FRHF-XCMK / BFSI

Download product group datasheet

Fire-resistant power cable for fixed installations indoors and outdoors. May be buried directly in soil. For locations where safety requires the operation of alarm, control, signalling and energy circuits also during a fire. The conductor insulation must be protected against UV-radiation. Installations must be in accordance with national regulations and rules of installations. No requirement for CPR-classification.

Standards SFS 5547, HD 604 5 D
Conductor 1,5-6 mm² circular solid copper, EN/IEC 60228 class 1
10-25 mm² circular stranded copper, EN/IEC 60228 class 2
35-240 mm² sector shaped stranded copper, EN/IEC 60228 class 2
Insulation Halogen-free XLPE, mica tape
Core Identification (all color combinations in the cable family) Blue, brown
Brown, black, grey
Blue, brown, black, grey
Separation sheath Halogen-free filling compound
Metal screen Copper wires and copper tape
Oversheath UV-protected halogen-free polyolefin compound
Colour of the oversheath Orange

2x1,5/1,5

Electric number Size Packaging Voltage

2x1,5/1,5

Nominal diameter of complete cable mm 12
Nominal weight of cable kg/km 199
Conductor material Copper
Nominal cross-sectional area of conductor mm2 1.5
Nominal thickness of insulation mm 0.7
Number of wires 2
Min. bending radius
During handling and installation, cable cm 15
In final installation, cable cm 10
During handling and installation, cable m 0.15
In final installation, cable m 0.1
Max. pulling force
Pulling-eye kN 0.05
Pulling-stocking kN 0.06
Resistance 20 °C Ω/km 12,1
Maximum d.c. resistance at 20 °C, metal screen Ω/km 12,1
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307694
Reka code 1146810

2x2,5/2,5

Electric number Size Packaging Voltage

2x2,5/2,5

Nominal diameter of complete cable mm 13
Nominal weight of cable kg/km 244
Conductor material Copper
Nominal cross-sectional area of conductor mm2 2.5
Nominal thickness of insulation mm 0.7
Number of wires 2
Min. bending radius
During handling and installation, cable cm 16
In final installation, cable cm 11
During handling and installation, cable m 0.16
In final installation, cable m 0.11
Max. pulling force
Pulling-eye kN 0.08
Pulling-stocking kN 0.1
Resistance 20 °C Ω/km 7,41
Maximum d.c. resistance at 20 °C, metal screen Ω/km 7,41
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307700
Reka code 1146811

2x4/4

Electric number Size Packaging Voltage

2x4/4

Nominal diameter of complete cable mm 15
Nominal weight of cable kg/km 330
Conductor material Copper
Nominal cross-sectional area of conductor mm2 4
Nominal thickness of insulation mm 0.7
Number of wires 2
Min. bending radius
During handling and installation, cable cm 18
In final installation, cable cm 12
During handling and installation, cable m 0.18
In final installation, cable m 0.12
Max. pulling force
Pulling-eye kN 0.12
Pulling-stocking kN 0.16
Resistance 20 °C Ω/km 4,61
Maximum d.c. resistance at 20 °C, metal screen Ω/km 4,61
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307717
Reka code 1146812

2x6/6

Electric number Size Packaging Voltage

2x6/6

Nominal diameter of complete cable mm 16
Nominal weight of cable kg/km 431
Conductor material Copper
Nominal cross-sectional area of conductor mm2 6
Nominal thickness of insulation mm 0.7
Number of wires 2
Min. bending radius
During handling and installation, cable cm 19
In final installation, cable cm 14
During handling and installation, cable m 0.19
In final installation, cable m 0.14
Max. pulling force
Pulling-eye kN 0.18
Pulling-stocking kN 0.24
Resistance 20 °C Ω/km 3,08
Maximum d.c. resistance at 20 °C, metal screen Ω/km 3,08
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307724
Reka code 1146813

