EQQ LiteRex

For Fixed installations indoors and outdoors. Not to be laid in soil nor directly in cast concrete. UV-protected outer sheath and core insulation.

Standards SS 424 02 19-5:2014
Reaction to fire Dca-s2,d2,a2
CPR - DoP 2021017_DOP.pdf
Conductor Circular solid copper, EN/IEC 60228 class 1
Insulation Halogen free UV-resistant polyethylene
Core Identification (all color combinations in the cable family) Blue, brown
Yellow-green, blue, brown
Yellow-green, blue, brown, black
Yellow-green, blue, brown, black, grey
Oversheath Halogen free UV-resistant polyolefin compound
Colour of the oversheath White

2x1,5 N

Electric number Size Packing (m) Voltage

2x1,5 N

Nominal diameter of complete cable (mm) 8
Nominal weight of cable (kg/km) 73
Conductor material Copper
Nominal diameter of conductor (mm) 1.36
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 2
Bending radius
During handling and installation, cable (cm) 80
In final installation, cable (cm) 24
During handling and installation, cable (cm) 8
In final installation, cable (cm) 2
Pulling force
Pulling-eye (kN) 0.15
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.17
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176224175
Reka code 1254728
Nominal diameter of complete cable (mm) 8
Nominal weight of cable (kg/km) 73
Conductor material Copper
Nominal diameter of conductor (mm) 1.36
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 2
Bending radius
During handling and installation, cable (cm) 80
In final installation, cable (cm) 24
During handling and installation, cable (cm) 8
In final installation, cable (cm) 2
Pulling force
Pulling-eye (kN) 0.15
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.17
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176224168
Reka code 1254728
Nominal diameter of complete cable (mm) 8
Nominal weight of cable (kg/km) 73
Conductor material Copper
Nominal diameter of conductor (mm) 1.36
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 2
Bending radius
During handling and installation, cable (cm) 80
In final installation, cable (cm) 24
During handling and installation, cable (cm) 8
In final installation, cable (cm) 2
Pulling force
Pulling-eye (kN) 0.15
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.17
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176224182
Reka code 1254728
Nominal diameter of complete cable (mm) 8
Nominal weight of cable (kg/km) 73
Conductor material Copper
Nominal diameter of conductor (mm) 1.36
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 2
Bending radius
During handling and installation, cable (cm) 80
In final installation, cable (cm) 24
During handling and installation, cable (cm) 8
In final installation, cable (cm) 2
Pulling force
Pulling-eye (kN) 0.15
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.17
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176224199
Reka code 1254728

3G1,5

Electric number Size Packing (m) Voltage

3G1,5

Nominal diameter of complete cable (mm) 8
Nominal weight of cable (kg/km) 93
Conductor material Copper
Nominal diameter of conductor (mm) 1.36
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 3
Bending radius
During handling and installation, cable (cm) 80
In final installation, cable (cm) 24
During handling and installation, cable (cm) 8
In final installation, cable (cm) 2
Pulling force
Pulling-eye (kN) 0.23
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.17
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176223956
Reka code 1254730
Nominal diameter of complete cable (mm) 8
Nominal weight of cable (kg/km) 93
Conductor material Copper
Nominal diameter of conductor (mm) 1.36
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 3
Bending radius
During handling and installation, cable (cm) 80
In final installation, cable (cm) 24
During handling and installation, cable (cm) 8
In final installation, cable (cm) 2
Pulling force
Pulling-eye (kN) 0.23
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.17
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176304457
Reka code 1254730
Nominal diameter of complete cable (mm) 8
Nominal weight of cable (kg/km) 93
Conductor material Copper
Nominal diameter of conductor (mm) 1.36
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 3
Bending radius
During handling and installation, cable (cm) 80
In final installation, cable (cm) 24
During handling and installation, cable (cm) 8
In final installation, cable (cm) 2
Pulling force
Pulling-eye (kN) 0.23
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.17
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176223932
Reka code 1254730
Nominal diameter of complete cable (mm) 8
Nominal weight of cable (kg/km) 93
Conductor material Copper
Nominal diameter of conductor (mm) 1.36
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 3
Bending radius
During handling and installation, cable (cm) 80
In final installation, cable (cm) 24
During handling and installation, cable (cm) 8
In final installation, cable (cm) 2
Pulling force
Pulling-eye (kN) 0.23
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.17
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176223925
Reka code 1254730
Nominal diameter of complete cable (mm) 8
Nominal weight of cable (kg/km) 93
Conductor material Copper
Nominal diameter of conductor (mm) 1.36
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 3
Bending radius
During handling and installation, cable (cm) 80
In final installation, cable (cm) 24
During handling and installation, cable (cm) 8
In final installation, cable (cm) 2
Pulling force
Pulling-eye (kN) 0.23
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.17
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176223949
Reka code 1254730

