FRHF / BFXI

Download product group datasheet

Fire-resistant power cable for fixed installations indoors and outdoors. Not to be laid in soil nor directly in cast concrete. For locations where safety requires the operation of alarm, control, signalling and energy circuits also during a fire. The conductor insulation must be protected against UV-radiation. Installations must be in accordance with national regulations and rules of installations. No requirement for CPR-classification.

Standards HD 604 5 D, IEC 60502-1
Conductor 1,5-4 mm² circular solid copper, EN/IEC 60228 class 1
6-70 mm² circular stranded copper, EN/IEC 60228 class 2
Insulation Halogen-free XLPE, mica tape
Core Identification (all color combinations in the cable family) 2x: Blue, brown
3x: Brown, black, grey
3G: Yellowgreen, blue, brown
4G: Yellowgreen, blue, brown, black (1,5 and 2,5 mm²)
4G: Yellowgreen, brown, black, grey (4 mm² and above)
5G: Yellowgreen, blue, brown, black, grey
Separation sheath Halogen-free filling compound
Oversheath UV-protected halogen-free polyolefin compound
Colour of the oversheath Orange

2x1,5 N

Electric number Size Packaging Voltage

2x1,5 N

Nominal diameter of complete cable mm 11
Nominal weight of cable kg/km 165
Conductor material Copper
Nominal cross-sectional area of conductor mm2 1.5
Nominal thickness of insulation mm 0.7
Number of wires 2
Min. bending radius
During handling and installation, cable cm 13
In final installation, cable cm 9
During handling and installation, cable m 0.13
In final installation, cable m 0.09
Max. pulling force
Pulling-eye kN 0.05
Pulling-stocking kN 0.06
Resistance 20 °C Ω/km 12,1
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301708
Reka code 1146542
Nominal diameter of complete cable mm 11
Nominal weight of cable kg/km 165
Conductor material Copper
Nominal cross-sectional area of conductor mm2 1.5
Nominal thickness of insulation mm 0.7
Number of wires 2
Min. bending radius
During handling and installation, cable cm 13
In final installation, cable cm 9
During handling and installation, cable m 0.13
In final installation, cable m 0.09
Max. pulling force
Pulling-eye kN 0.05
Pulling-stocking kN 0.06
Resistance 20 °C Ω/km 12,1
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301692
Reka code 1146542

2x2,5 N

Electric number Size Packaging Voltage

2x2,5 N

Nominal diameter of complete cable mm 12
Nominal weight of cable kg/km 200
Conductor material Copper
Nominal cross-sectional area of conductor mm2 2.5
Nominal thickness of insulation mm 0.7
Number of wires 2
Min. bending radius
During handling and installation, cable cm 14
In final installation, cable cm 10
During handling and installation, cable m 0.14
In final installation, cable m 0.1
Max. pulling force
Pulling-eye kN 0.08
Pulling-stocking kN 0.1
Resistance 20 °C Ω/km 7,41
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301739
Reka code 1146543
Nominal diameter of complete cable mm 12
Nominal weight of cable kg/km 200
Conductor material Copper
Nominal cross-sectional area of conductor mm2 2.5
Nominal thickness of insulation mm 0.7
Number of wires 2
Min. bending radius
During handling and installation, cable cm 14
In final installation, cable cm 10
During handling and installation, cable m 0.14
In final installation, cable m 0.1
Max. pulling force
Pulling-eye kN 0.08
Pulling-stocking kN 0.1
Resistance 20 °C Ω/km 7,41
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301746
Reka code 1146543

2x4 N

Electric number Size Packaging Voltage

2x4 N

Nominal diameter of complete cable mm 13
Nominal weight of cable kg/km 254
Conductor material Copper
Nominal cross-sectional area of conductor mm2 4
Nominal thickness of insulation mm 0.7
Number of wires 2
Min. bending radius
During handling and installation, cable cm 15
In final installation, cable cm 11
During handling and installation, cable m 0.15
In final installation, cable m 0.11
Max. pulling force
Pulling-eye kN 0.12
Pulling-stocking kN 0.16
Resistance 20 °C Ω/km 4,61
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301760
Reka code 1146544