2x10/10

Electric number Size Packaging Voltage

2x10/10

Nominal diameter of complete cable mm 19
Nominal weight of cable kg/km 619
Conductor material Copper
Nominal cross-sectional area of conductor mm2 10
Nominal thickness of insulation mm 0.7
Number of wires 2
Min. bending radius
During handling and installation, cable cm 23
In final installation, cable cm 16
During handling and installation, cable m 0.23
In final installation, cable m 0.16
Max. pulling force
Pulling-eye kN 0.3
Pulling-stocking kN 0.4
Resistance 20 °C Ω/km 1,83
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,83
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307731
Reka code 1146814

2x16/16

Electric number Size Packaging Voltage

2x16/16

Nominal diameter of complete cable mm 21
Nominal weight of cable kg/km 863
Conductor material Copper
Nominal cross-sectional area of conductor mm2 16
Nominal thickness of insulation mm 0.7
Number of wires 2
Min. bending radius
During handling and installation, cable cm 26
In final installation, cable cm 18
During handling and installation, cable m 0.26
In final installation, cable m 0.18
Max. pulling force
Pulling-eye kN 0.48
Pulling-stocking kN 0.64
Resistance 20 °C Ω/km 1,15
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307748
Reka code 1146815

2x25/16

Electric number Size Packaging Voltage

2x25/16

Nominal diameter of complete cable mm 26
Nominal weight of cable kg/km 1189
Conductor material Copper
Nominal cross-sectional area of conductor mm2 25
Nominal thickness of insulation mm 0.9
Number of wires 2
Min. bending radius
During handling and installation, cable cm 31
In final installation, cable cm 21
During handling and installation, cable m 0.31
In final installation, cable m 0.21
Max. pulling force
Pulling-eye kN 0.75
Pulling-stocking kN 1
Resistance 20 °C Ω/km 0,727
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307755
Reka code 1146816

3x1,5/1,5

Electric number Size Packaging Voltage

3x1,5/1,5

Nominal diameter of complete cable mm 13
Nominal weight of cable kg/km 221
Conductor material Copper
Nominal cross-sectional area of conductor mm2 1.5
Nominal thickness of insulation mm 0.7
Number of wires 3
Min. bending radius
During handling and installation, cable cm 16
In final installation, cable cm 11
During handling and installation, cable m 0.15
In final installation, cable m 0.11
Max. pulling force
Pulling-eye kN 0.07
Pulling-stocking kN 0.09
Resistance 20 °C Ω/km 12,1
Maximum d.c. resistance at 20 °C, metal screen Ω/km 12,1
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307762
Reka code 1146819

3x2,5/2,5

Electric number Size Packaging Voltage

3x2,5/2,5

Nominal diameter of complete cable mm 14
Nominal weight of cable kg/km 275
Conductor material Copper
Nominal cross-sectional area of conductor mm2 2.5
Nominal thickness of insulation mm 0.7
Number of wires 3
Min. bending radius
During handling and installation, cable cm 17
In final installation, cable cm 12
During handling and installation, cable m 0.17
In final installation, cable m 0.12
Max. pulling force
Pulling-eye kN 0.11
Pulling-stocking kN 0.15
Resistance 20 °C Ω/km 7,41
Maximum d.c. resistance at 20 °C, metal screen Ω/km 7,41
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307779
Reka code 1146820

3x4/4

Electric number Size Packaging Voltage

3x4/4

Nominal diameter of complete cable mm 16
Nominal weight of cable kg/km 384
Conductor material Copper
Nominal cross-sectional area of conductor mm2 4
Nominal thickness of insulation mm 0.7
Number of wires 3
Min. bending radius
During handling and installation, cable cm 19
In final installation, cable cm 13
During handling and installation, cable m 0.19
In final installation, cable m 0.13
Max. pulling force
Pulling-eye kN 0.18
Pulling-stocking kN 0.24
Resistance 20 °C Ω/km 4,61
Maximum d.c. resistance at 20 °C, metal screen Ω/km 4,61
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307786
Reka code 1146821

3x6/6

Electric number Size Packaging Voltage

3x6/6

Nominal diameter of complete cable mm 17
Nominal weight of cable kg/km 487
Conductor material Copper
Nominal cross-sectional area of conductor mm2 6
Nominal thickness of insulation mm 0.7
Number of wires 3
Min. bending radius
During handling and installation, cable cm 20
In final installation, cable cm 14
During handling and installation, cable m 0.2
In final installation, cable m 0.14
Max. pulling force
Pulling-eye kN 0.27
Pulling-stocking kN 0.36
Resistance 20 °C Ω/km 3,08
Maximum d.c. resistance at 20 °C, metal screen Ω/km 3,08
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307793
Reka code 1146822

