XCMK-HF / FXQJ / IFSI-Cu
Download product group datasheet
Copper power cable for fixed installations indoors and outdoors. May be buried directly in soil. The conductor insulation must be protected against UV-radiation. Installations must be in accordance with national regulations and rules of installations. The cable is halogen-free and flame-retardant according to CPR-class Dca-s2,d2,a2.
| Standards | SFS 5546, SEK TS 424 14 18-1, HD 604 5 I & D, IEC 60502-1 |
|---|---|
| Reaction to fire | Dca-s2,d2,a2 |
| CPR - DoP | 2021012_DOP.pdf 2021003_DOP.pdf |
| Product Environmental Profile (PEP) | PEP NXNS-00665-V01.01-EN.pdf PEP NXNS-00666-V01.01-EN.pdf |
| Conductor | 2,5-25 mm² circular stranded copper, EN/IEC 60228 class 2 35-300 mm² sector shaped stranded copper, EN/IEC 60228 class 2 |
| Insulation | Cross-linked polyethylene XLPE |
| Core Identification (all color combinations in the cable family) | Blue, brown Brown, black, grey Blue, brown, black, grey |
| Inner covering | Plastic tape |
| Metal screen | Copper wires and copper tape |
| Oversheath | UV-protected polyolefin compound |
| Colour of the oversheath | Black |
2x10/10
Electric number
Size
Packaging
Voltage
2x10/10
Nominal diameter of complete cable mm
18
Nominal weight of cable kg/km
563
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
10
Nominal thickness of insulation mm
0.7
Number of wires
2
Min. bending radius
During handling and installation, cable mm
211
In final installation, cable mm
148
During handling and installation, cable cm
21
In final installation, cable cm
15
During handling and installation, cable m
0.21
In final installation, cable m
0.15
Max. pulling force
Pulling-eye kN
1
Pulling-stocking kN
0.3
Resistance 20 °C Ω/km
1,83
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,83
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006029914
Reka code
1146109
Nominal diameter of complete cable mm
18
Nominal weight of cable kg/km
563
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
10
Nominal thickness of insulation mm
0.7
Number of wires
2
Min. bending radius
During handling and installation, cable mm
211
In final installation, cable mm
148
During handling and installation, cable cm
21
In final installation, cable cm
15
During handling and installation, cable m
0.21
In final installation, cable m
0.15
Max. pulling force
Pulling-eye kN
1
Pulling-stocking kN
0.3
Resistance 20 °C Ω/km
1,83
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,83
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176011645
Reka code
1146109
2x16/16
Electric number
Size
Packaging
Voltage
2x16/16
Nominal diameter of complete cable mm
20
Nominal weight of cable kg/km
821
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
16
Nominal thickness of insulation mm
0.7
Number of wires
2
Min. bending radius
During handling and installation, cable mm
246
In final installation, cable mm
172
During handling and installation, cable cm
25
In final installation, cable cm
17
During handling and installation, cable m
0.25
In final installation, cable m
0.17
Max. pulling force
Pulling-eye kN
1.6
Pulling-stocking kN
0.5
Resistance 20 °C Ω/km
1,15
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176011652
Reka code
1146110
Nominal diameter of complete cable mm
20
Nominal weight of cable kg/km
821
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
16
Nominal thickness of insulation mm
0.7
Number of wires
2
Min. bending radius
During handling and installation, cable mm
246
In final installation, cable mm
172
During handling and installation, cable cm
25
In final installation, cable cm
17
During handling and installation, cable m
0.25
In final installation, cable m
0.17
Max. pulling force
Pulling-eye kN
1.6
Pulling-stocking kN
0.5
Resistance 20 °C Ω/km
1,15
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006029921
Reka code
1146110
2x25/16
Electric number
Size
Packaging
Voltage
2x25/16
Nominal diameter of complete cable mm
24
Nominal weight of cable kg/km
1130
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
25
Nominal thickness of insulation mm
0.9
Number of wires
2
Min. bending radius
During handling and installation, cable mm
288
In final installation, cable mm
201
During handling and installation, cable cm
29
In final installation, cable cm
20
During handling and installation, cable m
0.29
In final installation, cable m
0.2
Max. pulling force
Pulling-eye kN
2.5
Pulling-stocking kN
0.8
Resistance 20 °C Ω/km
0,727
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176011669
Reka code
1146111
2x35/16
Electric number
Size
Packaging
Voltage
2x35/16
Nominal diameter of complete cable mm
25
Nominal weight of cable kg/km
1274
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
35
Nominal thickness of insulation mm
0.9
Number of wires
2
Min. bending radius
During handling and installation, cable mm
300
In final installation, cable mm
210
During handling and installation, cable cm
30
In final installation, cable cm
21
During handling and installation, cable m
0.3
In final installation, cable m
0.21
Max. pulling force
Pulling-eye kN
3.5
Pulling-stocking kN
1.1
Resistance 20 °C Ω/km