2x6 N

Electric number Size Packaging Voltage

2x6 N

Nominal diameter of complete cable mm 14
Nominal weight of cable kg/km 339
Conductor material Copper
Nominal cross-sectional area of conductor mm2 6
Nominal thickness of insulation mm 0.7
Number of wires 2
Min. bending radius
During handling and installation, cable cm 17
In final installation, cable cm 12
During handling and installation, cable m 0.17
In final installation, cable m 0.12
Max. pulling force
Pulling-eye kN 0.18
Pulling-stocking kN 0.24
Resistance 20 °C Ω/km 3,08
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301784
Reka code 1146545

3x1,5

Electric number Size Packaging Voltage

3x1,5

Nominal diameter of complete cable mm 11
Nominal weight of cable kg/km 181
Conductor material Copper
Nominal cross-sectional area of conductor mm2 1.5
Nominal thickness of insulation mm 0.7
Number of wires 3
Min. bending radius
During handling and installation, cable cm 14
In final installation, cable cm 9
During handling and installation, cable m 0.14
In final installation, cable m 0.1
Max. pulling force
Pulling-eye kN 0.07
Pulling-stocking kN 0.09
Resistance 20 °C Ω/km 12,1
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301814
Reka code 1146546
Nominal diameter of complete cable mm 11
Nominal weight of cable kg/km 181
Conductor material Copper
Nominal cross-sectional area of conductor mm2 1.5
Nominal thickness of insulation mm 0.7
Number of wires 3
Min. bending radius
During handling and installation, cable cm 14
In final installation, cable cm 9
During handling and installation, cable m 0.14
In final installation, cable m 0.1
Max. pulling force
Pulling-eye kN 0.07
Pulling-stocking kN 0.09
Resistance 20 °C Ω/km 12,1
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301821
Reka code 1146546

3G1,5

Electric number Size Packaging Voltage

3G1,5

Nominal diameter of complete cable mm 11
Nominal weight of cable kg/km 181
Conductor material Copper
Nominal cross-sectional area of conductor mm2 1.5
Nominal thickness of insulation mm 0.7
Number of wires 3
Min. bending radius
During handling and installation, cable cm 14
In final installation, cable cm 9
During handling and installation, cable m 0.14
In final installation, cable m 0.1
Max. pulling force
Pulling-eye kN 0.07
Pulling-stocking kN 0.09
Resistance 20 °C Ω/km 12,1
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301869
Reka code 1146547
Nominal diameter of complete cable mm 11
Nominal weight of cable kg/km 181
Conductor material Copper
Nominal cross-sectional area of conductor mm2 1.5
Nominal thickness of insulation mm 0.7
Number of wires 3
Min. bending radius
During handling and installation, cable cm 14
In final installation, cable cm 9
During handling and installation, cable m 0.14
In final installation, cable m 0.1
Max. pulling force
Pulling-eye kN 0.07
Pulling-stocking kN 0.09
Resistance 20 °C Ω/km 12,1
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301876
Reka code 1146547
Nominal diameter of complete cable mm 11
Nominal weight of cable kg/km 181
Conductor material Copper
Nominal cross-sectional area of conductor mm2 1.5
Nominal thickness of insulation mm 0.7
Number of wires 3
Min. bending radius
During handling and installation, cable cm 14
In final installation, cable cm 9
During handling and installation, cable m 0.14
In final installation, cable m 0.1
Max. pulling force
Pulling-eye kN 0.07
Pulling-stocking kN 0.09
Resistance 20 °C Ω/km 12,1
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301852
Reka code 1146547