4G1,5

Electric number Size Packing (m) Voltage

4G1,5

Nominal diameter of complete cable (mm) 9
Nominal weight of cable (kg/km) 113
Conductor material Copper
Nominal diameter of conductor (mm) 1.36
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 4
Bending radius
During handling and installation, cable (cm) 90
In final installation, cable (cm) 27
During handling and installation, cable (cm) 9
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.3
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.17
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176223994
Reka code 1254731
Nominal diameter of complete cable (mm) 9
Nominal weight of cable (kg/km) 113
Conductor material Copper
Nominal diameter of conductor (mm) 1.36
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 4
Bending radius
During handling and installation, cable (cm) 90
In final installation, cable (cm) 27
During handling and installation, cable (cm) 9
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.3
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.17
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176223963
Reka code 1254731
Nominal diameter of complete cable (mm) 9
Nominal weight of cable (kg/km) 113
Conductor material Copper
Nominal diameter of conductor (mm) 1.36
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 4
Bending radius
During handling and installation, cable (cm) 90
In final installation, cable (cm) 27
During handling and installation, cable (cm) 9
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.3
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.17
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176304082
Reka code 1254731
Nominal diameter of complete cable (mm) 9
Nominal weight of cable (kg/km) 113
Conductor material Copper
Nominal diameter of conductor (mm) 1.36
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 4
Bending radius
During handling and installation, cable (cm) 90
In final installation, cable (cm) 27
During handling and installation, cable (cm) 9
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.3
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.17
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176223970
Reka code 1254731
Nominal diameter of complete cable (mm) 9
Nominal weight of cable (kg/km) 113
Conductor material Copper
Nominal diameter of conductor (mm) 1.36
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 4
Bending radius
During handling and installation, cable (cm) 90
In final installation, cable (cm) 27
During handling and installation, cable (cm) 9
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.3
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.17
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176223987
Reka code 1254731

5G1,5

Electric number Size Packing (m) Voltage

5G1,5

Nominal diameter of complete cable (mm) 9
Nominal weight of cable (kg/km) 135
Conductor material Copper
Nominal diameter of conductor (mm) 1.36
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 5
Bending radius
During handling and installation, cable (cm) 90
In final installation, cable (cm) 27
During handling and installation, cable (cm) 9
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.38
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.17
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176224021
Reka code 1254732
Nominal diameter of complete cable (mm) 9
Nominal weight of cable (kg/km) 135
Conductor material Copper
Nominal diameter of conductor (mm) 1.36
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 5
Bending radius
During handling and installation, cable (cm) 90
In final installation, cable (cm) 27
During handling and installation, cable (cm) 9
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.38
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.17
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176304471
Reka code 1254732
Nominal diameter of complete cable (mm) 9
Nominal weight of cable (kg/km) 135
Conductor material Copper
Nominal diameter of conductor (mm) 1.36
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 5
Bending radius
During handling and installation, cable (cm) 90
In final installation, cable (cm) 27
During handling and installation, cable (cm) 9
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.38
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.17
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176224014
Reka code 1254732
Nominal diameter of complete cable (mm) 9
Nominal weight of cable (kg/km) 135
Conductor material Copper
Nominal diameter of conductor (mm) 1.36
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 5
Bending radius
During handling and installation, cable (cm) 90
In final installation, cable (cm) 27
During handling and installation, cable (cm) 9
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.38
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.17
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176304099
Reka code 1254732
Nominal diameter of complete cable (mm) 9
Nominal weight of cable (kg/km) 135
Conductor material Copper
Nominal diameter of conductor (mm) 1.36
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 5
Bending radius
During handling and installation, cable (cm) 90
In final installation, cable (cm) 27
During handling and installation, cable (cm) 9
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.38
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.17
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176224007
Reka code 1254732
Nominal diameter of complete cable (mm) 9
Nominal weight of cable (kg/km) 135
Conductor material Copper
Nominal diameter of conductor (mm) 1.36
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 5
Bending radius
During handling and installation, cable (cm) 90
In final installation, cable (cm) 27
During handling and installation, cable (cm) 9
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.38
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.17
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176224151
Reka code 1254732

