FRHF / BFXI

Download product group datasheet

Fire-resistant power cable for fixed installations indoors and outdoors. Not to be laid in soil nor directly in cast concrete. For locations where safety requires the operation of alarm, control, signalling and energy circuits also during a fire. The conductor insulation must be protected against UV-radiation. Installations must be in accordance with national regulations and rules of installations. No requirement for CPR-classification.

Standards SFS 5545, HD 604 5 D, IEC 60502-1
Product Environmental Profile (PEP) PEP NXNS-00708-V0101-EN.pdf
PEP NXNS-00709-V0101-EN.pdf
Conductor 1,5-4 mm² circular solid copper, EN/IEC 60228 class 1
6-95 mm² circular stranded copper, EN/IEC 60228 class 2
Insulation Cross-linked polyethylene XLPE and mica-tape
Core Identification (all color combinations in the cable family) 2x: Blue, brown
3x: Brown, black, grey
3G: Yellow-green, blue, brown
4G: Yellow-green, blue, brown, black (1,5 and 2,5 mm²)
4G: Yellow-green, brown, black, grey (4 mm² and above)
5G: Yellow-green, blue, brown, black, grey
Inner covering Extruded filling compound
Oversheath UV-protected polyolefin compound
Colour of the oversheath Orange

2x1,5 N

Electric number Size Packaging Voltage

2x1,5 N

Nominal diameter of complete cable mm 11
Nominal weight of cable kg/km 166
Conductor material Copper
Nominal cross-sectional area of conductor mm2 1.5
Nominal thickness of insulation mm 0,7
Number of wires 2
Min. bending radius
During handling and installation, cable mm 130
In final installation, cable mm 91
During handling and installation, cable cm 13
In final installation, cable cm 9
During handling and installation, cable m 0.13
In final installation, cable m 0.09
Max. pulling force
Pulling-eye kN 0.15
Pulling-stocking kN 0.06
Resistance 20 °C Ω/km 12,1
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301708
Reka code 1146542
Nominal diameter of complete cable mm 11
Nominal weight of cable kg/km 166
Conductor material Copper
Nominal cross-sectional area of conductor mm2 1.5
Nominal thickness of insulation mm 0,7
Number of wires 2
Min. bending radius
During handling and installation, cable mm 130
In final installation, cable mm 91
During handling and installation, cable cm 13
In final installation, cable cm 9
During handling and installation, cable m 0.13
In final installation, cable m 0.09
Max. pulling force
Pulling-eye kN 0.15
Pulling-stocking kN 0.06
Resistance 20 °C Ω/km 12,1
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301692
Reka code 1146542

2x2,5 N

Electric number Size Packaging Voltage

2x2,5 N

Nominal diameter of complete cable mm 12
Nominal weight of cable kg/km 201
Conductor material Copper
Nominal cross-sectional area of conductor mm2 2.5
Nominal thickness of insulation mm 0,7
Number of wires 2
Min. bending radius
During handling and installation, cable mm 139
In final installation, cable mm 97
During handling and installation, cable cm 14
In final installation, cable cm 10
During handling and installation, cable m 0.14
In final installation, cable m 0.1
Max. pulling force
Pulling-eye kN 0.25
Pulling-stocking kN 0.1
Resistance 20 °C Ω/km 7,41
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301739
Reka code 1146543
Nominal diameter of complete cable mm 12
Nominal weight of cable kg/km 201
Conductor material Copper
Nominal cross-sectional area of conductor mm2 2.5
Nominal thickness of insulation mm 0,7
Number of wires 2
Min. bending radius
During handling and installation, cable mm 139
In final installation, cable mm 97
During handling and installation, cable cm 14
In final installation, cable cm 10
During handling and installation, cable m 0.14
In final installation, cable m 0.1
Max. pulling force
Pulling-eye kN 0.25
Pulling-stocking kN 0.1
Resistance 20 °C Ω/km 7,41
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301746
Reka code 1146543

