AHXAMK-WP 19/33 (36) kV 3-core

Download product group datasheet

DryRex Nordic Wind cables are designed especially to meet the requirements of 36 kV wind farms. May be buried directly in soil, also by ploughing. Cable is longitudinally and radially watertight and therefore it is suitable where wet soil and / or fresh water permanently occurs. Installations must be in accordance with national regulations and rules of installations. The cable is halogen-free, but without fire protection. The cable is not CPR-classified.

Standards HD 620 10 F, SFS 5636
Conductor Watertight, circular, stranded aluminium EN/IEC 60228 class 2
Conductor screen Semiconducting cross-linked polyethylene XLPE
Insulation Cross-linked polyethylene XLPE
Insulation screen Semiconducting cross-linked polyethylene XLPE
Core Identification (all color combinations in the cable family) White phase numbering: L1, L2, L3
Cable lay up Three sheathed cores are laid up together
Inner covering Semiconducting waterswellable tape against longitudinal water penetration
Metal screen Polyethylene laminated aluminium foil, which acts also as a radial water barrier
Oversheath PE-plastic PELLD
Colour of the oversheath Black

3x95

Electric number Size Packaging Voltage

3x95

Nominal diameter of complete cable mm 76
Nominal weight of cable kg/km 3332
Conductor material Aluminium
Nominal diameter of conductor mm 11.1
Nominal cross-sectional area of conductor mm2 95
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 26.7
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 53
During handling and installation, cable cm 91
In final installation, phase conductor cm 37
In final installation, cable cm 64
During handling and installation, phase conductor m 0.53
During handling and installation, cable m 0.91
In final installation, phase conductor m 0.37
In final installation, cable m 0.64
Max. pulling force
Pulling-eye kN 8.6
Pulling-stocking kN 4.3
Resistance 20 °C Ω/km 0,320
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176306116
Reka code 1181888

3x120

Electric number Size Packaging Voltage

3x120

Nominal diameter of complete cable mm 79
Nominal weight of cable kg/km 3732
Conductor material Aluminium
Nominal diameter of conductor mm 12.6
Nominal cross-sectional area of conductor mm2 120
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 28.2
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 56
During handling and installation, cable cm 95
In final installation, phase conductor cm 39
In final installation, cable cm 66
During handling and installation, phase conductor m 0.56
During handling and installation, cable m 0.95
In final installation, phase conductor m 0.39
In final installation, cable m 0.67
Max. pulling force
Pulling-eye kN 10.8
Pulling-stocking kN 5.4
Resistance 20 °C Ω/km 0,253
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176306123
Reka code 1181889

3x150

Electric number Size Packaging Voltage

3x150

Nominal diameter of complete cable mm 82
Nominal weight of cable kg/km 4108
Conductor material Aluminium
Nominal diameter of conductor mm 13.9
Nominal cross-sectional area of conductor mm2 150
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 29.5
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 57
During handling and installation, cable cm 99
In final installation, phase conductor cm 40
In final installation, cable cm 69
During handling and installation, phase conductor m 0.57
During handling and installation, cable m 0.99
In final installation, phase conductor m 0.4
In final installation, cable m 0.69
Max. pulling force
Pulling-eye kN 13.5
Pulling-stocking kN 6.8
Resistance 20 °C Ω/km 0,206
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176306260
Reka code 1181890

3x185

Electric number Size Packaging Voltage

3x185

Nominal diameter of complete cable mm 86
Nominal weight of cable kg/km 4625
Conductor material Aluminium
Nominal diameter of conductor mm 15.6
Nominal cross-sectional area of conductor mm2 185
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 31.2
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 60
During handling and installation, cable cm 103
In final installation, phase conductor cm 42
In final installation, cable cm 72
During handling and installation, phase conductor m 0.6
During handling and installation, cable m 1.03
In final installation, phase conductor m 0.42
In final installation, cable m 0.72
Max. pulling force
Pulling-eye kN 16.7
Pulling-stocking kN 8.3
Resistance 20 °C Ω/km 0,164
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176306130
Reka code 1181891

3x240

Electric number Size Packaging Voltage

3x240

Nominal diameter of complete cable mm 92
Nominal weight of cable kg/km 5391
Conductor material Aluminium
Nominal diameter of conductor mm 17.8
Nominal cross-sectional area of conductor mm2 240
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 33.6
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 65
During handling and installation, cable cm 110
In final installation, phase conductor cm 45
In final installation, cable cm 77
During handling and installation, phase conductor m 0.65
During handling and installation, cable m 1.1
In final installation, phase conductor m 0.45
In final installation, cable m 0.77
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,125
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176306147
Reka code 1181892

3x300

Electric number Size Packaging Voltage

3x300

Nominal diameter of complete cable mm 96
Nominal weight of cable kg/km 6166
Conductor material Aluminium
Nominal diameter of conductor mm 19.8
Nominal cross-sectional area of conductor mm2 300
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 35.4
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 68
During handling and installation, cable cm 115
In final installation, phase conductor cm 47
In final installation, cable cm 80
During handling and installation, phase conductor m 0.68
During handling and installation, cable m 1.15
In final installation, phase conductor m 0.47
In final installation, cable m 0.81
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,100
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176306154
Reka code 1181893