0,524
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176011676
Reka code
1146112
3x10/10
Electric number
Size
Packaging
Voltage
3x10/10
Nominal diameter of complete cable mm
18
Nominal weight of cable kg/km
651
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
10
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable mm
221
In final installation, cable mm
155
During handling and installation, cable cm
22
In final installation, cable cm
15
During handling and installation, cable m
0.22
In final installation, cable m
0.15
Max. pulling force
Pulling-eye kN
1.5
Pulling-stocking kN
0.5
Resistance 20 °C Ω/km
1,83
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,83
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023684
Reka code
1146229
Nominal diameter of complete cable mm
18
Nominal weight of cable kg/km
651
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
10
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable mm
221
In final installation, cable mm
155
During handling and installation, cable cm
22
In final installation, cable cm
15
During handling and installation, cable m
0.22
In final installation, cable m
0.15
Max. pulling force
Pulling-eye kN
1.5
Pulling-stocking kN
0.5
Resistance 20 °C Ω/km
1,83
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,83
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023349
Reka code
1146229
3x16/16
Electric number
Size
Packaging
Voltage
3x16/16
Nominal diameter of complete cable mm
21
Nominal weight of cable kg/km
952
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
16
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable mm
258
In final installation, cable mm
180
During handling and installation, cable cm
26
In final installation, cable cm
18
During handling and installation, cable m
0.26
In final installation, cable m
0.18
Max. pulling force
Pulling-eye kN
2.4
Pulling-stocking kN
0.7
Resistance 20 °C Ω/km
1,15
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023387
Reka code
1146230
Nominal diameter of complete cable mm
21
Nominal weight of cable kg/km
952
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
16
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable mm
258
In final installation, cable mm
180
During handling and installation, cable cm
26
In final installation, cable cm
18
During handling and installation, cable m
0.26
In final installation, cable m
0.18
Max. pulling force
Pulling-eye kN
2.4
Pulling-stocking kN
0.7
Resistance 20 °C Ω/km
1,15
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023394
Reka code
1146230
3x25/16
Electric number
Size
Packaging
Voltage
3x25/16
Nominal diameter of complete cable mm
25
Nominal weight of cable kg/km
1313
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
25
Nominal thickness of insulation mm
0.9
Number of wires
3
Min. bending radius
During handling and installation, cable mm
305
In final installation, cable mm
213
During handling and installation, cable cm
30
In final installation, cable cm
21
During handling and installation, cable m
0.3
In final installation, cable m
0.21
Max. pulling force
Pulling-eye kN
3.8
Pulling-stocking kN
1.1
Resistance 20 °C Ω/km
0,727
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023400
Reka code
1146231
Nominal diameter of complete cable mm
25
Nominal weight of cable kg/km
1313
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
25
Nominal thickness of insulation mm
0.9
Number of wires
3
Min. bending radius
During handling and installation, cable mm
305
In final installation, cable mm
213
During handling and installation, cable cm
30
In final installation, cable cm
21
During handling and installation, cable m
0.3
In final installation, cable m
0.21
Max. pulling force
Pulling-eye kN
3.8
Pulling-stocking kN
1.1
Resistance 20 °C Ω/km
0,727
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023417
Reka code
1146231
3x35/16
Electric number
Size
Packaging
Voltage
3x35/16
Nominal diameter of complete cable mm
23
Nominal weight of cable kg/km
1328
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
35
Nominal thickness of insulation mm
0.9
Number of wires
3
Min. bending radius
During handling and installation, cable mm
277
In final installation, cable mm
194
During handling and installation, cable cm
28
In final installation, cable cm
19
During handling and installation, cable m
0.28
In final installation, cable m
0.19
Max. pulling force
Pulling-eye kN
5.3
Pulling-stocking kN
1.6
Resistance 20 °C Ω/km
0,524
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023424
Reka code
1146232
Nominal diameter of complete cable mm
23
Nominal weight of cable kg/km
1328
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
35
Nominal thickness of insulation mm
0.9
Number of wires
3
Min. bending radius
During handling and installation, cable mm
277
In final installation, cable mm
194
During handling and installation, cable cm
28
In final installation, cable cm
19
During handling and installation, cable m
0.28
In final installation, cable m
0.19
Max. pulling force
Pulling-eye kN
5.3
Pulling-stocking kN
1.6
Resistance 20 °C Ω/km
0,524
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023431