2x4 N

Electric number Size Packaging Voltage

2x4 N

Nominal diameter of complete cable mm 13
Nominal weight of cable kg/km 256
Conductor material Copper
Nominal cross-sectional area of conductor mm2 4
Nominal thickness of insulation mm 0,7
Number of wires 2
Min. bending radius
During handling and installation, cable mm 151
In final installation, cable mm 106
During handling and installation, cable cm 15
In final installation, cable cm 11
During handling and installation, cable m 0.15
In final installation, cable m 0.11
Max. pulling force
Pulling-eye kN 0.4
Pulling-stocking kN 0.16
Resistance 20 °C Ω/km 4,61
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301760
Reka code 1146544

2x6 N

Electric number Size Packaging Voltage

2x6 N

Nominal diameter of complete cable mm 14
Nominal weight of cable kg/km 341
Conductor material Copper
Nominal cross-sectional area of conductor mm2 6
Nominal thickness of insulation mm 0,7
Number of wires 2
Min. bending radius
During handling and installation, cable mm 172
In final installation, cable mm 120
During handling and installation, cable cm 17
In final installation, cable cm 12
During handling and installation, cable m 0.17
In final installation, cable m 0.12
Max. pulling force
Pulling-eye kN 0.6
Pulling-stocking kN 0.24
Resistance 20 °C Ω/km 3,08
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301784
Reka code 1146545

3x1,5

Electric number Size Packaging Voltage

3x1,5

Nominal diameter of complete cable mm 11
Nominal weight of cable kg/km 182
Conductor material Copper
Nominal cross-sectional area of conductor mm2 1.5
Nominal thickness of insulation mm 0,7
Number of wires 3
Min. bending radius
During handling and installation, cable mm 135
In final installation, cable mm 95
During handling and installation, cable cm 14
In final installation, cable cm 9
During handling and installation, cable m 0.14
In final installation, cable m 0.1
Max. pulling force
Pulling-eye kN 0.225
Pulling-stocking kN 0.09
Resistance 20 °C Ω/km 12,1
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301814
Reka code 1146546
Nominal diameter of complete cable mm 11
Nominal weight of cable kg/km 182
Conductor material Copper
Nominal cross-sectional area of conductor mm2 1.5
Nominal thickness of insulation mm 0,7
Number of wires 3
Min. bending radius
During handling and installation, cable mm 135
In final installation, cable mm 95
During handling and installation, cable cm 14
In final installation, cable cm 9
During handling and installation, cable m 0.14
In final installation, cable m 0.1
Max. pulling force
Pulling-eye kN 0.225
Pulling-stocking kN 0.09
Resistance 20 °C Ω/km 12,1
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301821
Reka code 1146546

3G1,5

Electric number Size Packaging Voltage

3G1,5

Nominal diameter of complete cable mm 11
Nominal weight of cable kg/km 182
Conductor material Copper
Nominal cross-sectional area of conductor mm2 1.5
Nominal thickness of insulation mm 0,7
Number of wires 3
Min. bending radius
During handling and installation, cable mm 135
In final installation, cable mm 95
During handling and installation, cable cm 14
In final installation, cable cm 9
During handling and installation, cable m 0.14
In final installation, cable m 0.1
Max. pulling force
Pulling-eye kN 0.225
Pulling-stocking kN 0.09
Resistance 20 °C Ω/km 12,1
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301869
Reka code 1146547
Nominal diameter of complete cable mm 11
Nominal weight of cable kg/km 182
Conductor material Copper
Nominal cross-sectional area of conductor mm2 1.5
Nominal thickness of insulation mm 0,7
Number of wires 3
Min. bending radius
During handling and installation, cable mm 135
In final installation, cable mm 95
During handling and installation, cable cm 14
In final installation, cable cm 9
During handling and installation, cable m 0.14
In final installation, cable m 0.1
Max. pulling force
Pulling-eye kN 0.225
Pulling-stocking kN 0.09
Resistance 20 °C Ω/km 12,1
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301876
Reka code 1146547
Nominal diameter of complete cable mm 11
Nominal weight of cable kg/km 182
Conductor material Copper
Nominal cross-sectional area of conductor mm2 1.5
Nominal thickness of insulation mm 0,7
Number of wires 3
Min. bending radius
During handling and installation, cable mm 135
In final installation, cable mm 95
During handling and installation, cable cm 14
In final installation, cable cm 9
During handling and installation, cable m 0.14
In final installation, cable m 0.1
Max. pulling force
Pulling-eye kN 0.225
Pulling-stocking kN 0.09
Resistance 20 °C Ω/km 12,1
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301852
Reka code 1146547

