AXCMK-HF D / AXQJ D / IFSI-Al D Helppo


Aluminium power cable for fixed installations indoors and outdoors. May be buried directly in soil. The conductor insulation must be protected against UV-radiation. Installations must be in accordance with national regulations and rules of installations. The cable is halogen-free and flame-retardant according to CPR-class Dca-s2,d2,a2.
Standards | SFS 5546, SEK TS 424 14 18-1, HD 604 5 I & D, IEC 60502-1 |
---|---|
Reaction to fire | Dca-s2,d2,a2 |
CPR - DoP | 2025003_DOP.pdf |
Product Environmental Profile (PEP) | PEP NXNS-00560-V01.01-EN.pdf |
Conductor | 35-300 mm² sector shaped, stranded aluminium, EN/IEC 60228 class 2 |
Insulation | Cross-linked polyethylene XLPE |
Core Identification (all color combinations in the cable family) | Brown, black, grey Blue, brown, black, grey |
Inner covering | Plastic tape |
Metal screen | Copper wires and copper tape |
Oversheath | UV-protected polyolefin compound |
Colour of the oversheath | Black |
4x35/16
Electric number
Size
Packaging
Voltage
4x35/16
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
35
Nominal thickness of insulation mm
0.9
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
16
During handling and installation, cable cm
29
In final installation, phase conductor cm
11
In final installation, cable cm
20
During handling and installation, cable m
0.29
In final installation, cable m
0.2
Max. pulling force
Pulling-eye kN
2.1
Pulling-stocking kN
2.1
Resistance 20 °C Ω/km
0,868
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176310335
Reka code
1149336
4x50/16
Electric number
Size
Packaging
Voltage
4x50/16
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
50
Nominal thickness of insulation mm
1
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
19
During handling and installation, cable cm
34
In final installation, phase conductor cm
13
In final installation, cable cm
24
During handling and installation, cable m
0.34
In final installation, cable m
0.24
Max. pulling force
Pulling-eye kN
3
Pulling-stocking kN
3
Resistance 20 °C Ω/km
0,641
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,15
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176310359
Reka code
1149337
4x70/21
Electric number
Size
Packaging
Voltage
4x70/21
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
70
Nominal thickness of insulation mm
1.1
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
23
During handling and installation, cable cm
38
In final installation, phase conductor cm
16
In final installation, cable cm
27
During handling and installation, cable m
0.38
In final installation, cable m
0.27
Max. pulling force
Pulling-eye kN
4.2
Pulling-stocking kN
4.2
Resistance 20 °C Ω/km
0,443
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,868
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176310373
Reka code
1149338
4x95/29
Electric number
Size
Packaging
Voltage
4x95/29
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
95
Nominal thickness of insulation mm
1.1
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
26
During handling and installation, cable cm
43
In final installation, phase conductor cm
18
In final installation, cable cm
30
During handling and installation, cable m
0.43
In final installation, cable m
0.3
Max. pulling force
Pulling-eye kN
5.7
Pulling-stocking kN
5.7
Resistance 20 °C Ω/km
0,320
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,641
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176310397
Reka code
1149339
4x120/41
Electric number
Size
Packaging
Voltage
4x120/41
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
120
Nominal thickness of insulation mm
1.2
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
29
During handling and installation, cable cm
48
In final installation, phase conductor cm
20
In final installation, cable cm
34
During handling and installation, cable m
0.48
In final installation, cable m
0.34
Max. pulling force
Pulling-eye kN
7.2
Pulling-stocking kN
7.2
Resistance 20 °C Ω/km
0,253
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,443
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176310410
Reka code
1149340
4x150/41
Electric number
Size
Packaging
Voltage
4x150/41
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
150
Nominal thickness of insulation mm
1.4
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
32
During handling and installation, cable cm
53
In final installation, phase conductor cm
23
In final installation, cable cm
37
During handling and installation, cable m
0.53
In final installation, cable m
0.37
Max. pulling force
Pulling-eye kN
9
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,206
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,443
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176310434
Reka code
1149341
4x185/57
Electric number
Size
Packaging
Voltage
4x185/57
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
185
Nominal thickness of insulation mm
1.6
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
37
During handling and installation, cable cm
59
In final installation, phase conductor cm
26
In final installation, cable cm
41
During handling and installation, cable m
0.59
In final installation, cable m
0.41
Max. pulling force
Pulling-eye kN
11.1
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,164
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,320
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176310458
Reka code
1149342
4x240/72
Electric number
Size
Packaging
Voltage
4x240/72
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
240
Nominal thickness of insulation mm
1.7
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
43
During handling and installation, cable cm
67
In final installation, phase conductor cm
30
In final installation, cable cm
47
During handling and installation, cable m
0.67
In final installation, cable m
0.47
Max. pulling force
Pulling-eye kN
14.4
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,125
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,253
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176310472
Reka code
1149343
4x300/88
Electric number
Size
Packaging
Voltage
4x300/88
Conductor material
Aluminium
Nominal cross-sectional area of conductor mm2
300
Nominal thickness of insulation mm
1.8
Number of wires
4
Min. bending radius
During handling and installation, phase conductor cm
46
During handling and installation, cable cm
72
In final installation, phase conductor cm
32
In final installation, cable cm
50
During handling and installation, cable m
0.72
In final installation, cable m
0.5
Max. pulling force
Pulling-eye kN
18
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,100
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,206
Minimum cable temperature during transport °C
-25
Minimum cable temperature during handling and installation °C
-15
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176310496
Reka code