3x10/10

Electric number Size Packaging Voltage

3x10/10

Nominal diameter of complete cable mm 20
Nominal weight of cable kg/km 703
Conductor material Copper
Nominal cross-sectional area of conductor mm2 10
Nominal thickness of insulation mm 0.7
Number of wires 3
Min. bending radius
During handling and installation, cable cm 24
In final installation, cable cm 17
During handling and installation, cable m 0.24
In final installation, cable m 0.17
Max. pulling force
Pulling-eye kN 0.45
Pulling-stocking kN 0.6
Resistance 20 °C Ω/km 1,83
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,83
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307809
Reka code 1146823

3x16/16

Electric number Size Packaging Voltage

3x16/16

Nominal diameter of complete cable mm 23
Nominal weight of cable kg/km 1006
Conductor material Copper
Nominal cross-sectional area of conductor mm2 16
Nominal thickness of insulation mm 0.7
Number of wires 3
Min. bending radius
During handling and installation, cable cm 27
In final installation, cable cm 19
During handling and installation, cable m 0.27
In final installation, cable m 0.19
Max. pulling force
Pulling-eye kN 0.72
Pulling-stocking kN 0.96
Resistance 20 °C Ω/km 1,15
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307816
Reka code 1146824

3x25/16

Electric number Size Packaging Voltage

3x25/16

Nominal diameter of complete cable mm 26
Nominal weight of cable kg/km 1370
Conductor material Copper
Nominal cross-sectional area of conductor mm2 25
Nominal thickness of insulation mm 0.9
Number of wires 3
Min. bending radius
During handling and installation, cable cm 32
In final installation, cable cm 22
During handling and installation, cable m 0.32
In final installation, cable m 0.22
Max. pulling force
Pulling-eye kN 1.13
Pulling-stocking kN 1.5
Resistance 20 °C Ω/km 0,727
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307823
Reka code 1146825

3x35/16

Electric number Size Packaging Voltage

3x35/16

Nominal diameter of complete cable mm 26
Nominal weight of cable kg/km 1478
Conductor material Copper
Nominal cross-sectional area of conductor mm2 35
Nominal thickness of insulation mm 0.9
Number of wires 3
Min. bending radius
During handling and installation, cable cm 31
In final installation, cable cm 22
During handling and installation, cable m 0.32
In final installation, cable m 0.22
Max. pulling force
Pulling-eye kN 1.58
Pulling-stocking kN 2.1
Resistance 20 °C Ω/km 0,524
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307830
Reka code 1146826

3x50/25

Electric number Size Packaging Voltage

3x50/25

Nominal diameter of complete cable mm 30
Nominal weight of cable kg/km 2083
Conductor material Copper
Nominal cross-sectional area of conductor mm2 50
Nominal thickness of insulation mm 1
Number of wires 3
Min. bending radius
During handling and installation, cable cm 36
In final installation, cable cm 25
During handling and installation, cable m 0.36
In final installation, cable m 0.25
Max. pulling force
Pulling-eye kN 2.25
Pulling-stocking kN 3
Resistance 20 °C Ω/km 0,387
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,727
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307847
Reka code 1146827

3x70/35

Electric number Size Packaging Voltage

3x70/35

Nominal diameter of complete cable mm 34
Nominal weight of cable kg/km 2883
Conductor material Copper
Nominal cross-sectional area of conductor mm2 70
Nominal thickness of insulation mm 1.1
Number of wires 3
Min. bending radius
During handling and installation, cable cm 41
In final installation, cable cm 28
During handling and installation, cable m 0.41
In final installation, cable m 0.28
Max. pulling force
Pulling-eye kN 3.15
Pulling-stocking kN 4.2
Resistance 20 °C Ω/km 0,268
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,524
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307854
Reka code 1146828