3G2,5

Electric number Size Packaging Voltage

3G2,5

Nominal diameter of complete cable mm 12
Nominal weight of cable kg/km 225
Conductor material Copper
Nominal cross-sectional area of conductor mm2 2.5
Nominal thickness of insulation mm 0,7
Number of wires 3
Min. bending radius
During handling and installation, cable mm 145
In final installation, cable mm 102
During handling and installation, cable cm 15
In final installation, cable cm 10
During handling and installation, cable m 0.14
In final installation, cable m 0.1
Max. pulling force
Pulling-eye kN 0.375
Pulling-stocking kN 0.15
Resistance 20 °C Ω/km 7,41
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301913
Reka code 1146548
Nominal diameter of complete cable mm 12
Nominal weight of cable kg/km 225
Conductor material Copper
Nominal cross-sectional area of conductor mm2 2.5
Nominal thickness of insulation mm 0,7
Number of wires 3
Min. bending radius
During handling and installation, cable mm 145
In final installation, cable mm 102
During handling and installation, cable cm 15
In final installation, cable cm 10
During handling and installation, cable m 0.14
In final installation, cable m 0.1
Max. pulling force
Pulling-eye kN 0.375
Pulling-stocking kN 0.15
Resistance 20 °C Ω/km 7,41
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301906
Reka code 1146548
Nominal diameter of complete cable mm 12
Nominal weight of cable kg/km 225
Conductor material Copper
Nominal cross-sectional area of conductor mm2 2.5
Nominal thickness of insulation mm 0,7
Number of wires 3
Min. bending radius
During handling and installation, cable mm 145
In final installation, cable mm 102
During handling and installation, cable cm 15
In final installation, cable cm 10
During handling and installation, cable m 0.14
In final installation, cable m 0.1
Max. pulling force
Pulling-eye kN 0.375
Pulling-stocking kN 0.15
Resistance 20 °C Ω/km 7,41
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301890
Reka code 1146548

3G4

Electric number Size Packaging Voltage

3G4

Nominal diameter of complete cable mm 13
Nominal weight of cable kg/km 293
Conductor material Copper
Nominal cross-sectional area of conductor mm2 4
Nominal thickness of insulation mm 0,7
Number of wires 3
Min. bending radius
During handling and installation, cable mm 158
In final installation, cable mm 111
During handling and installation, cable cm 16
In final installation, cable cm 11
During handling and installation, cable m 0.16
In final installation, cable m 0.11
Max. pulling force
Pulling-eye kN 0.6
Pulling-stocking kN 0.24
Resistance 20 °C Ω/km 4,61
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301920
Reka code 1146549

3G6

Electric number Size Packaging Voltage

3G6

Nominal diameter of complete cable mm 15
Nominal weight of cable kg/km 393
Conductor material Copper
Nominal cross-sectional area of conductor mm2 6
Nominal thickness of insulation mm 0,7
Number of wires 3
Min. bending radius
During handling and installation, cable mm 180
In final installation, cable mm 126
During handling and installation, cable cm 18
In final installation, cable cm 13
During handling and installation, cable m 0.18
In final installation, cable m 0.13
Max. pulling force
Pulling-eye kN 0.9
Pulling-stocking kN 0.36
Resistance 20 °C Ω/km 3,08
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301944
Reka code 1146550

