XCMK-HF / EXQJ / IFSI-Cu


Copper power cable for fixed installations indoors and outdoors. May be buried directly in soil. Installations must be in accordance with national regulations and rules of installations. The conductor insulation must be protected against UV-radiation. The cable is halogen-free and flame-retardant according to CPR-class Dca-s2,d2,a2.
Standards | SFS 5546, SS 424 14 18, HD 604 5 I & D, IEC 60502-1 |
---|---|
Reaction to fire | Dca-s2,d2,a2 |
CPR - DoP | 2021012_DOP.pdf |
Conductor | 1,5-6 mm² circular solid copper, EN/IEC 60228 class 1 |
Insulation | Halogen-free XLPE |
Core Identification (all color combinations in the cable family) | blue, brown brown, black, grey blue, brown, black, grey |
Inner covering | Plastic tape |
Metal screen | Copper wires and copper tape |
Oversheath | UV-protected halogen-free polyolefin compound |
Colour of the oversheath | Black |
2x1,5/1,5
Electric number
Size
Packaging
Voltage
2x1,5/1,5
Nominal diameter of complete cable mm
12
Nominal weight of cable kg/km
187
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
1.5
Nominal thickness of insulation mm
0.7
Number of wires
2
Min. bending radius
During handling and installation, cable mm
141
In final installation, cable mm
99
During handling and installation, cable cm
14
In final installation, cable cm
10
During handling and installation, cable m
0.14
In final installation, cable m
0.1
Max. pulling force
Pulling-eye kN
0.2
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
12.1
Maximum d.c. resistance at 20 °C, metal screen Ω/km
12.1
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176011607
Reka code
1146105
2x2,5/2,5
Electric number
Size
Packaging
Voltage
2x2,5/2,5
Nominal diameter of complete cable mm
13
Nominal weight of cable kg/km
235
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
2.5
Nominal thickness of insulation mm
0.7
Number of wires
2
Min. bending radius
During handling and installation, cable mm
151
In final installation, cable mm
105
During handling and installation, cable cm
15
In final installation, cable cm
11
During handling and installation, cable m
0.15
In final installation, cable m
0.11
Max. pulling force
Pulling-eye kN
0.3
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
7.41
Maximum d.c. resistance at 20 °C, metal screen Ω/km
7.41
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176011614
Reka code
1146106
Nominal diameter of complete cable mm
13
Nominal weight of cable kg/km
235
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
2.5
Nominal thickness of insulation mm
0.7
Number of wires
2
Min. bending radius
During handling and installation, cable mm
151
In final installation, cable mm
105
During handling and installation, cable cm
15
In final installation, cable cm
11
During handling and installation, cable m
0.15
In final installation, cable m
0.11
Max. pulling force
Pulling-eye kN
0.3
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
7.41
Maximum d.c. resistance at 20 °C, metal screen Ω/km
7.41
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176219393
Reka code
1146106
2x4/4
Electric number
Size
Packaging
Voltage
2x4/4
Nominal diameter of complete cable mm
14
Nominal weight of cable kg/km
302
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
4
Nominal thickness of insulation mm
0.7
Number of wires
2
Min. bending radius
During handling and installation, cable mm
165
In final installation, cable mm
116
During handling and installation, cable cm
17
In final installation, cable cm
12
During handling and installation, cable m
0.17
In final installation, cable m
0.12
Max. pulling force
Pulling-eye kN
0.4
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
4.61
Maximum d.c. resistance at 20 °C, metal screen Ω/km
4.61
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176011621
Reka code
1146107
2x6/6
Electric number
Size
Packaging
Voltage
2x6/6
Nominal diameter of complete cable mm
15
Nominal weight of cable kg/km
383
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
6
Nominal thickness of insulation mm
0.7
Number of wires
2
Min. bending radius
During handling and installation, cable mm
178
In final installation, cable mm
124
During handling and installation, cable cm
18
In final installation, cable cm
12
During handling and installation, cable m
0.18
In final installation, cable m
0.12
Max. pulling force
Pulling-eye kN
0.6
Pulling-stocking kN
0.2
Resistance 20 °C Ω/km
3.08
Maximum d.c. resistance at 20 °C, metal screen Ω/km
3.08
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176011638
Reka code
1146108
Nominal diameter of complete cable mm
15
Nominal weight of cable kg/km
383
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
6
Nominal thickness of insulation mm
0.7
Number of wires
2
Min. bending radius
During handling and installation, cable mm
178
In final installation, cable mm
