0.24
Max. pulling force
Pulling-eye kN 4.2
Pulling-stocking kN 4.2
Resistance 20 °C Ω/km 0,443
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176310083
Reka code 1116153

4x95 S Low Carbon

Electric number Size Packaging Voltage

4x95 S Low Carbon

Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 95
Nominal thickness of insulation mm 1.1
Number of wires 4
Min. bending radius
During handling and installation, cable mm 400
In final installation, cable mm 280
During handling and installation, phase conductor cm 26
During handling and installation, cable cm 40
In final installation, phase conductor cm 18
In final installation, cable cm 28
During handling and installation, cable m 0.4
In final installation, cable m 0.28
Max. pulling force
Pulling-eye kN 5.7
Pulling-stocking kN 5.7
Resistance 20 °C Ω/km 0,320
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176310090
Reka code 1116154

4x120 S Low Carbon

Electric number Size Packaging Voltage

4x120 S Low Carbon

Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 120
Nominal thickness of insulation mm 1.2
Number of wires 4
Min. bending radius
During handling and installation, cable mm 450
In final installation, cable mm 315
During handling and installation, phase conductor cm 29
During handling and installation, cable cm 45
In final installation, phase conductor cm 20
In final installation, cable cm 32
During handling and installation, cable m 0.45
In final installation, cable m 0.32
Max. pulling force
Pulling-eye kN 7.2
Pulling-stocking kN 7.2
Resistance 20 °C Ω/km 0,253
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176310106
Reka code 1116155

4x150 S Low Carbon

Electric number Size Packaging Voltage

4x150 S Low Carbon

Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 150
Nominal thickness of insulation mm 1.4
Number of wires 4
Min. bending radius
During handling and installation, cable mm 499
In final installation, cable mm 349
During handling and installation, phase conductor cm 32
During handling and installation, cable cm 50
In final installation, phase conductor cm 23
In final installation, cable cm 35
During handling and installation, cable m 0.5
In final installation, cable m 0.35
Max. pulling force
Pulling-eye kN 9
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,206
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176310113
Reka code 1116156

4x185 S Low Carbon

Electric number Size Packaging Voltage

4x185 S Low Carbon

Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 185
Nominal thickness of insulation mm 1.6
Number of wires 4
Min. bending radius
During handling and installation, cable mm 547
In final installation, cable mm 383
During handling and installation, phase conductor cm 37
During handling and installation, cable cm 55
In final installation, phase conductor cm 26
In final installation, cable cm 38
During handling and installation, cable m 0.55
In final installation, cable m 0.38
Max. pulling force
Pulling-eye kN 11.1
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,164
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176310120
Reka code 1116157

4x240 S Low Carbon

Electric number Size Packaging Voltage

4x240 S Low Carbon

Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 240
Nominal thickness of insulation mm 1.7
Number of wires 4
Min. bending radius
During handling and installation, cable mm 633
In final installation, cable mm 443
During handling and installation, phase conductor cm 43
During handling and installation, cable cm 63
In final installation, phase conductor cm 30
In final installation, cable cm 44
During handling and installation, cable m 0.63
In final installation, cable m 0.44
Max. pulling force
Pulling-eye kN 14.4
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,125
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176310137
Reka code 1116158

4x300 S Low Carbon

Electric number Size Packaging Voltage

4x300 S Low Carbon

Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 300
Nominal thickness of insulation mm 1.8
Number of wires 4
Min. bending radius
During handling and installation, cable mm 678
In final installation, cable mm 474
During handling and installation, phase conductor cm 46
During handling and installation, cable cm 68
In final installation, phase conductor cm 32
In final installation, cable cm 47
During handling and installation, cable m 0.68
In final installation, cable m 0.47
Max. pulling force
Pulling-eye kN 18
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,100
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176310144
Reka code 1116159