3G10

Electric number Size Packaging Voltage

3G10

Nominal diameter of complete cable mm 17
Nominal weight of cable kg/km 543
Conductor material Copper
Nominal cross-sectional area of conductor mm2 10
Nominal thickness of insulation mm 0,7
Number of wires 3
Min. bending radius
During handling and installation, cable mm 203
In final installation, cable mm 142
During handling and installation, cable cm 20
In final installation, cable cm 14
During handling and installation, cable m 0.2
In final installation, cable m 0.14
Max. pulling force
Pulling-eye kN 1.5
Pulling-stocking kN 0.6
Resistance 20 °C Ω/km 1,83
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301968
Reka code 1146551

3G16

Electric number Size Packaging Voltage

3G16

Nominal diameter of complete cable mm 19
Nominal weight of cable kg/km 761
Conductor material Copper
Nominal cross-sectional area of conductor mm2 16
Nominal thickness of insulation mm 0,7
Number of wires 3
Min. bending radius
During handling and installation, cable mm 230
In final installation, cable mm 161
During handling and installation, cable cm 23
In final installation, cable cm 16
During handling and installation, cable m 0.23
In final installation, cable m 0.16
Max. pulling force
Pulling-eye kN 2.4
Pulling-stocking kN 0.96
Resistance 20 °C Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176301982
Reka code 1146552

3G25

Electric number Size Packaging Voltage

3G25

Nominal diameter of complete cable mm 24
Nominal weight of cable kg/km 1175
Conductor material Copper
Nominal cross-sectional area of conductor mm2 25
Nominal thickness of insulation mm 0,9
Number of wires 3
Min. bending radius
During handling and installation, cable mm 285
In final installation, cable mm 200
During handling and installation, cable cm 29
In final installation, cable cm 20
During handling and installation, cable m 0.28
In final installation, cable m 0.2
Max. pulling force
Pulling-eye kN 3.75
Pulling-stocking kN 1.5
Resistance 20 °C Ω/km 0,727
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302002
Reka code 1146553

3G35

Electric number Size Packaging Voltage

3G35

Nominal diameter of complete cable mm 25
Nominal weight of cable kg/km 1518
Conductor material Copper
Nominal cross-sectional area of conductor mm2 35
Nominal thickness of insulation mm 0,9
Number of wires 3
Min. bending radius
During handling and installation, cable mm 306
In final installation, cable mm 214
During handling and installation, cable cm 31
In final installation, cable cm 21
During handling and installation, cable m 0.31
In final installation, cable m 0.21
Max. pulling force
Pulling-eye kN 5.25
Pulling-stocking kN 2.1
Resistance 20 °C Ω/km 0,524
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302026
Reka code 1146554

3G50

Electric number Size Packaging Voltage

3G50

Nominal diameter of complete cable mm 29
Nominal weight of cable kg/km 1998
Conductor material Copper
Nominal cross-sectional area of conductor mm2 50
Nominal thickness of insulation mm 1,0
Number of wires 3
Min. bending radius
During handling and installation, cable mm 347
In final installation, cable mm 243
During handling and installation, cable cm 35
In final installation, cable cm 24
During handling and installation, cable m 0.35
In final installation, cable m 0.24
Max. pulling force
Pulling-eye kN 7.5
Pulling-stocking kN 3
Resistance 20 °C Ω/km 0,387
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302040
Reka code 1146555