Reka code
1146232
3x50/25
Electric number
Size
Packaging
Voltage
3x50/25
Nominal diameter of complete cable mm
26
Nominal weight of cable kg/km
1815
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
50
Nominal thickness of insulation mm
1
Number of wires
3
Min. bending radius
During handling and installation, cable mm
316
In final installation, cable mm
221
During handling and installation, cable cm
32
In final installation, cable cm
22
During handling and installation, cable m
0.32
In final installation, cable m
0.22
Max. pulling force
Pulling-eye kN
7.5
Pulling-stocking kN
2.3
Resistance 20 °C Ω/km
0,387
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,727
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023448
Reka code
1146233
Nominal diameter of complete cable mm
26
Nominal weight of cable kg/km
1815
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
50
Nominal thickness of insulation mm
1
Number of wires
3
Min. bending radius
During handling and installation, cable mm
316
In final installation, cable mm
221
During handling and installation, cable cm
32
In final installation, cable cm
22
During handling and installation, cable m
0.32
In final installation, cable m
0.22
Max. pulling force
Pulling-eye kN
7.5
Pulling-stocking kN
2.3
Resistance 20 °C Ω/km
0,387
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,727
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023455
Reka code
1146233
3x120/70
Electric number
Size
Packaging
Voltage
3x120/70
Nominal diameter of complete cable mm
37
Nominal weight of cable kg/km
4304
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
120
Nominal thickness of insulation mm
1.2
Number of wires
3
Min. bending radius
During handling and installation, cable mm
440
In final installation, cable mm
308
During handling and installation, cable cm
44
In final installation, cable cm
31
During handling and installation, cable m
0.44
In final installation, cable m
0.31
Max. pulling force
Pulling-eye kN
18
Pulling-stocking kN
5.4
Resistance 20 °C Ω/km
0,153
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,268
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023509
Reka code
1146236
Nominal diameter of complete cable mm
37
Nominal weight of cable kg/km
4304
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
120
Nominal thickness of insulation mm
1.2
Number of wires
3
Min. bending radius
During handling and installation, cable mm
440
In final installation, cable mm
308
During handling and installation, cable cm
44
In final installation, cable cm
31
During handling and installation, cable m
0.44
In final installation, cable m
0.31
Max. pulling force
Pulling-eye kN
18
Pulling-stocking kN
5.4
Resistance 20 °C Ω/km
0,153
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,268
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023516
Reka code
1146236
3x150/70
Electric number
Size
Packaging
Voltage
3x150/70
Nominal diameter of complete cable mm
41
Nominal weight of cable kg/km
5189
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
150
Nominal thickness of insulation mm
1.4
Number of wires
3
Min. bending radius
During handling and installation, cable mm
492
In final installation, cable mm
344
During handling and installation, cable cm
49
In final installation, cable cm
34
During handling and installation, cable m
0.49
In final installation, cable m
0.34
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
6.8
Resistance 20 °C Ω/km
0,124
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,268
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023561
Reka code
1146237
Nominal diameter of complete cable mm
41
Nominal weight of cable kg/km
5189
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
150
Nominal thickness of insulation mm
1.4
Number of wires
3
Min. bending radius
During handling and installation, cable mm
492
In final installation, cable mm
344
During handling and installation, cable cm
49
In final installation, cable cm
34
During handling and installation, cable m
0.49
In final installation, cable m
0.34
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
6.8
Resistance 20 °C Ω/km
0,124
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,268
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023523
Reka code
1146237
3x185/95
Electric number
Size
Packaging
Voltage
3x185/95
Nominal diameter of complete cable mm
45
Nominal weight of cable kg/km
6550
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
185
Nominal thickness of insulation mm
1.6
Number of wires
3
Min. bending radius
During handling and installation, cable mm
544
In final installation, cable mm
381
During handling and installation, cable cm
54
In final installation, cable cm
38
During handling and installation, cable m
0.54
In final installation, cable m
0.38
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
8.3
Resistance 20 °C Ω/km
0,0991
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,193
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023585
Reka code
1146238
Nominal diameter of complete cable mm
45
Nominal weight of cable kg/km
6550
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
