XCMK-HF C

For fixed installations indoors and outdoors. Direct burial in soil is allowed, as long as the relevant national rules of installations are followed. Halogen free cable are recommended when it is important to avoid thick smoke and corrosive gases, in case of fire or overheating.

Standards SFS 5546:2020, SS 424 14 18:2007, HD 604 S1:1994/A3:2005 Part 5 Section I and D, IEC 60502-1:2004
Reaction to fire Cca-s1,d1,a1
CPR - DoP 2019010_DOP.pdf
Conductor 1,5...6 mm² circular solid copper, EN/IEC 60228 class 1
10...25 mm² circular stranded copper, EN/IEC 60228 class 2
35…300 mm² sector shaped stranded copper, EN/IEC 60228 class 2
Insulation Halogen free XLPE
Core Identification (all color combinations in the cable family) blue, brown
brown, black, grey
blue, brown, black, grey
Inner covering plastic tape
Metal screen Copper wires and copper tape
Oversheath UV-protected halogen free polyolefin compound
Colour of the oversheath Black

2x1,5/1,5

Electric number Size Packing (m) Voltage

2x1,5/1,5

Nominal diameter of complete cable (mm) 12
Nominal weight of cable (kg/km) 191
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 1.5
Bending radius
During handling and installation, cable (cm) 141
In final installation, cable (cm) 99
During handling and installation, cable (cm) 14
In final installation, cable (cm) 10
During handling and installation, cable (m) 0.14
In final installation, cable (m) 0.1
Pulling force
Pulling-eye (kN) 0.1
Pulling-stocking (kN) 0.1
Resistance 20 °C (ohm/km) 12.1
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 12.1
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.21
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301005
Reka code 1146403
Nominal diameter of complete cable (mm) 12
Nominal weight of cable (kg/km) 191
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 1.5
Bending radius
During handling and installation, cable (cm) 141
In final installation, cable (cm) 99
During handling and installation, cable (cm) 14
In final installation, cable (cm) 10
During handling and installation, cable (m) 0.14
In final installation, cable (m) 0.1
Pulling force
Pulling-eye (kN) 0.1
Pulling-stocking (kN) 0.1
Resistance 20 °C (ohm/km) 12.1
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 12.1
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.21
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301012
Reka code 1146403

2x2,5/2,5

Electric number Size Packing (m) Voltage

2x2,5/2,5

Nominal diameter of complete cable (mm) 13
Nominal weight of cable (kg/km) 239
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 2.5
Bending radius
During handling and installation, cable (cm) 151
In final installation, cable (cm) 105
During handling and installation, cable (cm) 15
In final installation, cable (cm) 11
During handling and installation, cable (m) 0.15
In final installation, cable (m) 0.11
Pulling force
Pulling-eye (kN) 0.1
Pulling-stocking (kN) 0.1
Resistance 20 °C (ohm/km) 7.41
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 7.41
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.36
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301036
Reka code 1146404
Nominal diameter of complete cable (mm) 13
Nominal weight of cable (kg/km) 239
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 2.5
Bending radius
During handling and installation, cable (cm) 151
In final installation, cable (cm) 105
During handling and installation, cable (cm) 15
In final installation, cable (cm) 11
During handling and installation, cable (m) 0.15
In final installation, cable (m) 0.11
Pulling force
Pulling-eye (kN) 0.1
Pulling-stocking (kN) 0.1
Resistance 20 °C (ohm/km) 7.41
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 7.41
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.36
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301029
Reka code 1146404

2x4/4

Electric number Size Packing (m) Voltage

2x4/4

Nominal diameter of complete cable (mm) 14
Nominal weight of cable (kg/km) 307
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 4
Bending radius
During handling and installation, cable (cm) 165
In final installation, cable (cm) 116
During handling and installation, cable (cm) 17
In final installation, cable (cm) 12
During handling and installation, cable (m) 0.17
In final installation, cable (m) 0.12
Pulling force
Pulling-eye (kN) 0.1
Pulling-stocking (kN) 0.2
Resistance 20 °C (ohm/km) 4.61
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 4.61
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.57
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301043
Reka code 1146405
Nominal diameter of complete cable (mm) 14
Nominal weight of cable (kg/km) 307
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 4
Bending radius
During handling and installation, cable (cm) 165
In final installation, cable (cm) 116
During handling and installation, cable (cm) 17
In final installation, cable (cm) 12
During handling and installation, cable (m) 0.17
In final installation, cable (m) 0.12
Pulling force
Pulling-eye (kN) 0.1
Pulling-stocking (kN) 0.2
Resistance 20 °C (ohm/km) 4.61
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 4.61
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.57
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301050
Reka code 1146405

