AEMCMK-HF / AXQJ-EMC / IFSI-EMC-Al

Download product group datasheet

Aluminium power cable for fixed installations indoors and outdoors. May be buried directly in soil. EMC shielded cable gives an excellent protection against electromagnetic disturbancies. The conductor insulation must be protected against UV-radiation. Installations must be in accordance with national regulations and rules of installations. The cable is halogen-free and flame-retardant according to CPR-class Dca-s2,d2,a2.

Standards SFS 5546, SS 424 14 18, HD 604 5 I & D, IEC 60502-1
Reaction to fire Dca-s2,d2,a2
CPR - DoP 2021005_DOP.pdf
2021006_DOP.pdf
Conductor 16-25 mm² circular stranded aluminium, EN/IEC 60228 class 2
35-300 mm² sector shaped stranded aluminium, EN/IEC 60228 class 2
Insulation Cross-linked polyethylene XLPE
Core Identification (all color combinations in the cable family) Brown, black, grey
Blue, brown, black, grey
Inner covering Plastic tape
Metal screen EMC-copper foil and copper wires
Oversheath UV-protected polyolefin compound
Colour of the oversheath Black

3x16/10

Electric number Size Packaging Voltage

3x16/10

Nominal diameter of complete cable mm 21
Nominal weight of cable kg/km 613
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 16
Nominal thickness of insulation mm 0.7
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 10
During handling and installation, cable cm 25
In final installation, phase conductor cm 7
In final installation, cable cm 17
During handling and installation, cable m 0.25
In final installation, cable m 0.17
Max. pulling force
Pulling-eye kN 0.7
Pulling-stocking kN 0.7
Resistance 20 °C Ω/km 1,91
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,83
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176225653
Reka code 1149200

3x120/41

Electric number Size Packaging Voltage

3x120/41

Nominal diameter of complete cable mm 36
Nominal weight of cable kg/km 1977
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 120
Nominal thickness of insulation mm 1.2
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 31
During handling and installation, cable cm 43
In final installation, phase conductor cm 22
In final installation, cable cm 30
During handling and installation, cable m 0.43
In final installation, cable m 0.3
Max. pulling force
Pulling-eye kN 5.4
Pulling-stocking kN 5.4
Resistance 20 °C Ω/km 0,253
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,443
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176225776
Reka code 1149206

3x185/57

Electric number Size Packaging Voltage

3x185/57

Nominal diameter of complete cable mm 44
Nominal weight of cable kg/km 2882
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 185
Nominal thickness of insulation mm 1.6
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 38
During handling and installation, cable cm 53
In final installation, phase conductor cm 27
In final installation, cable cm 37
During handling and installation, cable m 0.53
In final installation, cable m 0.37
Max. pulling force
Pulling-eye kN 8.3
Pulling-stocking kN 8.3
Resistance 20 °C Ω/km 0,164
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,320
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176225813
Reka code 1149208

3x240/72

Electric number Size Packaging Voltage

3x240/72

Nominal diameter of complete cable mm 48
Nominal weight of cable kg/km 3660
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 240
Nominal thickness of insulation mm 1.7
Number of wires 3
Min. bending radius
During handling and installation, phase conductor cm 43
During handling and installation, cable cm 58
In final installation, phase conductor cm 30
In final installation, cable cm 40
During handling and installation, cable m 0.58
In final installation, cable m 0.4
Max. pulling force
Pulling-eye kN 10.8
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,125
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,253
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176225837
Reka code 1149209

4x16/10

Electric number Size Packaging Voltage

4x16/10

Nominal diameter of complete cable mm 22
Nominal weight of cable kg/km 709
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 16
Nominal thickness of insulation mm 0.7
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 10
During handling and installation, cable cm 27
In final installation, phase conductor cm 7
In final installation, cable cm 19
During handling and installation, cable m 0.27
In final installation, cable m 0.19
Max. pulling force
Pulling-eye kN 1
Pulling-stocking kN 1
Resistance 20 °C Ω/km 1,91
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,83
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176225875
Reka code 1149214

4x25/16

Electric number Size Packaging Voltage

4x25/16

Nominal diameter of complete cable mm 26
Nominal weight of cable kg/km 1003
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 25
Nominal thickness of insulation mm 0.9
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 9
During handling and installation, cable cm 31
In final installation, phase conductor cm 6
In final installation, cable cm 22
During handling and installation, cable m 0.31
In final installation, cable m 0.22
Max. pulling force
Pulling-eye kN 1.5
Pulling-stocking kN 1.5
Resistance 20 °C Ω/km 1,20
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176225899
Reka code 1149215

4x35/16

Electric number Size Packaging Voltage

4x35/16

Nominal diameter of complete cable mm 24
Nominal weight of cable kg/km 859
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 35
Nominal thickness of insulation mm 0.9
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 16
During handling and installation, cable cm 29
In final installation, phase conductor cm 11
In final installation, cable cm 20
During handling and installation, cable m 0.29
In final installation, cable m 0.2
Max. pulling force
Pulling-eye kN 2.1
Pulling-stocking kN 2.1
Resistance 20 °C Ω/km 0,868
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1,15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176225912
Reka code 1149216

4x70/21

Electric number Size Packaging Voltage

4x70/21

Nominal diameter of complete cable mm 31
Nominal weight of cable kg/km 1464
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 70
Nominal thickness of insulation mm 1.1
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 23
During handling and installation, cable cm 38
In final installation, phase conductor cm 16
In final installation, cable cm 26
During handling and installation, cable m 0.38
In final installation, cable m 0.26
Max. pulling force
Pulling-eye kN 4.2
Pulling-stocking kN 4.2
Resistance 20 °C Ω/km 0,443
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,868
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176225950
Reka code 1149218

4x120/41

Electric number Size Packaging Voltage

4x120/41

Nominal diameter of complete cable mm 40
Nominal weight of cable kg/km 2425
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 120
Nominal thickness of insulation mm 1.2
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 29
During handling and installation, cable cm 49
In final installation, phase conductor cm 20
In final installation, cable cm 34
During handling and installation, cable m 0.49
In final installation, cable m 0.34
Max. pulling force
Pulling-eye kN 7.2
Pulling-stocking kN 7.2
Resistance 20 °C Ω/km 0,253
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,443
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176225998
Reka code 1149220

4x150/41

Electric number Size Packaging Voltage

4x150/41

Nominal diameter of complete cable mm 45
Nominal weight of cable kg/km 2875
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 150
Nominal thickness of insulation mm 1.4
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 32
During handling and installation, cable cm 54
In final installation, phase conductor cm 23
In final installation, cable cm 38
During handling and installation, cable m 0.54
In final installation, cable m 0.38
Max. pulling force
Pulling-eye kN 9
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,206
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,443
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176226018
Reka code 1149221

4x300/88

Electric number Size Packaging Voltage

4x300/88

Nominal diameter of complete cable mm 60
Nominal weight of cable kg/km 5554
Conductor material Aluminium
Nominal cross-sectional area of conductor mm2 300
Nominal thickness of insulation mm 1.8
Number of wires 4
Min. bending radius
During handling and installation, phase conductor cm 46
During handling and installation, cable cm 72
In final installation, phase conductor cm 32
In final installation, cable cm 50
During handling and installation, cable m 0.72
In final installation, cable m 0.5
Max. pulling force
Pulling-eye kN 18
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,100
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0,206
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176226070