3x95/50

Electric number Size Packaging Voltage

3x95/50

Nominal diameter of complete cable mm 37
Nominal weight of cable kg/km 3645
Conductor material Copper
Nominal cross-sectional area of conductor mm2 95
Nominal thickness of insulation mm 1.1
Number of wires 3
Min. bending radius
During handling and installation, cable cm 45
In final installation, cable cm 31
During handling and installation, cable m 0.45
In final installation, cable m 0.31
Max. pulling force
Pulling-eye kN 4.28
Pulling-stocking kN 5.7
Resistance 20 °C Ω/km 0,193
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,387
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307861
Reka code 1146829

3x120/70

Electric number Size Packaging Voltage

3x120/70

Nominal diameter of complete cable mm 40
Nominal weight of cable kg/km 4645
Conductor material Copper
Nominal cross-sectional area of conductor mm2 120
Nominal thickness of insulation mm 1.2
Number of wires 3
Min. bending radius
During handling and installation, cable cm 48
In final installation, cable cm 34
During handling and installation, cable m 0.48
In final installation, cable m 0.34
Max. pulling force
Pulling-eye kN 5.4
Pulling-stocking kN 7.2
Resistance 20 °C Ω/km 0,153
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,268
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307878
Reka code 1146830

3x150/70

Electric number Size Packaging Voltage

3x150/70

Nominal diameter of complete cable mm 43
Nominal weight of cable kg/km 5530
Conductor material Copper
Nominal cross-sectional area of conductor mm2 150
Nominal thickness of insulation mm 1.4
Number of wires 3
Min. bending radius
During handling and installation, cable cm 52
In final installation, cable cm 36
During handling and installation, cable m 0.52
In final installation, cable m 0.36
Max. pulling force
Pulling-eye kN 6.75
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,124
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,268
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307885
Reka code 1146831

3x185/95

Electric number Size Packaging Voltage

3x185/95

Nominal diameter of complete cable mm 50
Nominal weight of cable kg/km 7132
Conductor material Copper
Nominal cross-sectional area of conductor mm2 185
Nominal thickness of insulation mm 1.6
Number of wires 3
Min. bending radius
During handling and installation, cable cm 61
In final installation, cable cm 42
During handling and installation, cable m 0.61
In final installation, cable m 0.42
Max. pulling force
Pulling-eye kN 8.32
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,0991
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,193
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307892
Reka code 1146832

3x240/120

Electric number Size Packaging Voltage

3x240/120

Nominal diameter of complete cable mm 56
Nominal weight of cable kg/km 9233
Conductor material Copper
Nominal cross-sectional area of conductor mm2 240
Nominal thickness of insulation mm 1.7
Number of wires 3
Min. bending radius
During handling and installation, cable cm 67
In final installation, cable cm 47
During handling and installation, cable m 0.67
In final installation, cable m 0.47
Max. pulling force
Pulling-eye kN 10.8
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,0754
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,153
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307908
Reka code 1146833

4x1,5/1,5

Electric number Size Packaging Voltage

4x1,5/1,5

Nominal diameter of complete cable mm 14
Nominal weight of cable kg/km 274
Conductor material Copper
Nominal cross-sectional area of conductor mm2 1.5
Nominal thickness of insulation mm 0.7
Number of wires 4
Min. bending radius
During handling and installation, cable cm 17
In final installation, cable cm 12
During handling and installation, cable m 0.17
In final installation, cable m 0.12
Max. pulling force
Pulling-eye kN 0.09
Pulling-stocking kN 0.12
Resistance 20 °C Ω/km 12,1
Maximum d.c. resistance at 20 °C, metal screen Ω/km 12,1
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307915
Reka code 1146835

4x2,5/2,5

Electric number Size Packaging Voltage

4x2,5/2,5

Nominal diameter of complete cable mm 15
Nominal weight of cable kg/km 340
Conductor material Copper
Nominal cross-sectional area of conductor mm2 2.5
Nominal thickness of insulation mm 0.7
Number of wires 4
Min. bending radius
During handling and installation, cable cm 18
In final installation, cable cm 13
During handling and installation, cable m 0.18
In final installation, cable m 0.13
Max. pulling force
Pulling-eye kN 0.15
Pulling-stocking kN 0.2
Resistance 20 °C Ω/km 7,41
Maximum d.c. resistance at 20 °C, metal screen Ω/km 7,41
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307922
Reka code 1146836