2x6/6

Electric number Size Packing (m) Voltage

2x6/6

Nominal diameter of complete cable (mm) 15
Nominal weight of cable (kg/km) 389
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 6
Bending radius
During handling and installation, cable (cm) 178
In final installation, cable (cm) 124
During handling and installation, cable (cm) 18
In final installation, cable (cm) 12
During handling and installation, cable (m) 0.18
In final installation, cable (m) 0.12
Pulling force
Pulling-eye (kN) 0.2
Pulling-stocking (kN) 0.2
Resistance 20 °C (ohm/km) 3.08
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 3.08
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.86
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301067
Reka code 1146406
Nominal diameter of complete cable (mm) 15
Nominal weight of cable (kg/km) 389
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 6
Bending radius
During handling and installation, cable (cm) 178
In final installation, cable (cm) 124
During handling and installation, cable (cm) 18
In final installation, cable (cm) 12
During handling and installation, cable (m) 0.18
In final installation, cable (m) 0.12
Pulling force
Pulling-eye (kN) 0.2
Pulling-stocking (kN) 0.2
Resistance 20 °C (ohm/km) 3.08
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 3.08
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.86
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301074
Reka code 1146406

2x10/10

Electric number Size Packing (m) Voltage

2x10/10

Nominal diameter of complete cable (mm) 18
Nominal weight of cable (kg/km) 570
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 10
Bending radius
During handling and installation, cable (cm) 211
In final installation, cable (cm) 148
During handling and installation, cable (cm) 21
In final installation, cable (cm) 15
During handling and installation, cable (m) 0.21
In final installation, cable (m) 0.15
Pulling force
Pulling-eye (kN) 0.3
Pulling-stocking (kN) 0.4
Resistance 20 °C (ohm/km) 1.83
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.83
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 1.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301081
Reka code 1146407
Nominal diameter of complete cable (mm) 18
Nominal weight of cable (kg/km) 570
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 10
Bending radius
During handling and installation, cable (cm) 211
In final installation, cable (cm) 148
During handling and installation, cable (cm) 21
In final installation, cable (cm) 15
During handling and installation, cable (m) 0.21
In final installation, cable (m) 0.15
Pulling force
Pulling-eye (kN) 0.3
Pulling-stocking (kN) 0.4
Resistance 20 °C (ohm/km) 1.83
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.83
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 1.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301098
Reka code 1146407

2x16/16

Electric number Size Packing (m) Voltage

2x16/16

Nominal diameter of complete cable (mm) 20
Nominal weight of cable (kg/km) 828
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 246
In final installation, cable (cm) 172
During handling and installation, cable (cm) 25
In final installation, cable (cm) 17
During handling and installation, cable (m) 0.25
In final installation, cable (m) 0.17
Pulling force
Pulling-eye (kN) 0.5
Pulling-stocking (kN) 0.6
Resistance 20 °C (ohm/km) 1.15
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 2.3
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301111
Reka code 1146408
Nominal diameter of complete cable (mm) 20
Nominal weight of cable (kg/km) 828
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 246
In final installation, cable (cm) 172
During handling and installation, cable (cm) 25
In final installation, cable (cm) 17
During handling and installation, cable (m) 0.25
In final installation, cable (m) 0.17
Pulling force
Pulling-eye (kN) 0.5
Pulling-stocking (kN) 0.6
Resistance 20 °C (ohm/km) 1.15
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 2.3
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301104
Reka code 1146408