2x2,5 N

Electric number Size Packing (m) Voltage

2x2,5 N

Nominal diameter of complete cable (mm) 9
Nominal weight of cable (kg/km) 100
Conductor material Copper
Nominal diameter of conductor (mm) 1.74
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 2
Bending radius
During handling and installation, cable (cm) 90
In final installation, cable (cm) 27
During handling and installation, cable (cm) 9
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.25
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 7.41
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.29
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176224236
Reka code 1254729
Nominal diameter of complete cable (mm) 9
Nominal weight of cable (kg/km) 100
Conductor material Copper
Nominal diameter of conductor (mm) 1.74
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 2
Bending radius
During handling and installation, cable (cm) 90
In final installation, cable (cm) 27
During handling and installation, cable (cm) 9
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.25
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 7.41
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.29
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176224212
Reka code 1254729
Nominal diameter of complete cable (mm) 9
Nominal weight of cable (kg/km) 100
Conductor material Copper
Nominal diameter of conductor (mm) 1.74
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 2
Bending radius
During handling and installation, cable (cm) 90
In final installation, cable (cm) 27
During handling and installation, cable (cm) 9
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.25
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 7.41
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.29
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176304112
Reka code 1254729
Nominal diameter of complete cable (mm) 9
Nominal weight of cable (kg/km) 100
Conductor material Copper
Nominal diameter of conductor (mm) 1.74
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 2
Bending radius
During handling and installation, cable (cm) 90
In final installation, cable (cm) 27
During handling and installation, cable (cm) 9
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.25
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 7.41
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.29
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176224205
Reka code 1254729
Nominal diameter of complete cable (mm) 9
Nominal weight of cable (kg/km) 100
Conductor material Copper
Nominal diameter of conductor (mm) 1.74
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 2
Bending radius
During handling and installation, cable (cm) 90
In final installation, cable (cm) 27
During handling and installation, cable (cm) 9
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.25
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 7.41
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.29
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176224229
Reka code 1254729

3G2,5

Electric number Size Packing (m) Voltage

3G2,5

Nominal diameter of complete cable (mm) 9
Nominal weight of cable (kg/km) 130
Conductor material Copper
Nominal diameter of conductor (mm) 1.74
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 3
Bending radius
During handling and installation, cable (cm) 90
In final installation, cable (cm) 27
During handling and installation, cable (cm) 9
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.38
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 7.41
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.29
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176224052
Reka code 1254733
Nominal diameter of complete cable (mm) 9
Nominal weight of cable (kg/km) 130
Conductor material Copper
Nominal diameter of conductor (mm) 1.74
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 3
Bending radius
During handling and installation, cable (cm) 90
In final installation, cable (cm) 27
During handling and installation, cable (cm) 9
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.38
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 7.41
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.29
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176304495
Reka code 1254733
Nominal diameter of complete cable (mm) 9
Nominal weight of cable (kg/km) 130
Conductor material Copper
Nominal diameter of conductor (mm) 1.74
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 3
Bending radius
During handling and installation, cable (cm) 90
In final installation, cable (cm) 27
During handling and installation, cable (cm) 9
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.38
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 7.41
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.29
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176224120
Reka code 1254733
Nominal diameter of complete cable (mm) 9
Nominal weight of cable (kg/km) 130
Conductor material Copper
Nominal diameter of conductor (mm) 1.74
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 3
Bending radius
During handling and installation, cable (cm) 90
In final installation, cable (cm) 27
During handling and installation, cable (cm) 9
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.38
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 7.41
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.29
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176224038
Reka code 1254733
Nominal diameter of complete cable (mm) 9
Nominal weight of cable (kg/km) 130
Conductor material Copper
Nominal diameter of conductor (mm) 1.74
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 3
Bending radius
During handling and installation, cable (cm) 90
In final installation, cable (cm) 27
During handling and installation, cable (cm) 9
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.38
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 7.41
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.29
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176224045
Reka code 1254733