3G2,5

Electric number Size Packaging Voltage

3G2,5

Nominal diameter of complete cable mm 12
Nominal weight of cable kg/km 223
Conductor material Copper
Nominal cross-sectional area of conductor mm2 2.5
Nominal thickness of insulation mm 0.7
Number of wires 3
Min. bending radius
During handling and installation, cable cm 15
In final installation, cable cm 10
During handling and installation, cable m 0.14
In final installation, cable m 0.1
Max. pulling force
Pulling-eye kN 0.11
Pulling-stocking kN 0.15
Resistance 20 °C Ω/km 7,41
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301913
Reka code 1146548
Nominal diameter of complete cable mm 12
Nominal weight of cable kg/km 223
Conductor material Copper
Nominal cross-sectional area of conductor mm2 2.5
Nominal thickness of insulation mm 0.7
Number of wires 3
Min. bending radius
During handling and installation, cable cm 15
In final installation, cable cm 10
During handling and installation, cable m 0.14
In final installation, cable m 0.1
Max. pulling force
Pulling-eye kN 0.11
Pulling-stocking kN 0.15
Resistance 20 °C Ω/km 7,41
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301906
Reka code 1146548
Nominal diameter of complete cable mm 12
Nominal weight of cable kg/km 223
Conductor material Copper
Nominal cross-sectional area of conductor mm2 2.5
Nominal thickness of insulation mm 0.7
Number of wires 3
Min. bending radius
During handling and installation, cable cm 15
In final installation, cable cm 10
During handling and installation, cable m 0.14
In final installation, cable m 0.1
Max. pulling force
Pulling-eye kN 0.11
Pulling-stocking kN 0.15
Resistance 20 °C Ω/km 7,41
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301890
Reka code 1146548

3G4

Electric number Size Packaging Voltage

3G4

Nominal diameter of complete cable mm 13
Nominal weight of cable kg/km 291
Conductor material Copper
Nominal cross-sectional area of conductor mm2 4
Nominal thickness of insulation mm 0.7
Number of wires 3
Min. bending radius
During handling and installation, cable cm 16
In final installation, cable cm 11
During handling and installation, cable m 0.16
In final installation, cable m 0.11
Max. pulling force
Pulling-eye kN 0.18
Pulling-stocking kN 0.24
Resistance 20 °C Ω/km 4,61
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301920
Reka code 1146549

3G6

Electric number Size Packaging Voltage

3G6

Nominal diameter of complete cable mm 15
Nominal weight of cable kg/km 391
Conductor material Copper
Nominal cross-sectional area of conductor mm2 6
Nominal thickness of insulation mm 0.7
Number of wires 3
Min. bending radius
During handling and installation, cable cm 18
In final installation, cable cm 13
During handling and installation, cable m 0.18
In final installation, cable m 0.13
Max. pulling force
Pulling-eye kN 0.27
Pulling-stocking kN 0.36
Resistance 20 °C Ω/km 3,08
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301944
Reka code 1146550

3G10

Electric number Size Packaging Voltage

3G10

Nominal diameter of complete cable mm 17
Nominal weight of cable kg/km 541
Conductor material Copper
Nominal cross-sectional area of conductor mm2 10
Nominal thickness of insulation mm 0.7
Number of wires 3
Min. bending radius
During handling and installation, cable cm 20
In final installation, cable cm 14
During handling and installation, cable m 0.2
In final installation, cable m 0.14
Max. pulling force
Pulling-eye kN 0.45
Pulling-stocking kN 0.6
Resistance 20 °C Ω/km 1,83
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301968
Reka code 1146551

3G16

Electric number Size Packaging Voltage

3G16

Nominal diameter of complete cable mm 19
Nominal weight of cable kg/km 758
Conductor material Copper
Nominal cross-sectional area of conductor mm2 16
Nominal thickness of insulation mm 0.7
Number of wires 3
Min. bending radius
During handling and installation, cable cm 23
In final installation, cable cm 16
During handling and installation, cable m 0.23
In final installation, cable m 0.16
Max. pulling force
Pulling-eye kN 0.72
Pulling-stocking kN 0.96
Resistance 20 °C Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301982
Reka code 1146552