124
During handling and installation, cable cm
18
In final installation, cable cm
12
During handling and installation, cable m
0.18
In final installation, cable m
0.12
Max. pulling force
Pulling-eye kN
0.6
Pulling-stocking kN
0.2
Resistance 20 °C Ω/km
3.08
Maximum d.c. resistance at 20 °C, metal screen Ω/km
3.08
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006029907
Reka code
1146108
3x1,5/1,5
Electric number
Size
Packaging
Voltage
3x1,5/1,5
Nominal diameter of complete cable mm
12
Nominal weight of cable kg/km
205
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
1.5
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable mm
147
In final installation, cable mm
103
During handling and installation, cable cm
15
In final installation, cable cm
10
During handling and installation, cable m
0.15
In final installation, cable m
0.1
Max. pulling force
Pulling-eye kN
0.2
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
12.1
Maximum d.c. resistance at 20 °C, metal screen Ω/km
12.1
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023172
Reka code
1146225
Nominal diameter of complete cable mm
12
Nominal weight of cable kg/km
205
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
1.5
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable mm
147
In final installation, cable mm
103
During handling and installation, cable cm
15
In final installation, cable cm
10
During handling and installation, cable m
0.15
In final installation, cable m
0.1
Max. pulling force
Pulling-eye kN
0.2
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
12.1
Maximum d.c. resistance at 20 °C, metal screen Ω/km
12.1
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023189
Reka code
1146225
3x2,5/2,5
Electric number
Size
Packaging
Voltage
3x2,5/2,5
Nominal diameter of complete cable mm
13
Nominal weight of cable kg/km
254
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
2.5
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable mm
156
In final installation, cable mm
109
During handling and installation, cable cm
16
In final installation, cable cm
11
During handling and installation, cable m
0.16
In final installation, cable m
0.11
Max. pulling force
Pulling-eye kN
0.4
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
7.41
Maximum d.c. resistance at 20 °C, metal screen Ω/km
7.41
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023202
Reka code
1146226
Nominal diameter of complete cable mm
13
Nominal weight of cable kg/km
254
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
2.5
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable mm
156
In final installation, cable mm
109
During handling and installation, cable cm
16
In final installation, cable cm
11
During handling and installation, cable m
0.16
In final installation, cable m
0.11
Max. pulling force
Pulling-eye kN
0.4
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
7.41
Maximum d.c. resistance at 20 °C, metal screen Ω/km
7.41
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023196
Reka code
1146226
3x4/4
Electric number
Size
Packaging
Voltage
3x4/4
Nominal diameter of complete cable mm
14
Nominal weight of cable kg/km
338
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
4
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable mm
172
In final installation, cable mm
120
During handling and installation, cable cm
17
In final installation, cable cm
12
During handling and installation, cable m
0.17
In final installation, cable m
0.12
Max. pulling force
Pulling-eye kN
0.6
Pulling-stocking kN
0.2
Resistance 20 °C Ω/km
4.61
Maximum d.c. resistance at 20 °C, metal screen Ω/km
4.61
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176011706
Reka code
1146227
3x6/6
Electric number
Size
Packaging
Voltage
3x6/6
Nominal diameter of complete cable mm
15
Nominal weight of cable kg/km
437
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
6
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable mm
185
In final installation, cable mm
130
During handling and installation, cable cm
19
In final installation, cable cm
13
During handling and installation, cable m
0.19
In final installation, cable m
0.13
Max. pulling force
Pulling-eye kN
0.9
Pulling-stocking kN
0.3
Resistance 20 °C Ω/km
3.08
Maximum d.c. resistance at 20 °C, metal screen Ω/km
3.08
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023257
Reka code
1146228
Nominal diameter of complete cable mm
15
Nominal weight of cable kg/km
437
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
6
Nominal thickness of insulation mm
0.7
Number of wires
3
Min. bending radius
During handling and installation, cable mm
185
In final installation, cable mm
130
During handling and installation, cable cm
19
In final installation, cable cm
13
During handling and installation, cable m
0.19
In final installation, cable m
0.13
Max. pulling force