4G1,5

Electric number Size Packaging Voltage

4G1,5

Nominal diameter of complete cable mm 12
Nominal weight of cable kg/km 211
Conductor material Copper
Nominal cross-sectional area of conductor mm2 1.5
Nominal thickness of insulation mm 0,7
Number of wires 4
Min. bending radius
During handling and installation, cable mm 145
In final installation, cable mm 102
During handling and installation, cable cm 15
In final installation, cable cm 10
During handling and installation, cable m 0.14
In final installation, cable m 0.1
Max. pulling force
Pulling-eye kN 0.3
Pulling-stocking kN 0.12
Resistance 20 °C Ω/km 12,1
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302071
Reka code 1146558
Nominal diameter of complete cable mm 12
Nominal weight of cable kg/km 211
Conductor material Copper
Nominal cross-sectional area of conductor mm2 1.5
Nominal thickness of insulation mm 0,7
Number of wires 4
Min. bending radius
During handling and installation, cable mm 145
In final installation, cable mm 102
During handling and installation, cable cm 15
In final installation, cable cm 10
During handling and installation, cable m 0.14
In final installation, cable m 0.1
Max. pulling force
Pulling-eye kN 0.3
Pulling-stocking kN 0.12
Resistance 20 °C Ω/km 12,1
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302088
Reka code 1146558

4G2,5

Electric number Size Packaging Voltage

4G2,5

Nominal diameter of complete cable mm 13
Nominal weight of cable kg/km 265
Conductor material Copper
Nominal cross-sectional area of conductor mm2 2.5
Nominal thickness of insulation mm 0,7
Number of wires 4
Min. bending radius
During handling and installation, cable mm 156
In final installation, cable mm 109
During handling and installation, cable cm 16
In final installation, cable cm 11
During handling and installation, cable m 0.16
In final installation, cable m 0.11
Max. pulling force
Pulling-eye kN 0.5
Pulling-stocking kN 0.2
Resistance 20 °C Ω/km 7,41
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302125
Reka code 1146559
Nominal diameter of complete cable mm 13
Nominal weight of cable kg/km 265
Conductor material Copper
Nominal cross-sectional area of conductor mm2 2.5
Nominal thickness of insulation mm 0,7
Number of wires 4
Min. bending radius
During handling and installation, cable mm 156
In final installation, cable mm 109
During handling and installation, cable cm 16
In final installation, cable cm 11
During handling and installation, cable m 0.16
In final installation, cable m 0.11
Max. pulling force
Pulling-eye kN 0.5
Pulling-stocking kN 0.2
Resistance 20 °C Ω/km 7,41
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302118
Reka code 1146559

4G4

Electric number Size Packaging Voltage

4G4

Nominal diameter of complete cable mm 14
Nominal weight of cable kg/km 353
Conductor material Copper
Nominal cross-sectional area of conductor mm2 4
Nominal thickness of insulation mm 0,7
Number of wires 4
Min. bending radius
During handling and installation, cable mm 171
In final installation, cable mm 120
During handling and installation, cable cm 17
In final installation, cable cm 12
During handling and installation, cable m 0.17
In final installation, cable m 0.12
Max. pulling force
Pulling-eye kN 0.8
Pulling-stocking kN 0.32
Resistance 20 °C Ω/km 4,61
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302149
Reka code 1146560

4G6

Electric number Size Packaging Voltage

4G6

Nominal diameter of complete cable mm 16
Nominal weight of cable kg/km 475
Conductor material Copper
Nominal cross-sectional area of conductor mm2 6
Nominal thickness of insulation mm 0,7
Number of wires 4
Min. bending radius
During handling and installation, cable mm 196
In final installation, cable mm 137
During handling and installation, cable cm 20
In final installation, cable cm 14
During handling and installation, cable m 0.2
In final installation, cable m 0.14
Max. pulling force
Pulling-eye kN 1.2
Pulling-stocking kN 0.48
Resistance 20 °C Ω/km 3,08
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302163
Reka code 1146561