185
Nominal thickness of insulation mm
1.6
Number of wires
3
Min. bending radius
During handling and installation, cable mm
544
In final installation, cable mm
381
During handling and installation, cable cm
54
In final installation, cable cm
38
During handling and installation, cable m
0.54
In final installation, cable m
0.38
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
8.3
Resistance 20 °C Ω/km
0,0991
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,193
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023578
Reka code
1146238
3x240/120
Electric number
Size
Packaging
Voltage
3x240/120
Nominal diameter of complete cable mm
53
Nominal weight of cable kg/km
8551
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
240
Nominal thickness of insulation mm
1.7
Number of wires
3
Min. bending radius
During handling and installation, cable mm
635
In final installation, cable mm
444
During handling and installation, cable cm
63
In final installation, cable cm
44
During handling and installation, cable m
0.64
In final installation, cable m
0.44
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,0754
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,153
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023608
Reka code
1146239
Nominal diameter of complete cable mm
53
Nominal weight of cable kg/km
8551
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
240
Nominal thickness of insulation mm
1.7
Number of wires
3
Min. bending radius
During handling and installation, cable mm
635
In final installation, cable mm
444
During handling and installation, cable cm
63
In final installation, cable cm
44
During handling and installation, cable m
0.64
In final installation, cable m
0.44
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,0754
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,153
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023592
Reka code
1146239
4x10/10
Electric number
Size
Packaging
Voltage
4x10/10
Nominal diameter of complete cable mm
20
Nominal weight of cable kg/km
801
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
10
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable mm
244
In final installation, cable mm
171
During handling and installation, cable cm
24
In final installation, cable cm
17
During handling and installation, cable m
0.24
In final installation, cable m
0.17
Max. pulling force
Pulling-eye kN
2
Pulling-stocking kN
0.6
Resistance 20 °C Ω/km
1,83
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,83
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023226
Reka code
1146309
Nominal diameter of complete cable mm
20
Nominal weight of cable kg/km
801
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
10
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable mm
244
In final installation, cable mm
171
During handling and installation, cable cm
24
In final installation, cable cm
17
During handling and installation, cable m
0.24
In final installation, cable m
0.17
Max. pulling force
Pulling-eye kN
2
Pulling-stocking kN
0.6
Resistance 20 °C Ω/km
1,83
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,83
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023233
Reka code
1146309
4x16/16
Electric number
Size
Packaging
Voltage
4x16/16
Nominal diameter of complete cable mm
23
Nominal weight of cable kg/km
1137
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
16
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable mm
278
In final installation, cable mm
194
During handling and installation, cable cm
28
In final installation, cable cm
19
During handling and installation, cable m
0.28
In final installation, cable m
0.19
Max. pulling force
Pulling-eye kN
3.2
Pulling-stocking kN
1
Resistance 20 °C Ω/km
1,15
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023271
Reka code
1146310
Nominal diameter of complete cable mm
23
Nominal weight of cable kg/km
1137
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
16
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable mm
278
In final installation, cable mm
194
During handling and installation, cable cm
28
In final installation, cable cm
19
During handling and installation, cable m
0.28
In final installation, cable m
0.19
Max. pulling force
Pulling-eye kN
3.2
Pulling-stocking kN
1
Resistance 20 °C Ω/km
1,15
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023240
Reka code
1146310
4x25/16
Electric number
Size
Packaging
Voltage
4x25/16
Nominal diameter of complete cable mm
28
Nominal weight of cable kg/km
1590
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
25
Nominal thickness of insulation mm
0.9
Number of wires
4
Min. bending radius
During handling and installation, cable mm
330
In final installation, cable mm
231
During handling and installation, cable cm
33
In final installation, cable cm
23
During handling and installation, cable m
0.33
In final installation, cable m
0.23
Max. pulling force
Pulling-eye kN
5
Pulling-stocking kN
1.5
Resistance 20 °C Ω/km
0,727
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023264
Reka code
1146311
Nominal diameter of complete cable mm
28
Nominal weight of cable kg/km