4x4/4

Electric number Size Packaging Voltage

4x4/4

Nominal diameter of complete cable mm 17
Nominal weight of cable kg/km 445
Conductor material Copper
Nominal cross-sectional area of conductor mm2 4
Nominal thickness of insulation mm 0.7
Number of wires 4
Min. bending radius
During handling and installation, cable cm 20
In final installation, cable cm 14
During handling and installation, cable m 0.2
In final installation, cable m 0.14
Max. pulling force
Pulling-eye kN 0.24
Pulling-stocking kN 0.32
Resistance 20 °C Ω/km 4,61
Maximum d.c. resistance at 20 °C, metal screen Ω/km 4,61
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307939
Reka code 1146837

4x6/6

Electric number Size Packaging Voltage

4x6/6

Nominal diameter of complete cable mm 18
Nominal weight of cable kg/km 570
Conductor material Copper
Nominal cross-sectional area of conductor mm2 6
Nominal thickness of insulation mm 0.7
Number of wires 4
Min. bending radius
During handling and installation, cable cm 22
In final installation, cable cm 15
During handling and installation, cable m 0.22
In final installation, cable m 0.15
Max. pulling force
Pulling-eye kN 0.36
Pulling-stocking kN 0.48
Resistance 20 °C Ω/km 3,08
Maximum d.c. resistance at 20 °C, metal screen Ω/km 3,08
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307946
Reka code 1146838

4x10/10

Electric number Size Packaging Voltage

4x10/10

Nominal diameter of complete cable mm 21
Nominal weight of cable kg/km 829
Conductor material Copper
Nominal cross-sectional area of conductor mm2 10
Nominal thickness of insulation mm 0.7
Number of wires 4
Min. bending radius
During handling and installation, cable cm 26
In final installation, cable cm 18
During handling and installation, cable m 0.26
In final installation, cable m 0.18
Max. pulling force
Pulling-eye kN 0.6
Pulling-stocking kN 0.8
Resistance 20 °C Ω/km 1,83
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,83
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307953
Reka code 1146839

4x16/16

Electric number Size Packaging Voltage

4x16/16

Nominal diameter of complete cable mm 24
Nominal weight of cable kg/km 1174
Conductor material Copper
Nominal cross-sectional area of conductor mm2 16
Nominal thickness of insulation mm 0.7
Number of wires 4
Min. bending radius
During handling and installation, cable cm 29
In final installation, cable cm 20
During handling and installation, cable m 0.29
In final installation, cable m 0.2
Max. pulling force
Pulling-eye kN 0.96
Pulling-stocking kN 1.28
Resistance 20 °C Ω/km 1,15
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307960
Reka code 1146840

4x25/16

Electric number Size Packaging Voltage

4x25/16

Nominal diameter of complete cable mm 29
Nominal weight of cable kg/km 1658
Conductor material Copper
Nominal cross-sectional area of conductor mm2 25
Nominal thickness of insulation mm 0.9
Number of wires 4
Min. bending radius
During handling and installation, cable cm 34
In final installation, cable cm 24
During handling and installation, cable m 0.34
In final installation, cable m 0.24
Max. pulling force
Pulling-eye kN 1.5
Pulling-stocking kN 2
Resistance 20 °C Ω/km 0,727
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307977
Reka code 1146841

4x35/16

Electric number Size Packaging Voltage

4x35/16

Nominal diameter of complete cable mm 29
Nominal weight of cable kg/km 1876
Conductor material Copper
Nominal cross-sectional area of conductor mm2 35
Nominal thickness of insulation mm 0.9
Number of wires 4
Min. bending radius
During handling and installation, cable cm 34
In final installation, cable cm 24
During handling and installation, cable m 0.34
In final installation, cable m 0.24
Max. pulling force
Pulling-eye kN 2.1
Pulling-stocking kN 2.8
Resistance 20 °C Ω/km 0,524
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307984
Reka code 1146842