4G10

Electric number Size Packaging Voltage

4G10

Nominal diameter of complete cable mm 18
Nominal weight of cable kg/km 676
Conductor material Copper
Nominal cross-sectional area of conductor mm2 10
Nominal thickness of insulation mm 0,7
Number of wires 4
Min. bending radius
During handling and installation, cable mm 221
In final installation, cable mm 155
During handling and installation, cable cm 22
In final installation, cable cm 15
During handling and installation, cable m 0.22
In final installation, cable m 0.15
Max. pulling force
Pulling-eye kN 2
Pulling-stocking kN 0.8
Resistance 20 °C Ω/km 1,83
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302187
Reka code 1146562

4G16

Electric number Size Packaging Voltage

4G16

Nominal diameter of complete cable mm 21
Nominal weight of cable kg/km 952
Conductor material Copper
Nominal cross-sectional area of conductor mm2 16
Nominal thickness of insulation mm 0,7
Number of wires 4
Min. bending radius
During handling and installation, cable mm 252
In final installation, cable mm 176
During handling and installation, cable cm 25
In final installation, cable cm 18
During handling and installation, cable m 0.25
In final installation, cable m 0.18
Max. pulling force
Pulling-eye kN 3.2
Pulling-stocking kN 1.28
Resistance 20 °C Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302200
Reka code 1146563

4G25

Electric number Size Packaging Voltage

4G25

Nominal diameter of complete cable mm 26
Nominal weight of cable kg/km 1493
Conductor material Copper
Nominal cross-sectional area of conductor mm2 25
Nominal thickness of insulation mm 0,9
Number of wires 4
Min. bending radius
During handling and installation, cable mm 314
In final installation, cable mm 220
During handling and installation, cable cm 31
In final installation, cable cm 22
During handling and installation, cable m 0.31
In final installation, cable m 0.22
Max. pulling force
Pulling-eye kN 5
Pulling-stocking kN 2
Resistance 20 °C Ω/km 0,727
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302224
Reka code 1146564

4G35

Electric number Size Packaging Voltage

4G35

Nominal diameter of complete cable mm 27
Nominal weight of cable kg/km 1858
Conductor material Copper
Nominal cross-sectional area of conductor mm2 35
Nominal thickness of insulation mm 0,9
Number of wires 4
Min. bending radius
During handling and installation, cable mm 329
In final installation, cable mm 230
During handling and installation, cable cm 33
In final installation, cable cm 23
During handling and installation, cable m 0.33
In final installation, cable m 0.23
Max. pulling force
Pulling-eye kN 7
Pulling-stocking kN 2.8
Resistance 20 °C Ω/km 0,524
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302248
Reka code 1146565

4G50

Electric number Size Packaging Voltage

4G50

Nominal diameter of complete cable mm 31
Nominal weight of cable kg/km 2477
Conductor material Copper
Nominal cross-sectional area of conductor mm2 50
Nominal thickness of insulation mm 1,0
Number of wires 4
Min. bending radius
During handling and installation, cable mm 377
In final installation, cable mm 264
During handling and installation, cable cm 38
In final installation, cable cm 26
During handling and installation, cable m 0.38
In final installation, cable m 0.26
Max. pulling force
Pulling-eye kN 10
Pulling-stocking kN 4
Resistance 20 °C Ω/km 0,387
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302262
Reka code 1146566

