AXLJ-F TT 18/30 (36) kV 1-core CAS


Medium-voltage cable for fixed installations outdoors. May be buried directly in soil, also by ploughing. Cable is longitudinally and radially watertight and therefore it is suitable where wet soil and / or fresh water permanently occurs. Installations must be in accordance with national regulations and rules of installations. The cable is halogen-free, but without fire protection. The cable is not CPR-classified.
Standards | HD 620 10 M, SS 424 14 16 |
---|---|
Conductor | Watertight, circular, stranded aluminium, EN/IEC 60228 class 2 |
Conductor screen | Semiconducting cross-linked polyethylene XLPE |
Insulation | Cross-linked polyethylene XLPE |
Insulation screen | Semiconducting cross-linked polyethylene XLPE |
Inner covering | Water swellable tape under and over screen |
Metal screen | Copper wires and aluminium foil (CAS). Polyethylene laminated aluminium foil acts as a part of the metallic screen and needs to be connected in cable joints and terminations |
Radial watertightness | Polyethylene laminated aluminium foil bonded to the sheath |
Oversheath | UV-protected PE-plastic PELLD |
Colour of the oversheath | Black |
1x500/35 CAS
Electric number
Size
Packaging
Voltage
1x500/35 CAS
Nominal diameter of complete cable mm
51
Nominal weight of cable kg/km
2862
Conductor material
Aluminium
Nominal diameter of conductor mm
25.7
Nominal cross-sectional area of conductor mm2
500
Nominal thickness of insulation mm
8
Nominal diameter over the insulation without insulation screen mm
41.3
Number of wires
1
Nominal size of metal screen mm2
35
Min. bending radius
During handling and installation, cable cm
77
In final installation, cable cm
54
During handling and installation, cable m
0.77
In final installation, cable m
0.54
Max. pulling force
Pulling-eye kN
15
Pulling-stocking kN
7.5
Resistance 20 °C Ω/km
0,0605
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,6
Minimum cable temperature during transport °C
-40
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176217672
Reka code