3G25

Electric number Size Packaging Voltage

3G25

Nominal diameter of complete cable mm 24
Nominal weight of cable kg/km 1172
Conductor material Copper
Nominal cross-sectional area of conductor mm2 25
Nominal thickness of insulation mm 0.9
Number of wires 3
Min. bending radius
During handling and installation, cable cm 29
In final installation, cable cm 20
During handling and installation, cable m 0.28
In final installation, cable m 0.2
Max. pulling force
Pulling-eye kN 1.13
Pulling-stocking kN 1.5
Resistance 20 °C Ω/km 0,727
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302002
Reka code 1146553

3G35

Electric number Size Packaging Voltage

3G35

Nominal diameter of complete cable mm 25
Nominal weight of cable kg/km 1514
Conductor material Copper
Nominal cross-sectional area of conductor mm2 35
Nominal thickness of insulation mm 0.9
Number of wires 3
Min. bending radius
During handling and installation, cable cm 31
In final installation, cable cm 21
During handling and installation, cable m 0.31
In final installation, cable m 0.21
Max. pulling force
Pulling-eye kN 1.58
Pulling-stocking kN 2.1
Resistance 20 °C Ω/km 0,524
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302026
Reka code 1146554

3G50

Electric number Size Packaging Voltage

3G50

Nominal diameter of complete cable mm 29
Nominal weight of cable kg/km 1993
Conductor material Copper
Nominal cross-sectional area of conductor mm2 50
Nominal thickness of insulation mm 1
Number of wires 3
Min. bending radius
During handling and installation, cable cm 35
In final installation, cable cm 24
During handling and installation, cable m 0.35
In final installation, cable m 0.24
Max. pulling force
Pulling-eye kN 2.25
Pulling-stocking kN 3
Resistance 20 °C Ω/km 0,387
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302040
Reka code 1146555

4G1,5

Electric number Size Packaging Voltage

4G1,5

Nominal diameter of complete cable mm 12
Nominal weight of cable kg/km 213
Conductor material Copper
Nominal cross-sectional area of conductor mm2 1.5
Nominal thickness of insulation mm 0.7
Number of wires 4
Min. bending radius
During handling and installation, cable cm 15
In final installation, cable cm 10
During handling and installation, cable m 0.14
In final installation, cable m 0.1
Max. pulling force
Pulling-eye kN 0.09
Pulling-stocking kN 0.12
Resistance 20 °C Ω/km 12,1
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302071
Reka code 1146558
Nominal diameter of complete cable mm 12
Nominal weight of cable kg/km 213
Conductor material Copper
Nominal cross-sectional area of conductor mm2 1.5
Nominal thickness of insulation mm 0.7
Number of wires 4
Min. bending radius
During handling and installation, cable cm 15
In final installation, cable cm 10
During handling and installation, cable m 0.14
In final installation, cable m 0.1
Max. pulling force
Pulling-eye kN 0.09
Pulling-stocking kN 0.12
Resistance 20 °C Ω/km 12,1
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302088
Reka code 1146558

4G2,5

Electric number Size Packaging Voltage

4G2,5

Nominal diameter of complete cable mm 13
Nominal weight of cable kg/km 266
Conductor material Copper
Nominal cross-sectional area of conductor mm2 2.5
Nominal thickness of insulation mm 0.7
Number of wires 4
Min. bending radius
During handling and installation, cable cm 16
In final installation, cable cm 11
During handling and installation, cable m 0.16
In final installation, cable m 0.11
Max. pulling force
Pulling-eye kN 0.15
Pulling-stocking kN 0.2
Resistance 20 °C Ω/km 7,41
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302125
Reka code 1146559
Nominal diameter of complete cable mm 13
Nominal weight of cable kg/km 266
Conductor material Copper
Nominal cross-sectional area of conductor mm2 2.5
Nominal thickness of insulation mm 0.7
Number of wires 4
Min. bending radius
During handling and installation, cable cm 16
In final installation, cable cm 11
During handling and installation, cable m 0.16
In final installation, cable m 0.11
Max. pulling force
Pulling-eye kN 0.15
Pulling-stocking kN 0.2
Resistance 20 °C Ω/km 7,41
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302118
Reka code 1146559