4x50/25

Electric number Size Packaging Voltage

4x50/25

Nominal diameter of complete cable mm 33
Nominal weight of cable kg/km 2548
Conductor material Copper
Nominal cross-sectional area of conductor mm2 50
Nominal thickness of insulation mm 1
Number of wires 4
Min. bending radius
During handling and installation, cable cm 40
In final installation, cable cm 28
During handling and installation, cable m 0.4
In final installation, cable m 0.28
Max. pulling force
Pulling-eye kN 3
Pulling-stocking kN 4
Resistance 20 °C Ω/km 0,387
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,727
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176307991
Reka code 1146843

4x70/35

Electric number Size Packaging Voltage

4x70/35

Nominal diameter of complete cable mm 35
Nominal weight of cable kg/km 3452
Conductor material Copper
Nominal cross-sectional area of conductor mm2 70
Nominal thickness of insulation mm 1.1
Number of wires 4
Min. bending radius
During handling and installation, cable cm 43
In final installation, cable cm 30
During handling and installation, cable m 0.43
In final installation, cable m 0.3
Max. pulling force
Pulling-eye kN 4.2
Pulling-stocking kN 5.6
Resistance 20 °C Ω/km 0,268
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,524
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176308004
Reka code 1146844

4x95/50

Electric number Size Packaging Voltage

4x95/50

Nominal diameter of complete cable mm 41
Nominal weight of cable kg/km 4611
Conductor material Copper
Nominal cross-sectional area of conductor mm2 95
Nominal thickness of insulation mm 1.1
Number of wires 4
Min. bending radius
During handling and installation, cable cm 49
In final installation, cable cm 34
During handling and installation, cable m 0.49
In final installation, cable m 0.34
Max. pulling force
Pulling-eye kN 5.7
Pulling-stocking kN 7.6
Resistance 20 °C Ω/km 0,193
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,387
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176308011
Reka code 1146845

4x120/70

Electric number Size Packaging Voltage

4x120/70

Nominal diameter of complete cable mm 44
Nominal weight of cable kg/km 5773
Conductor material Copper
Nominal cross-sectional area of conductor mm2 120
Nominal thickness of insulation mm 1.2
Number of wires 4
Min. bending radius
During handling and installation, cable cm 53
In final installation, cable cm 37
During handling and installation, cable m 0.53
In final installation, cable m 0.37
Max. pulling force
Pulling-eye kN 7.2
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,153
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,268
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176308028
Reka code 1146846

4x150/70

Electric number Size Packaging Voltage

4x150/70

Nominal diameter of complete cable mm 49
Nominal weight of cable kg/km 7006
Conductor material Copper
Nominal cross-sectional area of conductor mm2 150
Nominal thickness of insulation mm 1.4
Number of wires 4
Min. bending radius
During handling and installation, cable cm 59
In final installation, cable cm 41
During handling and installation, cable m 0.58
In final installation, cable m 0.41
Max. pulling force
Pulling-eye kN 9
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,124
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,268
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176308035
Reka code 1146847

4x185/95

Electric number Size Packaging Voltage

4x185/95

Nominal diameter of complete cable mm 57
Nominal weight of cable kg/km 9067
Conductor material Copper
Nominal cross-sectional area of conductor mm2 185
Nominal thickness of insulation mm 1.6
Number of wires 4
Min. bending radius
During handling and installation, cable cm 68
In final installation, cable cm 48
During handling and installation, cable m 0.68
In final installation, cable m 0.47
Max. pulling force
Pulling-eye kN 11.1
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,0991
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,193
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176308042
Reka code 1146848

4x240/120

Electric number Size Packaging Voltage

4x240/120

Nominal diameter of complete cable mm 62
Nominal weight of cable kg/km 11641
Conductor material Copper
Nominal cross-sectional area of conductor mm2 240
Nominal thickness of insulation mm 1.7
Number of wires 4
Min. bending radius
During handling and installation, cable cm 74
In final installation, cable cm 52
During handling and installation, cable m 0.74
In final installation, cable m 0.52
Max. pulling force
Pulling-eye kN 14.4
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,0754
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,153
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176308059
Reka code 1146849