2x25/16

Electric number Size Packing (m) Voltage

2x25/16

Nominal diameter of complete cable (mm) 24
Nominal weight of cable (kg/km) 1139
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 288
In final installation, cable (cm) 201
During handling and installation, cable (cm) 29
In final installation, cable (cm) 20
During handling and installation, cable (m) 0.29
In final installation, cable (m) 0.2
Pulling force
Pulling-eye (kN) 0.8
Pulling-stocking (kN) 1
Resistance 20 °C (ohm/km) 0.727
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 3.6
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301135
Reka code 1146409
Nominal diameter of complete cable (mm) 24
Nominal weight of cable (kg/km) 1139
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 288
In final installation, cable (cm) 201
During handling and installation, cable (cm) 29
In final installation, cable (cm) 20
During handling and installation, cable (m) 0.29
In final installation, cable (m) 0.2
Pulling force
Pulling-eye (kN) 0.8
Pulling-stocking (kN) 1
Resistance 20 °C (ohm/km) 0.727
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 3.6
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301128
Reka code 1146409

3x1,5/1,5

Electric number Size Packing (m) Voltage

3x1,5/1,5

Nominal diameter of complete cable (mm) 12
Nominal weight of cable (kg/km) 207
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 1.5
Bending radius
During handling and installation, cable (cm) 147
In final installation, cable (cm) 103
During handling and installation, cable (cm) 15
In final installation, cable (cm) 10
During handling and installation, cable (m) 0.15
In final installation, cable (m) 0.1
Pulling force
Pulling-eye (kN) 0.1
Pulling-stocking (kN) 0.1
Resistance 20 °C (ohm/km) 12.1
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 12.1
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.21
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301142
Reka code 1146415
Nominal diameter of complete cable (mm) 12
Nominal weight of cable (kg/km) 207
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 1.5
Bending radius
During handling and installation, cable (cm) 147
In final installation, cable (cm) 103
During handling and installation, cable (cm) 15
In final installation, cable (cm) 10
During handling and installation, cable (m) 0.15
In final installation, cable (m) 0.1
Pulling force
Pulling-eye (kN) 0.1
Pulling-stocking (kN) 0.1
Resistance 20 °C (ohm/km) 12.1
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 12.1
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.21
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301159
Reka code 1146415

3x2,5/2,5

Electric number Size Packing (m) Voltage

3x2,5/2,5

Nominal diameter of complete cable (mm) 13
Nominal weight of cable (kg/km) 259
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 2.5
Bending radius
During handling and installation, cable (cm) 156
In final installation, cable (cm) 109
During handling and installation, cable (cm) 16
In final installation, cable (cm) 11
During handling and installation, cable (m) 0.16
In final installation, cable (m) 0.11
Pulling force
Pulling-eye (kN) 0.1
Pulling-stocking (kN) 0.2
Resistance 20 °C (ohm/km) 7.41
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 7.41
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.36
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301166
Reka code 1146416
Nominal diameter of complete cable (mm) 13
Nominal weight of cable (kg/km) 259
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 2.5
Bending radius
During handling and installation, cable (cm) 156
In final installation, cable (cm) 109
During handling and installation, cable (cm) 16
In final installation, cable (cm) 11
During handling and installation, cable (m) 0.16
In final installation, cable (m) 0.11
Pulling force
Pulling-eye (kN) 0.1
Pulling-stocking (kN) 0.2
Resistance 20 °C (ohm/km) 7.41
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 7.41
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.36
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301173
Reka code 1146416

3x4/4

Electric number Size Packing (m) Voltage

3x4/4

Nominal diameter of complete cable (mm) 14
Nominal weight of cable (kg/km) 343
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 4
Bending radius
During handling and installation, cable (cm) 172
In final installation, cable (cm) 120
During handling and installation, cable (cm) 17
In final installation, cable (cm) 12
During handling and installation, cable (m) 0.17
In final installation, cable (m) 0.12
Pulling force
Pulling-eye (kN) 0.2
Pulling-stocking (kN) 0.2
Resistance 20 °C (ohm/km) 4.61
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 4.61
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.57
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301197
Reka code 1146417
Nominal diameter of complete cable (mm) 14
Nominal weight of cable (kg/km) 343
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 4
Bending radius
During handling and installation, cable (cm) 172
In final installation, cable (cm) 120
During handling and installation, cable (cm) 17
In final installation, cable (cm) 12
During handling and installation, cable (m) 0.17
In final installation, cable (m) 0.12
Pulling force
Pulling-eye (kN) 0.2
Pulling-stocking (kN) 0.2
Resistance 20 °C (ohm/km) 4.61
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 4.61
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.57
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301180
Reka code 1146417

