KLMA-HF C

Download product group datasheet

Control cable for fixed installations indoors and outdoors. Not to be laid in soil nor directly in cast concrete. Can also be used in medical facilities where higher fire class is required. The conductor insulation must be protected against UV-radiation. Installations must be in accordance with national regulations and rules of installations. The cable is halogen-free and flame-retardant according to CPR-class Cca-s1,d1,a1.

Standards SFS 2755
Reaction to fire Cca-s1,d1,a1
CPR - DoP 2020007_DOP.pdf
Conductor Circular solid copper, EN/IEC 60228 class 1
Insulation Halogen free polyethylene
Core Identification (all color combinations in the cable family) Blue, yellow
Blue, yellow, white, red
Pair lay up Cores are twisted in pairs
Cable lay up Insulated cores twisted in pairs.
Inner covering Plastic tape
Overall shield Aluminium tape and earthing conductor
Oversheath UV-protected halogen-free compound
Colour of the oversheath Grey

2x0,8+0,8

Electric number Size Packaging Voltage

2x0,8+0,8

Nominal diameter of complete cable mm 6
Nominal weight of cable kg/km 36
Conductor material Copper
Nominal diameter of conductor mm 0.8
Nominal cross-sectional area of conductor mm2 0.5
Nominal thickness of insulation mm 0.4
Number of wires 2
Min. bending radius
During handling and installation, cable mm 83
In final installation, cable mm 55
During handling and installation, cable cm 8
In final installation, cable cm 6
Max. pulling force
Pulling-eye kN 0.05
Resistance 20 °C Ω/km 36,0
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -10
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6438176305720
Reka code 1147416

4x0,8+0,8

Electric number Size Packaging Voltage

4x0,8+0,8

Nominal diameter of complete cable mm 6.5
Nominal weight of cable kg/km 55
Conductor material Copper
Nominal diameter of conductor mm 0.8
Nominal cross-sectional area of conductor mm2 0.5
Nominal thickness of insulation mm 0.4
Number of wires 4
Min. bending radius
During handling and installation, cable mm 96
In final installation, cable mm 64
During handling and installation, cable cm 10
In final installation, cable cm 6
Max. pulling force
Pulling-eye kN 0.1
Resistance 20 °C Ω/km 36,0
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -10
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 160
EAN code 6438176305737
Reka code 1147417