5G1,5

Electric number Size Packaging Voltage

5G1,5

Nominal diameter of complete cable mm 13
Nominal weight of cable kg/km 246
Conductor material Copper
Nominal cross-sectional area of conductor mm2 1.5
Nominal thickness of insulation mm 0,7
Number of wires 5
Min. bending radius
During handling and installation, cable mm 156
In final installation, cable mm 110
During handling and installation, cable cm 16
In final installation, cable cm 11
During handling and installation, cable m 0.16
In final installation, cable m 0.11
Max. pulling force
Pulling-eye kN 0.375
Pulling-stocking kN 0.15
Resistance 20 °C Ω/km 12,1
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302316
Reka code 1146569
Nominal diameter of complete cable mm 13
Nominal weight of cable kg/km 246
Conductor material Copper
Nominal cross-sectional area of conductor mm2 1.5
Nominal thickness of insulation mm 0,7
Number of wires 5
Min. bending radius
During handling and installation, cable mm 156
In final installation, cable mm 110
During handling and installation, cable cm 16
In final installation, cable cm 11
During handling and installation, cable m 0.16
In final installation, cable m 0.11
Max. pulling force
Pulling-eye kN 0.375
Pulling-stocking kN 0.15
Resistance 20 °C Ω/km 12,1
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302309
Reka code 1146569
Nominal diameter of complete cable mm 13
Nominal weight of cable kg/km 246
Conductor material Copper
Nominal cross-sectional area of conductor mm2 1.5
Nominal thickness of insulation mm 0,7
Number of wires 5
Min. bending radius
During handling and installation, cable mm 156
In final installation, cable mm 110
During handling and installation, cable cm 16
In final installation, cable cm 11
During handling and installation, cable m 0.16
In final installation, cable m 0.11
Max. pulling force
Pulling-eye kN 0.375
Pulling-stocking kN 0.15
Resistance 20 °C Ω/km 12,1
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302293
Reka code 1146569

5G2,5

Electric number Size Packaging Voltage

5G2,5

Nominal diameter of complete cable mm 14
Nominal weight of cable kg/km 316
Conductor material Copper
Nominal cross-sectional area of conductor mm2 2.5
Nominal thickness of insulation mm 0,7
Number of wires 5
Min. bending radius
During handling and installation, cable mm 169
In final installation, cable mm 118
During handling and installation, cable cm 17
In final installation, cable cm 12
During handling and installation, cable m 0.17
In final installation, cable m 0.12
Max. pulling force
Pulling-eye kN 0.625
Pulling-stocking kN 0.25
Resistance 20 °C Ω/km 7,41
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302354
Reka code 1146570
Nominal diameter of complete cable mm 14
Nominal weight of cable kg/km 316
Conductor material Copper
Nominal cross-sectional area of conductor mm2 2.5
Nominal thickness of insulation mm 0,7
Number of wires 5
Min. bending radius
During handling and installation, cable mm 169
In final installation, cable mm 118
During handling and installation, cable cm 17
In final installation, cable cm 12
During handling and installation, cable m 0.17
In final installation, cable m 0.12
Max. pulling force
Pulling-eye kN 0.625
Pulling-stocking kN 0.25
Resistance 20 °C Ω/km 7,41
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302323
Reka code 1146570
Nominal diameter of complete cable mm 14
Nominal weight of cable kg/km 316
Conductor material Copper
Nominal cross-sectional area of conductor mm2 2.5
Nominal thickness of insulation mm 0,7
Number of wires 5
Min. bending radius
During handling and installation, cable mm 169
In final installation, cable mm 118
During handling and installation, cable cm 17
In final installation, cable cm 12
During handling and installation, cable m 0.17
In final installation, cable m 0.12
Max. pulling force
Pulling-eye kN 0.625
Pulling-stocking kN 0.25
Resistance 20 °C Ω/km 7,41
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302347
Reka code 1146570

5G4

Electric number Size Packaging Voltage

5G4

Nominal diameter of complete cable mm 15
Nominal weight of cable kg/km 419
Conductor material Copper
Nominal cross-sectional area of conductor mm2 4
Nominal thickness of insulation mm 0,7
Number of wires 5
Min. bending radius
During handling and installation, cable mm 185
In final installation, cable mm 130
During handling and installation, cable cm 19
In final installation, cable cm 13
During handling and installation, cable m 0.18
In final installation, cable m 0.13
Max. pulling force
Pulling-eye kN 1
Pulling-stocking kN 0.4
Resistance 20 °C Ω/km 4,61
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302361
Reka code 1146571