3x6/6

Electric number Size Packing (m) Voltage

3x6/6

Nominal diameter of complete cable (mm) 15
Nominal weight of cable (kg/km) 442
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 6
Bending radius
During handling and installation, cable (cm) 185
In final installation, cable (cm) 130
During handling and installation, cable (cm) 19
In final installation, cable (cm) 13
During handling and installation, cable (m) 0.19
In final installation, cable (m) 0.13
Pulling force
Pulling-eye (kN) 0.3
Pulling-stocking (kN) 0.4
Resistance 20 °C (ohm/km) 3.08
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 3.08
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.86
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301203
Reka code 1146418
Nominal diameter of complete cable (mm) 15
Nominal weight of cable (kg/km) 442
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 6
Bending radius
During handling and installation, cable (cm) 185
In final installation, cable (cm) 130
During handling and installation, cable (cm) 19
In final installation, cable (cm) 13
During handling and installation, cable (m) 0.19
In final installation, cable (m) 0.13
Pulling force
Pulling-eye (kN) 0.3
Pulling-stocking (kN) 0.4
Resistance 20 °C (ohm/km) 3.08
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 3.08
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.86
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301210
Reka code 1146418

3x10/10

Electric number Size Packing (m) Voltage

3x10/10

Nominal diameter of complete cable (mm) 18
Nominal weight of cable (kg/km) 657
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 10
Bending radius
During handling and installation, cable (cm) 221
In final installation, cable (cm) 155
During handling and installation, cable (cm) 22
In final installation, cable (cm) 15
During handling and installation, cable (m) 0.22
In final installation, cable (m) 0.15
Pulling force
Pulling-eye (kN) 0.5
Pulling-stocking (kN) 0.6
Resistance 20 °C (ohm/km) 1.83
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.83
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 1.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301227
Reka code 1146419
Nominal diameter of complete cable (mm) 18
Nominal weight of cable (kg/km) 657
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 10
Bending radius
During handling and installation, cable (cm) 221
In final installation, cable (cm) 155
During handling and installation, cable (cm) 22
In final installation, cable (cm) 15
During handling and installation, cable (m) 0.22
In final installation, cable (m) 0.15
Pulling force
Pulling-eye (kN) 0.5
Pulling-stocking (kN) 0.6
Resistance 20 °C (ohm/km) 1.83
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.83
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 1.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301234
Reka code 1146419

3x16/16

Electric number Size Packing (m) Voltage

3x16/16

Nominal diameter of complete cable (mm) 21
Nominal weight of cable (kg/km) 960
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 258
In final installation, cable (cm) 180
During handling and installation, cable (cm) 26
In final installation, cable (cm) 18
During handling and installation, cable (m) 0.26
In final installation, cable (m) 0.18
Pulling force
Pulling-eye (kN) 0.7
Pulling-stocking (kN) 1
Resistance 20 °C (ohm/km) 1.15
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 2.3
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301241
Reka code 1146420
Nominal diameter of complete cable (mm) 21
Nominal weight of cable (kg/km) 960
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 258
In final installation, cable (cm) 180
During handling and installation, cable (cm) 26
In final installation, cable (cm) 18
During handling and installation, cable (m) 0.26
In final installation, cable (m) 0.18
Pulling force
Pulling-eye (kN) 0.7
Pulling-stocking (kN) 1
Resistance 20 °C (ohm/km) 1.15
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 2.3
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301258
Reka code 1146420

3x25/16

Electric number Size Packing (m) Voltage

3x25/16

Nominal diameter of complete cable (mm) 25
Nominal weight of cable (kg/km) 1338
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 302
In final installation, cable (cm) 212
During handling and installation, cable (cm) 30
In final installation, cable (cm) 21
During handling and installation, cable (m) 0.3
In final installation, cable (m) 0.21
Pulling force
Pulling-eye (kN) 1.1
Pulling-stocking (kN) 1.5
Resistance 20 °C (ohm/km) 0.727
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 3.6
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301272
Reka code 1146421
Nominal diameter of complete cable (mm) 25
Nominal weight of cable (kg/km) 1338
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 302
In final installation, cable (cm) 212
During handling and installation, cable (cm) 30
In final installation, cable (cm) 21
During handling and installation, cable (m) 0.3
In final installation, cable (m) 0.21
Pulling force
Pulling-eye (kN) 1.1
Pulling-stocking (kN) 1.5
Resistance 20 °C (ohm/km) 0.727
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 3.6
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301265
Reka code 1146421