4G4

Electric number Size Packaging Voltage

4G4

Nominal diameter of complete cable mm 14
Nominal weight of cable kg/km 351
Conductor material Copper
Nominal cross-sectional area of conductor mm2 4
Nominal thickness of insulation mm 0.7
Number of wires 4
Min. bending radius
During handling and installation, cable cm 17
In final installation, cable cm 12
During handling and installation, cable m 0.17
In final installation, cable m 0.12
Max. pulling force
Pulling-eye kN 0.24
Pulling-stocking kN 0.32
Resistance 20 °C Ω/km 4,61
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302149
Reka code 1146560

4G6

Electric number Size Packaging Voltage

4G6

Nominal diameter of complete cable mm 16
Nominal weight of cable kg/km 473
Conductor material Copper
Nominal cross-sectional area of conductor mm2 6
Nominal thickness of insulation mm 0.7
Number of wires 4
Min. bending radius
During handling and installation, cable cm 20
In final installation, cable cm 14
During handling and installation, cable m 0.2
In final installation, cable m 0.14
Max. pulling force
Pulling-eye kN 0.36
Pulling-stocking kN 0.48
Resistance 20 °C Ω/km 3,08
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302163
Reka code 1146561

4G10

Electric number Size Packaging Voltage

4G10

Nominal diameter of complete cable mm 18
Nominal weight of cable kg/km 673
Conductor material Copper
Nominal cross-sectional area of conductor mm2 10
Nominal thickness of insulation mm 0.7
Number of wires 4
Min. bending radius
During handling and installation, cable cm 22
In final installation, cable cm 15
During handling and installation, cable m 0.22
In final installation, cable m 0.15
Max. pulling force
Pulling-eye kN 0.6
Pulling-stocking kN 0.8
Resistance 20 °C Ω/km 1,83
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302187
Reka code 1146562

4G16

Electric number Size Packaging Voltage

4G16

Nominal diameter of complete cable mm 21
Nominal weight of cable kg/km 949
Conductor material Copper
Nominal cross-sectional area of conductor mm2 16
Nominal thickness of insulation mm 0.7
Number of wires 4
Min. bending radius
During handling and installation, cable cm 25
In final installation, cable cm 18
During handling and installation, cable m 0.25
In final installation, cable m 0.18
Max. pulling force
Pulling-eye kN 0.96
Pulling-stocking kN 1.28
Resistance 20 °C Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302200
Reka code 1146563

4G25

Electric number Size Packaging Voltage

4G25

Nominal diameter of complete cable mm 26
Nominal weight of cable kg/km 1489
Conductor material Copper
Nominal cross-sectional area of conductor mm2 25
Nominal thickness of insulation mm 0.9
Number of wires 4
Min. bending radius
During handling and installation, cable cm 31
In final installation, cable cm 22
During handling and installation, cable m 0.31
In final installation, cable m 0.22
Max. pulling force
Pulling-eye kN 1.5
Pulling-stocking kN 2
Resistance 20 °C Ω/km 0,727
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302224
Reka code 1146564

4G35

Electric number Size Packaging Voltage

4G35

Nominal diameter of complete cable mm 27
Nominal weight of cable kg/km 1854
Conductor material Copper
Nominal cross-sectional area of conductor mm2 35
Nominal thickness of insulation mm 0.9
Number of wires 4
Min. bending radius
During handling and installation, cable cm 33
In final installation, cable cm 23
During handling and installation, cable m 0.33
In final installation, cable m 0.23
Max. pulling force
Pulling-eye kN 2.1
Pulling-stocking kN 2.8
Resistance 20 °C Ω/km 0,524
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302248
Reka code 1146565

4G50

Electric number Size Packaging Voltage

4G50

Nominal diameter of complete cable mm 31
Nominal weight of cable kg/km 2472
Conductor material Copper
Nominal cross-sectional area of conductor mm2 50
Nominal thickness of insulation mm 1
Number of wires 4
Min. bending radius
During handling and installation, cable cm 38
In final installation, cable cm 26
During handling and installation, cable m 0.38
In final installation, cable m 0.26
Max. pulling force
Pulling-eye kN 3
Pulling-stocking kN 4
Resistance 20 °C Ω/km 0,387
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302262
Reka code 1146566

