AXCMK-HF D / AXQJ D / IFSI-Al D Helppo

Download product group datasheet

Aluminium power cable for fixed installations indoors and outdoors. May be buried directly in soil. The conductor insulation must be protected against UV-radiation. Installations must be in accordance with national regulations and rules of installations. The cable is halogen-free and flame-retardant according to CPR-class Dca-s2,d2,a2.

Standards SFS 5546, SEK TS 424 14 18-1, HD 604 5 I & D, IEC 60502-1
Reaction to fire Dca-s2,d2,a2
CPR - DoP 2025003_DOP.pdf
Product Environmental Profile (PEP) PEP NXNS-00560-V01.01-EN.pdf
Conductor 35-300 mm² sector shaped, stranded aluminium, EN/IEC 60228 class 2
Insulation Cross-linked polyethylene XLPE
Core Identification (all color combinations in the cable family) Brown, black, grey
Blue, brown, black, grey
Inner covering Plastic tape
Metal screen Copper wires and copper tape
Oversheath UV-protected polyolefin compound
Colour of the oversheath Black

4x35/16

Electric number Size Packaging Voltage

4x35/16

Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 35
Nominal thickness of insulation mm 0.9
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 16
During handling and installation, cable cm 29
In final installation, phase conductor cm 11
In final installation, cable cm 20
During handling and installation, cable m 0.29
In final installation, cable m 0.2
Max. pulling force
Pulling-eye kN 2.1
Pulling-stocking kN 2.1
Resistance 20 °C Ω/km 0,868
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176310335
Reka code 1149336

4x50/16

Electric number Size Packaging Voltage

4x50/16

Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 50
Nominal thickness of insulation mm 1
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 19
During handling and installation, cable cm 34
In final installation, phase conductor cm 13
In final installation, cable cm 24
During handling and installation, cable m 0.34
In final installation, cable m 0.24
Max. pulling force
Pulling-eye kN 3
Pulling-stocking kN 3
Resistance 20 °C Ω/km 0,641
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176310359
Reka code 1149337

4x70/21

Electric number Size Packaging Voltage

4x70/21

Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 70
Nominal thickness of insulation mm 1.1
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 23
During handling and installation, cable cm 38
In final installation, phase conductor cm 16
In final installation, cable cm 27
During handling and installation, cable m 0.38
In final installation, cable m 0.27
Max. pulling force
Pulling-eye kN 4.2
Pulling-stocking kN 4.2
Resistance 20 °C Ω/km 0,443
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,868
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176310373
Reka code 1149338

4x95/29

Electric number Size Packaging Voltage

4x95/29

Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 95
Nominal thickness of insulation mm 1.1
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 26
During handling and installation, cable cm 43
In final installation, phase conductor cm 18
In final installation, cable cm 30
During handling and installation, cable m 0.43
In final installation, cable m 0.3
Max. pulling force
Pulling-eye kN 5.7
Pulling-stocking kN 5.7
Resistance 20 °C Ω/km 0,320
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,641
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176310397
Reka code 1149339

4x120/41

Electric number Size Packaging Voltage

4x120/41

Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 120
Nominal thickness of insulation mm 1.2
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 29
During handling and installation, cable cm 48
In final installation, phase conductor cm 20
In final installation, cable cm 34
During handling and installation, cable m 0.48
In final installation, cable m 0.34
Max. pulling force
Pulling-eye kN 7.2
Pulling-stocking kN 7.2
Resistance 20 °C Ω/km 0,253
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,443
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176310410
Reka code 1149340

4x150/41

Electric number Size Packaging Voltage

4x150/41

Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 150
Nominal thickness of insulation mm 1.4
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 32
During handling and installation, cable cm 53
In final installation, phase conductor cm 23
In final installation, cable cm 37
During handling and installation, cable m 0.53
In final installation, cable m 0.37
Max. pulling force
Pulling-eye kN 9
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,206
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,443
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176310434
Reka code 1149341

4x185/57

Electric number Size Packaging Voltage

4x185/57

Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 185
Nominal thickness of insulation mm 1.6
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 37
During handling and installation, cable cm 59
In final installation, phase conductor cm 26
In final installation, cable cm 41
During handling and installation, cable m 0.59
In final installation, cable m 0.41
Max. pulling force
Pulling-eye kN 11.1
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,164
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,320
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176310458
Reka code 1149342

4x240/72

Electric number Size Packaging Voltage

4x240/72

Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 240
Nominal thickness of insulation mm 1.7
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 43
During handling and installation, cable cm 67
In final installation, phase conductor cm 30
In final installation, cable cm 47
During handling and installation, cable m 0.67
In final installation, cable m 0.47
Max. pulling force
Pulling-eye kN 14.4
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,125
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,253
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176310472
Reka code 1149343

4x300/88

Electric number Size Packaging Voltage

4x300/88

Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 300
Nominal thickness of insulation mm 1.8
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 46
During handling and installation, cable cm 72
In final installation, phase conductor cm 32
In final installation, cable cm 50
During handling and installation, cable m 0.72
In final installation, cable m 0.5
Max. pulling force
Pulling-eye kN 18
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,100
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,206
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176310496
Reka code 1149344