4G2,5

Electric number Size Packing (m) Voltage

4G2,5

Nominal diameter of complete cable (mm) 10
Nominal weight of cable (kg/km) 161
Conductor material Copper
Nominal diameter of conductor (mm) 1.74
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 4
Bending radius
During handling and installation, cable (cm) 100
In final installation, cable (cm) 30
During handling and installation, cable (cm) 10
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.5
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 7.41
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.29
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176224137
Reka code 1254734
Nominal diameter of complete cable (mm) 10
Nominal weight of cable (kg/km) 161
Conductor material Copper
Nominal diameter of conductor (mm) 1.74
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 4
Bending radius
During handling and installation, cable (cm) 100
In final installation, cable (cm) 30
During handling and installation, cable (cm) 10
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.5
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 7.41
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.29
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176224113
Reka code 1254734
Nominal diameter of complete cable (mm) 10
Nominal weight of cable (kg/km) 161
Conductor material Copper
Nominal diameter of conductor (mm) 1.74
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 4
Bending radius
During handling and installation, cable (cm) 100
In final installation, cable (cm) 30
During handling and installation, cable (cm) 10
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.5
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 7.41
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.29
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176224090
Reka code 1254734
Nominal diameter of complete cable (mm) 10
Nominal weight of cable (kg/km) 161
Conductor material Copper
Nominal diameter of conductor (mm) 1.74
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 4
Bending radius
During handling and installation, cable (cm) 100
In final installation, cable (cm) 30
During handling and installation, cable (cm) 10
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.5
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 7.41
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.29
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176224106
Reka code 1254734

5G2,5

Electric number Size Packing (m) Voltage

5G2,5

Nominal diameter of complete cable (mm) 11
Nominal weight of cable (kg/km) 194
Conductor material Copper
Nominal diameter of conductor (mm) 1.74
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 5
Bending radius
During handling and installation, cable (cm) 110
In final installation, cable (cm) 33
During handling and installation, cable (cm) 11
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.63
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 7.41
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.29
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176224144
Reka code 1254735
Nominal diameter of complete cable (mm) 11
Nominal weight of cable (kg/km) 194
Conductor material Copper
Nominal diameter of conductor (mm) 1.74
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 5
Bending radius
During handling and installation, cable (cm) 110
In final installation, cable (cm) 33
During handling and installation, cable (cm) 11
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.63
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 7.41
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.29
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176304518
Reka code 1254735
Nominal diameter of complete cable (mm) 11
Nominal weight of cable (kg/km) 194
Conductor material Copper
Nominal diameter of conductor (mm) 1.74
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 5
Bending radius
During handling and installation, cable (cm) 110
In final installation, cable (cm) 33
During handling and installation, cable (cm) 11
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.63
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 7.41
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.29
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176224083
Reka code 1254735
Nominal diameter of complete cable (mm) 11
Nominal weight of cable (kg/km) 194
Conductor material Copper
Nominal diameter of conductor (mm) 1.74
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 5
Bending radius
During handling and installation, cable (cm) 110
In final installation, cable (cm) 33
During handling and installation, cable (cm) 11
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.63
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 7.41
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.29
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176224069
Reka code 1254735
Nominal diameter of complete cable (mm) 11
Nominal weight of cable (kg/km) 194
Conductor material Copper
Nominal diameter of conductor (mm) 1.74
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 5
Bending radius
During handling and installation, cable (cm) 110
In final installation, cable (cm) 33
During handling and installation, cable (cm) 11
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.63
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 7.41
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.29
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176304129
Reka code 1254735
Nominal diameter of complete cable (mm) 11
Nominal weight of cable (kg/km) 194
Conductor material Copper
Nominal diameter of conductor (mm) 1.74
Nominal cross-sectional area of conductor (mm2) 0
Number of wires 5
Bending radius
During handling and installation, cable (cm) 110
In final installation, cable (cm) 33
During handling and installation, cable (cm) 11
In final installation, cable (cm) 3
Pulling force
Pulling-eye (kN) 0.63
Pulling-stocking (kN) 0
Resistance 20 °C (ohm/km) 7.41
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Phase (initial temperature 70 °C, final temperature 160 °C) 0.29
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6438176224076
Reka code 1254735