3x35/16

Electric number Size Packing (m) Voltage

3x35/16

Nominal diameter of complete cable (mm) 23
Nominal weight of cable (kg/km) 1333
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 277
In final installation, cable (cm) 194
During handling and installation, cable (cm) 28
In final installation, cable (cm) 19
During handling and installation, cable (m) 0.28
In final installation, cable (m) 0.19
Pulling force
Pulling-eye (kN) 1.6
Pulling-stocking (kN) 2.1
Resistance 20 °C (ohm/km) 0.524
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 5
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301296
Reka code 1146422
Nominal diameter of complete cable (mm) 23
Nominal weight of cable (kg/km) 1333
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 277
In final installation, cable (cm) 194
During handling and installation, cable (cm) 28
In final installation, cable (cm) 19
During handling and installation, cable (m) 0.28
In final installation, cable (m) 0.19
Pulling force
Pulling-eye (kN) 1.6
Pulling-stocking (kN) 2.1
Resistance 20 °C (ohm/km) 0.524
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 5
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301289
Reka code 1146422

3x50/25

Electric number Size Packing (m) Voltage

3x50/25

Nominal diameter of complete cable (mm) 26
Nominal weight of cable (kg/km) 1821
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 25
Bending radius
During handling and installation, cable (cm) 316
In final installation, cable (cm) 221
During handling and installation, cable (cm) 32
In final installation, cable (cm) 22
During handling and installation, cable (m) 0.32
In final installation, cable (m) 0.22
Pulling force
Pulling-eye (kN) 2.3
Pulling-stocking (kN) 3
Resistance 20 °C (ohm/km) 0.387
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.727
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 7.2
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301319
Reka code 1146423
Nominal diameter of complete cable (mm) 26
Nominal weight of cable (kg/km) 1821
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 25
Bending radius
During handling and installation, cable (cm) 316
In final installation, cable (cm) 221
During handling and installation, cable (cm) 32
In final installation, cable (cm) 22
During handling and installation, cable (m) 0.32
In final installation, cable (m) 0.22
Pulling force
Pulling-eye (kN) 2.3
Pulling-stocking (kN) 3
Resistance 20 °C (ohm/km) 0.387
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.727
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 7.2
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301302
Reka code 1146423

3x70/35

Electric number Size Packing (m) Voltage

3x70/35

Nominal diameter of complete cable (mm) 30
Nominal weight of cable (kg/km) 2520
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 35
Bending radius
During handling and installation, cable (cm) 365
In final installation, cable (cm) 255
During handling and installation, cable (cm) 36
In final installation, cable (cm) 26
During handling and installation, cable (m) 0.36
In final installation, cable (m) 0.26
Pulling force
Pulling-eye (kN) 3.2
Pulling-stocking (kN) 4.2
Resistance 20 °C (ohm/km) 0.268
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.524
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 10
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301333
Reka code 1146424
Nominal diameter of complete cable (mm) 30
Nominal weight of cable (kg/km) 2520
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 35
Bending radius
During handling and installation, cable (cm) 365
In final installation, cable (cm) 255
During handling and installation, cable (cm) 36
In final installation, cable (cm) 26
During handling and installation, cable (m) 0.36
In final installation, cable (m) 0.26
Pulling force
Pulling-eye (kN) 3.2
Pulling-stocking (kN) 4.2
Resistance 20 °C (ohm/km) 0.268
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.524
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 10
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301326
Reka code 1146424

3x95/50

Electric number Size Packing (m) Voltage

3x95/50

Nominal diameter of complete cable (mm) 34
Nominal weight of cable (kg/km) 3406
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 50
Bending radius
During handling and installation, cable (cm) 402
In final installation, cable (cm) 282
During handling and installation, cable (cm) 40
In final installation, cable (cm) 28
During handling and installation, cable (m) 0.4
In final installation, cable (m) 0.28
Pulling force
Pulling-eye (kN) 4.3
Pulling-stocking (kN) 5.7
Resistance 20 °C (ohm/km) 0.193
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.387
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 13.6
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301357
Reka code 1146425
Nominal diameter of complete cable (mm) 34
Nominal weight of cable (kg/km) 3406
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 50
Bending radius
During handling and installation, cable (cm) 402
In final installation, cable (cm) 282
During handling and installation, cable (cm) 40
In final installation, cable (cm) 28
During handling and installation, cable (m) 0.4
In final installation, cable (m) 0.28
Pulling force
Pulling-eye (kN) 4.3
Pulling-stocking (kN) 5.7
Resistance 20 °C (ohm/km) 0.193
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.387
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 13.6
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301340
Reka code 1146425