5G1,5

Electric number Size Packaging Voltage

5G1,5

Nominal diameter of complete cable mm 13
Nominal weight of cable kg/km 244
Conductor material Copper
Nominal cross-sectional area of conductor mm2 1.5
Nominal thickness of insulation mm 0.7
Number of wires 5
Min. bending radius
During handling and installation, cable cm 16
In final installation, cable cm 11
During handling and installation, cable m 0.16
In final installation, cable m 0.11
Max. pulling force
Pulling-eye kN 0.11
Pulling-stocking kN 0.15
Resistance 20 °C Ω/km 12,1
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302316
Reka code 1146569
Nominal diameter of complete cable mm 13
Nominal weight of cable kg/km 244
Conductor material Copper
Nominal cross-sectional area of conductor mm2 1.5
Nominal thickness of insulation mm 0.7
Number of wires 5
Min. bending radius
During handling and installation, cable cm 16
In final installation, cable cm 11
During handling and installation, cable m 0.16
In final installation, cable m 0.11
Max. pulling force
Pulling-eye kN 0.11
Pulling-stocking kN 0.15
Resistance 20 °C Ω/km 12,1
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302309
Reka code 1146569
Nominal diameter of complete cable mm 13
Nominal weight of cable kg/km 244
Conductor material Copper
Nominal cross-sectional area of conductor mm2 1.5
Nominal thickness of insulation mm 0.7
Number of wires 5
Min. bending radius
During handling and installation, cable cm 16
In final installation, cable cm 11
During handling and installation, cable m 0.16
In final installation, cable m 0.11
Max. pulling force
Pulling-eye kN 0.11
Pulling-stocking kN 0.15
Resistance 20 °C Ω/km 12,1
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302293
Reka code 1146569

5G2,5

Electric number Size Packaging Voltage

5G2,5

Nominal diameter of complete cable mm 14
Nominal weight of cable kg/km 314
Conductor material Copper
Nominal cross-sectional area of conductor mm2 2.5
Nominal thickness of insulation mm 0.7
Number of wires 5
Min. bending radius
During handling and installation, cable cm 17
In final installation, cable cm 12
During handling and installation, cable m 0.17
In final installation, cable m 0.12
Max. pulling force
Pulling-eye kN 0.19
Pulling-stocking kN 0.25
Resistance 20 °C Ω/km 7,41
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302354
Reka code 1146570
Nominal diameter of complete cable mm 14
Nominal weight of cable kg/km 314
Conductor material Copper
Nominal cross-sectional area of conductor mm2 2.5
Nominal thickness of insulation mm 0.7
Number of wires 5
Min. bending radius
During handling and installation, cable cm 17
In final installation, cable cm 12
During handling and installation, cable m 0.17
In final installation, cable m 0.12
Max. pulling force
Pulling-eye kN 0.19
Pulling-stocking kN 0.25
Resistance 20 °C Ω/km 7,41
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302323
Reka code 1146570
Nominal diameter of complete cable mm 14
Nominal weight of cable kg/km 314
Conductor material Copper
Nominal cross-sectional area of conductor mm2 2.5
Nominal thickness of insulation mm 0.7
Number of wires 5
Min. bending radius
During handling and installation, cable cm 17
In final installation, cable cm 12
During handling and installation, cable m 0.17
In final installation, cable m 0.12
Max. pulling force
Pulling-eye kN 0.19
Pulling-stocking kN 0.25
Resistance 20 °C Ω/km 7,41
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302347
Reka code 1146570