1590
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
25
Nominal thickness of insulation mm
0.9
Number of wires
4
Min. bending radius
During handling and installation, cable mm
330
In final installation, cable mm
231
During handling and installation, cable cm
33
In final installation, cable cm
23
During handling and installation, cable m
0.33
In final installation, cable m
0.23
Max. pulling force
Pulling-eye kN
5
Pulling-stocking kN
1.5
Resistance 20 °C Ω/km
0,727
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023288
Reka code
1146311
4x35/16
Electric number
Size
Packaging
Voltage
4x35/16
Nominal diameter of complete cable mm
26
Nominal weight of cable kg/km
1684
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
35
Nominal thickness of insulation mm
0.9
Number of wires
4
Min. bending radius
During handling and installation, cable mm
312
In final installation, cable mm
219
During handling and installation, cable cm
31
In final installation, cable cm
22
During handling and installation, cable m
0.31
In final installation, cable m
0.22
Max. pulling force
Pulling-eye kN
7
Pulling-stocking kN
2.1
Resistance 20 °C Ω/km
0,524
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176219775
Reka code
1146312
Nominal diameter of complete cable mm
26
Nominal weight of cable kg/km
1684
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
35
Nominal thickness of insulation mm
0.9
Number of wires
4
Min. bending radius
During handling and installation, cable mm
312
In final installation, cable mm
219
During handling and installation, cable cm
31
In final installation, cable cm
22
During handling and installation, cable m
0.31
In final installation, cable m
0.22
Max. pulling force
Pulling-eye kN
7
Pulling-stocking kN
2.1
Resistance 20 °C Ω/km
0,524
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023295
Reka code
1146312
4x50/25
Electric number
Size
Packaging
Voltage
4x50/25
Nominal diameter of complete cable mm
30
Nominal weight of cable kg/km
2312
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
50
Nominal thickness of insulation mm
1
Number of wires
4
Min. bending radius
During handling and installation, cable mm
355
In final installation, cable mm
248
During handling and installation, cable cm
35
In final installation, cable cm
25
During handling and installation, cable m
0.35
In final installation, cable m
0.25
Max. pulling force
Pulling-eye kN
10
Pulling-stocking kN
3
Resistance 20 °C Ω/km
0,387
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,727
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023677
Reka code
1146313
Nominal diameter of complete cable mm
30
Nominal weight of cable kg/km
2312
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
50
Nominal thickness of insulation mm
1
Number of wires
4
Min. bending radius
During handling and installation, cable mm
355
In final installation, cable mm
248
During handling and installation, cable cm
35
In final installation, cable cm
25
During handling and installation, cable m
0.35
In final installation, cable m
0.25
Max. pulling force
Pulling-eye kN
10
Pulling-stocking kN
3
Resistance 20 °C Ω/km
0,387
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,727
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023660
Reka code
1146313
4x70/35
Electric number
Size
Packaging
Voltage
4x70/35
Nominal diameter of complete cable mm
34
Nominal weight of cable kg/km
3199
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
70
Nominal thickness of insulation mm
1.1
Number of wires
4
Min. bending radius
During handling and installation, cable mm
409
In final installation, cable mm
287
During handling and installation, cable cm
41
In final installation, cable cm
29
During handling and installation, cable m
0.41
In final installation, cable m
0.29
Max. pulling force
Pulling-eye kN
14
Pulling-stocking kN
4.2
Resistance 20 °C Ω/km
0,268
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,524
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023318
Reka code
1146314
Nominal diameter of complete cable mm
34
Nominal weight of cable kg/km
3199
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
70
Nominal thickness of insulation mm
1.1
Number of wires
4
Min. bending radius
During handling and installation, cable mm
409
In final installation, cable mm
287
During handling and installation, cable cm
41
In final installation, cable cm
29
During handling and installation, cable m
0.41
In final installation, cable m
0.29
Max. pulling force
Pulling-eye kN
14
Pulling-stocking kN
4.2
Resistance 20 °C Ω/km
0,268
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,524
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176219812
Reka code
1146314
4x95/50
Electric number
Size
Packaging
Voltage
4x95/50
Nominal diameter of complete cable mm
38
Nominal weight of cable kg/km
4319
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
95
Nominal thickness of insulation mm
1.1
Number of wires
4
Min. bending radius
During handling and installation, cable mm
450
In final installation, cable mm
315
During handling and installation, cable cm
45
In final installation, cable cm
32
During handling and installation, cable m