Pulling-eye kN
0.9
Pulling-stocking kN
0.3
Resistance 20 °C Ω/km
3.08
Maximum d.c. resistance at 20 °C, metal screen Ω/km
3.08
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023301
Reka code
1146228
4x1,5/1,5
Electric number
Size
Packaging
Voltage
4x1,5/1,5
Nominal diameter of complete cable mm
13
Nominal weight of cable kg/km
230
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
1.5
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable mm
155
In final installation, cable mm
109
During handling and installation, cable cm
16
In final installation, cable cm
11
During handling and installation, cable m
0.16
In final installation, cable m
0.11
Max. pulling force
Pulling-eye kN
0.3
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
12.1
Maximum d.c. resistance at 20 °C, metal screen Ω/km
12.1
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023615
Reka code
1146305
Nominal diameter of complete cable mm
13
Nominal weight of cable kg/km
230
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
1.5
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable mm
155
In final installation, cable mm
109
During handling and installation, cable cm
16
In final installation, cable cm
11
During handling and installation, cable m
0.16
In final installation, cable m
0.11
Max. pulling force
Pulling-eye kN
0.3
Pulling-stocking kN
0.1
Resistance 20 °C Ω/km
12.1
Maximum d.c. resistance at 20 °C, metal screen Ω/km
12.1
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023622
Reka code
1146305
4x2,5/2,5
Electric number
Size
Packaging
Voltage
4x2,5/2,5
Nominal diameter of complete cable mm
14
Nominal weight of cable kg/km
292
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
2.5
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable mm
166
In final installation, cable mm
116
During handling and installation, cable cm
17
In final installation, cable cm
12
During handling and installation, cable m
0.17
In final installation, cable m
0.12
Max. pulling force
Pulling-eye kN
0.5
Pulling-stocking kN
0.2
Resistance 20 °C Ω/km
7.41
Maximum d.c. resistance at 20 °C, metal screen Ω/km
7.41
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023639
Reka code
1146306
Nominal diameter of complete cable mm
14
Nominal weight of cable kg/km
292
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
2.5
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable mm
166
In final installation, cable mm
116
During handling and installation, cable cm
17
In final installation, cable cm
12
During handling and installation, cable m
0.17
In final installation, cable m
0.12
Max. pulling force
Pulling-eye kN
0.5
Pulling-stocking kN
0.2
Resistance 20 °C Ω/km
7.41
Maximum d.c. resistance at 20 °C, metal screen Ω/km
7.41
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023646
Reka code
1146306
4x4/4
Electric number
Size
Packaging
Voltage
4x4/4
Nominal diameter of complete cable mm
15
Nominal weight of cable kg/km
393
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
4
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable mm
183
In final installation, cable mm
128
During handling and installation, cable cm
18
In final installation, cable cm
13
During handling and installation, cable m
0.18
In final installation, cable m
0.13
Max. pulling force
Pulling-eye kN
0.8
Pulling-stocking kN
0.2
Resistance 20 °C Ω/km
4.61
Maximum d.c. resistance at 20 °C, metal screen Ω/km
4.61
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176011850
Reka code
1146307
4x6/6
Electric number
Size
Packaging
Voltage
4x6/6
Nominal diameter of complete cable mm
17
Nominal weight of cable kg/km
521
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
6
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable mm
198
In final installation, cable mm
139
During handling and installation, cable cm
20
In final installation, cable cm
14
During handling and installation, cable m
0.2
In final installation, cable m
0.14
Max. pulling force
Pulling-eye kN
1.2
Pulling-stocking kN
0.4
Resistance 20 °C Ω/km
3.08
Maximum d.c. resistance at 20 °C, metal screen Ω/km
3.08
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023004
Reka code
1146308
Nominal diameter of complete cable mm
17
Nominal weight of cable kg/km
521
Conductor material
Copper
Nominal cross-sectional area of conductor mm2
6
Nominal thickness of insulation mm
0.7
Number of wires
4
Min. bending radius
During handling and installation, cable mm
198
In final installation, cable mm
139
During handling and installation, cable cm
20
In final installation, cable cm
14
During handling and installation, cable m
0.2
In final installation, cable m
0.14
Max. pulling force
Pulling-eye kN
1.2
Pulling-stocking kN
0.4
Resistance 20 °C Ω/km
3.08
Maximum d.c. resistance at 20 °C, metal screen Ω/km
3.08
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006023219
Reka code
1146308