TSLF 18/30 (36) kV 1-core CAS
Download product group datasheet
Medium-voltage cable for fixed installations outdoors. May be buried directly in soil. Cable is longitudinally and radially watertight and therefore it is suitable where wet soil and / or fresh water permanently occurs. Installations must be in accordance with national regulations and rules of installations. The cable is halogen-free, but without fire protection. The cable is not CPR-classified.
| Standards | HD 620 10 K |
|---|---|
| Conductor | Watertight, circular, stranded aluminium, EN/IEC 60228 class 2 |
| Conductor screen | Semiconducting cross-linked polyethylene XLPE |
| Insulation | Cross-linked polyethylene XLPE |
| Insulation screen | Semiconducting cross-linked polyethylene XLPE |
| Metal screen | Copper wires and aluminium foil (CAS). Polyethylene laminated aluminium foil acts as a part of the metallic screen and needs to be connected in cable joints and terminations |
| Radial watertightness | Polyethylene laminated aluminium foil bonded to the sheath |
| Oversheath | UV-protected PE-plastic PEMD |
| Colour of the oversheath | Grey + black CL |
1x400/35 CAS
Electric number
Size
Packaging
Voltage
1x400/35 CAS
Nominal diameter of complete cable mm
48
Nominal weight of cable kg/km
2403
Conductor material
Aluminium
Nominal diameter of conductor mm
22.4
Nominal cross-sectional area of conductor mm2
400
Nominal thickness of insulation mm
8
Nominal diameter over the insulation without insulation screen mm
38
Number of wires
1
Nominal size of metal screen mm2
35
Nominal thickness of semi-conducting layer mm
0.3
Min. bending radius
During handling and installation, cable mm
722
In final installation, cable mm
505
During handling and installation, cable cm
72
In final installation, cable cm
51
During handling and installation, cable m
0.72
In final installation, cable m
0.51
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
6
Resistance 20 °C Ω/km
0,0778
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,524
Minimum cable temperature during transport °C
-40
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176014851
Reka code
1181233
1x630/50 CAS
Electric number
Size
Packaging
Voltage
1x630/50 CAS
Nominal diameter of complete cable mm
56
Nominal weight of cable kg/km
3574
Conductor material
Aluminium
Nominal diameter of conductor mm
29.3
Nominal cross-sectional area of conductor mm2
630
Nominal thickness of insulation mm
8
Nominal diameter over the insulation without insulation screen mm
45.1
Number of wires
1
Nominal size of metal screen mm2
50
Nominal thickness of semi-conducting layer mm
0.3
Min. bending radius
During handling and installation, cable mm
840
In final installation, cable mm
588
During handling and installation, cable cm
84
In final installation, cable cm
59
During handling and installation, cable m
0.84
In final installation, cable m
0.59
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,0469
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,387
Minimum cable temperature during transport °C
-40
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176014868
Reka code
1181235