5G4

Electric number Size Packaging Voltage

5G4

Nominal diameter of complete cable mm 15
Nominal weight of cable kg/km 417
Conductor material Copper
Nominal cross-sectional area of conductor mm2 4
Nominal thickness of insulation mm 0.7
Number of wires 5
Min. bending radius
During handling and installation, cable cm 19
In final installation, cable cm 13
During handling and installation, cable m 0.18
In final installation, cable m 0.13
Max. pulling force
Pulling-eye kN 0.3
Pulling-stocking kN 0.4
Resistance 20 °C Ω/km 4,61
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302361
Reka code 1146571

5G6

Electric number Size Packaging Voltage

5G6

Nominal diameter of complete cable mm 18
Nominal weight of cable kg/km 568
Conductor material Copper
Nominal cross-sectional area of conductor mm2 6
Nominal thickness of insulation mm 0.7
Number of wires 5
Min. bending radius
During handling and installation, cable cm 21
In final installation, cable cm 15
During handling and installation, cable m 0.21
In final installation, cable m 0.15
Max. pulling force
Pulling-eye kN 0.45
Pulling-stocking kN 0.6
Resistance 20 °C Ω/km 3,08
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302385
Reka code 1146572

5G10

Electric number Size Packaging Voltage

5G10

Nominal diameter of complete cable mm 20
Nominal weight of cable kg/km 807
Conductor material Copper
Nominal cross-sectional area of conductor mm2 10
Nominal thickness of insulation mm 0.7
Number of wires 5
Min. bending radius
During handling and installation, cable cm 24
In final installation, cable cm 17
During handling and installation, cable m 0.24
In final installation, cable m 0.17
Max. pulling force
Pulling-eye kN 0.75
Pulling-stocking kN 1
Resistance 20 °C Ω/km 1,83
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302408
Reka code 1146573

5G16

Electric number Size Packaging Voltage

5G16

Nominal diameter of complete cable mm 23
Nominal weight of cable kg/km 1156
Conductor material Copper
Nominal cross-sectional area of conductor mm2 16
Nominal thickness of insulation mm 0.7
Number of wires 5
Min. bending radius
During handling and installation, cable cm 28
In final installation, cable cm 19
During handling and installation, cable m 0.28
In final installation, cable m 0.2
Max. pulling force
Pulling-eye kN 1.2
Pulling-stocking kN 1.6
Resistance 20 °C Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302422
Reka code 1146574

5G25

Electric number Size Packaging Voltage

5G25

Nominal diameter of complete cable mm 29
Nominal weight of cable kg/km 1850
Conductor material Copper
Nominal cross-sectional area of conductor mm2 25
Nominal thickness of insulation mm 0.9
Number of wires 5
Min. bending radius
During handling and installation, cable cm 35
In final installation, cable cm 24
During handling and installation, cable m 0.35
In final installation, cable m 0.24
Max. pulling force
Pulling-eye kN 1.88
Pulling-stocking kN 2.5
Resistance 20 °C Ω/km 0,727
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302446
Reka code 1146575

5G35

Electric number Size Packaging Voltage

5G35

Nominal diameter of complete cable mm 31
Nominal weight of cable kg/km 2321
Conductor material Copper
Nominal cross-sectional area of conductor mm2 35
Nominal thickness of insulation mm 0.9
Number of wires 5
Min. bending radius
During handling and installation, cable cm 37
In final installation, cable cm 26
During handling and installation, cable m 0.37
In final installation, cable m 0.26
Max. pulling force
Pulling-eye kN 2.63
Pulling-stocking kN 3.5
Resistance 20 °C Ω/km 0,524
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302460
Reka code 1146576

5G50

Electric number Size Packaging Voltage

5G50

Nominal diameter of complete cable mm 35
Nominal weight of cable kg/km 3137
Conductor material Copper
Nominal cross-sectional area of conductor mm2 50
Nominal thickness of insulation mm 1
Number of wires 5
Min. bending radius
During handling and installation, cable cm 42
In final installation, cable cm 30
During handling and installation, cable m 0.42
In final installation, cable m 0.29
Max. pulling force
Pulling-eye kN 3.75
Pulling-stocking kN 5
Resistance 20 °C Ω/km 0,387
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302484
Reka code 1146577