3x120/70

Electric number Size Packing (m) Voltage

3x120/70

Nominal diameter of complete cable (mm) 36
Nominal weight of cable (kg/km) 4299
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 70
Bending radius
During handling and installation, cable (cm) 438
In final installation, cable (cm) 307
During handling and installation, cable (cm) 44
In final installation, cable (cm) 31
During handling and installation, cable (m) 0.44
In final installation, cable (m) 0.31
Pulling force
Pulling-eye (kN) 5.4
Pulling-stocking (kN) 7.2
Resistance 20 °C (ohm/km) 0.153
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.268
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 17.2
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301371
Reka code 1146426
Nominal diameter of complete cable (mm) 36
Nominal weight of cable (kg/km) 4299
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 70
Bending radius
During handling and installation, cable (cm) 438
In final installation, cable (cm) 307
During handling and installation, cable (cm) 44
In final installation, cable (cm) 31
During handling and installation, cable (m) 0.44
In final installation, cable (m) 0.31
Pulling force
Pulling-eye (kN) 5.4
Pulling-stocking (kN) 7.2
Resistance 20 °C (ohm/km) 0.153
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.268
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 17.2
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301364
Reka code 1146426

3x150/70

Electric number Size Packing (m) Voltage

3x150/70

Nominal diameter of complete cable (mm) 41
Nominal weight of cable (kg/km) 5201
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 70
Bending radius
During handling and installation, cable (cm) 492
In final installation, cable (cm) 344
During handling and installation, cable (cm) 49
In final installation, cable (cm) 34
During handling and installation, cable (m) 0.49
In final installation, cable (m) 0.34
Pulling force
Pulling-eye (kN) 6.8
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.124
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.268
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 21.5
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301388
Reka code 1146427

3x185/95

Electric number Size Packing (m) Voltage

3x185/95

Nominal diameter of complete cable (mm) 45
Nominal weight of cable (kg/km) 6563
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 95
Bending radius
During handling and installation, cable (cm) 544
In final installation, cable (cm) 381
During handling and installation, cable (cm) 54
In final installation, cable (cm) 38
During handling and installation, cable (m) 0.54
In final installation, cable (m) 0.38
Pulling force
Pulling-eye (kN) 8.3
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.0991
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.193
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 26.5
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301395
Reka code 1146428

3x240/120

Electric number Size Packing (m) Voltage

3x240/120

Nominal diameter of complete cable (mm) 53
Nominal weight of cable (kg/km) 8568
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 120
Bending radius
During handling and installation, cable (cm) 635
In final installation, cable (cm) 444
During handling and installation, cable (cm) 63
In final installation, cable (cm) 44
During handling and installation, cable (m) 0.63
In final installation, cable (m) 0.44
Pulling force
Pulling-eye (kN) 10.8
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.0754
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.153
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 34.3
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301401
Reka code 1146429

3x300/150

Electric number Size Packing (m) Voltage

3x300/150

Nominal diameter of complete cable (mm) 56
Nominal weight of cable (kg/km) 10608
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 150
Bending radius
During handling and installation, cable (cm) 666
In final installation, cable (cm) 466
During handling and installation, cable (cm) 67
In final installation, cable (cm) 47
During handling and installation, cable (m) 0.67
In final installation, cable (m) 0.47
Pulling force
Pulling-eye (kN) 13.5
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.0601
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.124
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 43.1
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301418
Reka code 1146430