0.45
In final installation, cable m
0.32
Max. pulling force
Pulling-eye kN
19
Pulling-stocking kN
5.7
Resistance 20 °C Ω/km
0,193
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,387
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023325
Reka code
1146315
Nominal diameter of complete cable mm
38
Nominal weight of cable kg/km
4319
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
95
Nominal thickness of insulation mm
1.1
Number of wires
4
Min. bending radius
During handling and installation, cable mm
450
In final installation, cable mm
315
During handling and installation, cable cm
45
In final installation, cable cm
32
During handling and installation, cable m
0.45
In final installation, cable m
0.32
Max. pulling force
Pulling-eye kN
19
Pulling-stocking kN
5.7
Resistance 20 °C Ω/km
0,193
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,387
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023691
Reka code
1146315
4x120/70
Electric number
Size
Packaging
Voltage
4x120/70
Nominal diameter of complete cable mm
42
Nominal weight of cable kg/km
5491
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
120
Nominal thickness of insulation mm
1.2
Number of wires
4
Min. bending radius
During handling and installation, cable mm
501
In final installation, cable mm
351
During handling and installation, cable cm
50
In final installation, cable cm
35
During handling and installation, cable m
0.5
In final installation, cable m
0.35
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
7.2
Resistance 20 °C Ω/km
0,153
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,268
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023332
Reka code
1146316
4x150/70
Electric number
Size
Packaging
Voltage
4x150/70
Nominal diameter of complete cable mm
46
Nominal weight of cable kg/km
6626
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
150
Nominal thickness of insulation mm
1.4
Number of wires
4
Min. bending radius
During handling and installation, cable mm
546
In final installation, cable mm
382
During handling and installation, cable cm
55
In final installation, cable cm
38
During handling and installation, cable m
0.55
In final installation, cable m
0.38
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,124
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,268
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023714
Reka code
1146317
Nominal diameter of complete cable mm
46
Nominal weight of cable kg/km
6626
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
150
Nominal thickness of insulation mm
1.4
Number of wires
4
Min. bending radius
During handling and installation, cable mm
546
In final installation, cable mm
382
During handling and installation, cable cm
55
In final installation, cable cm
38
During handling and installation, cable m
0.55
In final installation, cable m
0.38
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,124
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,268
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023707
Reka code
1146317
4x185/95
Electric number
Size
Packaging
Voltage
4x185/95
Nominal diameter of complete cable mm
51
Nominal weight of cable kg/km
8366
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
185
Nominal thickness of insulation mm
1.6
Number of wires
4
Min. bending radius
During handling and installation, cable mm
612
In final installation, cable mm
429
During handling and installation, cable cm
61
In final installation, cable cm
43
During handling and installation, cable m
0.61
In final installation, cable m
0.43
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,0991
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,193
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023356
Reka code
1146318
4x240/120
Electric number
Size
Packaging
Voltage
4x240/120
Nominal diameter of complete cable mm
57
Nominal weight of cable kg/km
10885
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
240
Nominal thickness of insulation mm
1.7
Number of wires
4
Min. bending radius
During handling and installation, cable mm
679
In final installation, cable mm
476
During handling and installation, cable cm
68
In final installation, cable cm
48
During handling and installation, cable m
0.68
In final installation, cable m
0.48
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,0754
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,153
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023363
Reka code
1146319
Nominal diameter of complete cable mm
57
Nominal weight of cable kg/km
10885
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
240
Nominal thickness of insulation mm
1.7
Number of wires
4
Min. bending radius
During handling and installation, cable mm
679
In final installation, cable mm
476
During handling and installation, cable cm
68
In final installation, cable cm
48
During handling and installation, cable m
0.68
In final installation, cable m
0.48
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,0754
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,153
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176011973
Reka code
1146319