5G6

Electric number Size Packaging Voltage

5G6

Nominal diameter of complete cable mm 18
Nominal weight of cable kg/km 570
Conductor material Copper
Nominal cross-sectional area of conductor mm2 6
Nominal thickness of insulation mm 0,7
Number of wires 5
Min. bending radius
During handling and installation, cable mm 213
In final installation, cable mm 149
During handling and installation, cable cm 21
In final installation, cable cm 15
During handling and installation, cable m 0.21
In final installation, cable m 0.15
Max. pulling force
Pulling-eye kN 1.5
Pulling-stocking kN 0.6
Resistance 20 °C Ω/km 3,08
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302385
Reka code 1146572

5G10

Electric number Size Packaging Voltage

5G10

Nominal diameter of complete cable mm 20
Nominal weight of cable kg/km 809
Conductor material Copper
Nominal cross-sectional area of conductor mm2 10
Nominal thickness of insulation mm 0,7
Number of wires 5
Min. bending radius
During handling and installation, cable mm 242
In final installation, cable mm 169
During handling and installation, cable cm 24
In final installation, cable cm 17
During handling and installation, cable m 0.24
In final installation, cable m 0.17
Max. pulling force
Pulling-eye kN 2.5
Pulling-stocking kN 1
Resistance 20 °C Ω/km 1,83
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302408
Reka code 1146573

5G16

Electric number Size Packaging Voltage

5G16

Nominal diameter of complete cable mm 23
Nominal weight of cable kg/km 1159
Conductor material Copper
Nominal cross-sectional area of conductor mm2 16
Nominal thickness of insulation mm 0,7
Number of wires 5
Min. bending radius
During handling and installation, cable mm 278
In final installation, cable mm 195
During handling and installation, cable cm 28
In final installation, cable cm 19
During handling and installation, cable m 0.28
In final installation, cable m 0.2
Max. pulling force
Pulling-eye kN 4
Pulling-stocking kN 1.6
Resistance 20 °C Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302422
Reka code 1146574

5G25

Electric number Size Packaging Voltage

5G25

Nominal diameter of complete cable mm 29
Nominal weight of cable kg/km 1855
Conductor material Copper
Nominal cross-sectional area of conductor mm2 25
Nominal thickness of insulation mm 0,9
Number of wires 5
Min. bending radius
During handling and installation, cable mm 350
In final installation, cable mm 245
During handling and installation, cable cm 35
In final installation, cable cm 24
During handling and installation, cable m 0.35
In final installation, cable m 0.24
Max. pulling force
Pulling-eye kN 6.25
Pulling-stocking kN 2.5
Resistance 20 °C Ω/km 0,727
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302446
Reka code 1146575

5G35

Electric number Size Packaging Voltage

5G35

Nominal diameter of complete cable mm 31
Nominal weight of cable kg/km 2326
Conductor material Copper
Nominal cross-sectional area of conductor mm2 35
Nominal thickness of insulation mm 0,9
Number of wires 5
Min. bending radius
During handling and installation, cable mm 369
In final installation, cable mm 258
During handling and installation, cable cm 37
In final installation, cable cm 26
During handling and installation, cable m 0.37
In final installation, cable m 0.26
Max. pulling force
Pulling-eye kN 8.75
Pulling-stocking kN 3.5
Resistance 20 °C Ω/km 0,524
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302460
Reka code 1146576

5G50

Electric number Size Packaging Voltage

5G50

Nominal diameter of complete cable mm 35
Nominal weight of cable kg/km 3143
Conductor material Copper
Nominal cross-sectional area of conductor mm2 50
Nominal thickness of insulation mm 1,0
Number of wires 5
Min. bending radius
During handling and installation, cable mm 422
In final installation, cable mm 295
During handling and installation, cable cm 42
In final installation, cable cm 30
During handling and installation, cable m 0.42
In final installation, cable m 0.29
Max. pulling force
Pulling-eye kN 12.5
Pulling-stocking kN 5
Resistance 20 °C Ω/km 0,387
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176302484
Reka code 1146577