4x1,5/1,5

Electric number Size Packing (m) Voltage

4x1,5/1,5

Nominal diameter of complete cable (mm) 13
Nominal weight of cable (kg/km) 234
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 1.5
Bending radius
During handling and installation, cable (cm) 155
In final installation, cable (cm) 109
During handling and installation, cable (cm) 16
In final installation, cable (cm) 11
During handling and installation, cable (m) 0.16
In final installation, cable (m) 0.11
Pulling force
Pulling-eye (kN) 0.1
Pulling-stocking (kN) 0.1
Resistance 20 °C (ohm/km) 12.1
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 12.1
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.21
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301432
Reka code 1146435
Nominal diameter of complete cable (mm) 13
Nominal weight of cable (kg/km) 234
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 1.5
Bending radius
During handling and installation, cable (cm) 155
In final installation, cable (cm) 109
During handling and installation, cable (cm) 16
In final installation, cable (cm) 11
During handling and installation, cable (m) 0.16
In final installation, cable (m) 0.11
Pulling force
Pulling-eye (kN) 0.1
Pulling-stocking (kN) 0.1
Resistance 20 °C (ohm/km) 12.1
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 12.1
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.21
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301425
Reka code 1146435

4x2,5/2,5

Electric number Size Packing (m) Voltage

4x2,5/2,5

Nominal diameter of complete cable (mm) 14
Nominal weight of cable (kg/km) 296
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 2.5
Bending radius
During handling and installation, cable (cm) 166
In final installation, cable (cm) 116
During handling and installation, cable (cm) 17
In final installation, cable (cm) 12
During handling and installation, cable (m) 0.17
In final installation, cable (m) 0.12
Pulling force
Pulling-eye (kN) 0.2
Pulling-stocking (kN) 0.2
Resistance 20 °C (ohm/km) 7.41
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 7.41
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.36
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301456
Reka code 1146436
Nominal diameter of complete cable (mm) 14
Nominal weight of cable (kg/km) 296
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 2.5
Bending radius
During handling and installation, cable (cm) 166
In final installation, cable (cm) 116
During handling and installation, cable (cm) 17
In final installation, cable (cm) 12
During handling and installation, cable (m) 0.17
In final installation, cable (m) 0.12
Pulling force
Pulling-eye (kN) 0.2
Pulling-stocking (kN) 0.2
Resistance 20 °C (ohm/km) 7.41
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 7.41
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.36
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301449
Reka code 1146436

4x4/4

Electric number Size Packing (m) Voltage

4x4/4

Nominal diameter of complete cable (mm) 15
Nominal weight of cable (kg/km) 398
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 4
Bending radius
During handling and installation, cable (cm) 183
In final installation, cable (cm) 128
During handling and installation, cable (cm) 18
In final installation, cable (cm) 13
During handling and installation, cable (m) 0.18
In final installation, cable (m) 0.13
Pulling force
Pulling-eye (kN) 0.2
Pulling-stocking (kN) 0.3
Resistance 20 °C (ohm/km) 4.61
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 4.61
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.57
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301470
Reka code 1146437
Nominal diameter of complete cable (mm) 15
Nominal weight of cable (kg/km) 398
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 4
Bending radius
During handling and installation, cable (cm) 183
In final installation, cable (cm) 128
During handling and installation, cable (cm) 18
In final installation, cable (cm) 13
During handling and installation, cable (m) 0.18
In final installation, cable (m) 0.13
Pulling force
Pulling-eye (kN) 0.2
Pulling-stocking (kN) 0.3
Resistance 20 °C (ohm/km) 4.61
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 4.61
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.57
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301463
Reka code 1146437

4x6/6

Electric number Size Packing (m) Voltage

4x6/6

Nominal diameter of complete cable (mm) 17
Nominal weight of cable (kg/km) 520
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 6
Bending radius
During handling and installation, cable (cm) 198
In final installation, cable (cm) 139
During handling and installation, cable (cm) 20
In final installation, cable (cm) 14
During handling and installation, cable (m) 0.2
In final installation, cable (m) 0.14
Pulling force
Pulling-eye (kN) 0.4
Pulling-stocking (kN) 0.5
Resistance 20 °C (ohm/km) 3.08
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 3.08
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.86
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301494
Reka code 1146438
Nominal diameter of complete cable (mm) 17
Nominal weight of cable (kg/km) 520
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 6
Bending radius
During handling and installation, cable (cm) 198
In final installation, cable (cm) 139
During handling and installation, cable (cm) 20
In final installation, cable (cm) 14
During handling and installation, cable (m) 0.2
In final installation, cable (m) 0.14
Pulling force
Pulling-eye (kN) 0.4
Pulling-stocking (kN) 0.5
Resistance 20 °C (ohm/km) 3.08
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 3.08
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.86
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301487
Reka code 1146438

4x10/10

Electric number Size Packing (m) Voltage

4x10/10

Nominal diameter of complete cable (mm) 20
Nominal weight of cable (kg/km) 801
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 10
Bending radius
During handling and installation, cable (cm) 244
In final installation, cable (cm) 171
During handling and installation, cable (cm) 24
In final installation, cable (cm) 17
During handling and installation, cable (m) 0.24
In final installation, cable (m) 0.17
Pulling force
Pulling-eye (kN) 0.6
Pulling-stocking (kN) 0.8
Resistance 20 °C (ohm/km) 1.83
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.83
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 1.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301500
Reka code 1146439
Nominal diameter of complete cable (mm) 20
Nominal weight of cable (kg/km) 801
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 10
Bending radius
During handling and installation, cable (cm) 244
In final installation, cable (cm) 171
During handling and installation, cable (cm) 24
In final installation, cable (cm) 17
During handling and installation, cable (m) 0.24
In final installation, cable (m) 0.17
Pulling force
Pulling-eye (kN) 0.6
Pulling-stocking (kN) 0.8
Resistance 20 °C (ohm/km) 1.83
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.83
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 1.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301517
Reka code 1146439

4x16/16

Electric number Size Packing (m) Voltage

4x16/16

Nominal diameter of complete cable (mm) 23
Nominal weight of cable (kg/km) 1142
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 278
In final installation, cable (cm) 194
During handling and installation, cable (cm) 28
In final installation, cable (cm) 19
During handling and installation, cable (m) 0.28
In final installation, cable (m) 0.19
Pulling force
Pulling-eye (kN) 1
Pulling-stocking (kN) 1.3
Resistance 20 °C (ohm/km) 1.15
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 2.3
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301524
Reka code 1146440
Nominal diameter of complete cable (mm) 23
Nominal weight of cable (kg/km) 1142
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 278
In final installation, cable (cm) 194
During handling and installation, cable (cm) 28
In final installation, cable (cm) 19
During handling and installation, cable (m) 0.28
In final installation, cable (m) 0.19
Pulling force
Pulling-eye (kN) 1
Pulling-stocking (kN) 1.3
Resistance 20 °C (ohm/km) 1.15
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 2.3
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301531
Reka code 1146440

4x25/16

Electric number Size Packing (m) Voltage

4x25/16

Nominal diameter of complete cable (mm) 27
Nominal weight of cable (kg/km) 1616
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 328
In final installation, cable (cm) 230
During handling and installation, cable (cm) 33
In final installation, cable (cm) 23
During handling and installation, cable (m) 0.33
In final installation, cable (m) 0.23
Pulling force
Pulling-eye (kN) 1.5
Pulling-stocking (kN) 2
Resistance 20 °C (ohm/km) 0.727
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 3.6
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301548
Reka code 1146441
Nominal diameter of complete cable (mm) 27
Nominal weight of cable (kg/km) 1616
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 328
In final installation, cable (cm) 230
During handling and installation, cable (cm) 33
In final installation, cable (cm) 23
During handling and installation, cable (m) 0.33
In final installation, cable (m) 0.23
Pulling force
Pulling-eye (kN) 1.5
Pulling-stocking (kN) 2
Resistance 20 °C (ohm/km) 0.727
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 3.6
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301555
Reka code 1146441

4x35/16

Electric number Size Packing (m) Voltage

4x35/16

Nominal diameter of complete cable (mm) 26
Nominal weight of cable (kg/km) 1690
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 312
In final installation, cable (cm) 219
During handling and installation, cable (cm) 31
In final installation, cable (cm) 22
During handling and installation, cable (m) 0.31
In final installation, cable (m) 0.22
Pulling force
Pulling-eye (kN) 2.1
Pulling-stocking (kN) 2.8
Resistance 20 °C (ohm/km) 0.524
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 5
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301562
Reka code 1146442
Nominal diameter of complete cable (mm) 26
Nominal weight of cable (kg/km) 1690
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 312
In final installation, cable (cm) 219
During handling and installation, cable (cm) 31
In final installation, cable (cm) 22
During handling and installation, cable (m) 0.31
In final installation, cable (m) 0.22
Pulling force
Pulling-eye (kN) 2.1
Pulling-stocking (kN) 2.8
Resistance 20 °C (ohm/km) 0.524
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 5
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301579
Reka code 1146442

4x50/25

Electric number Size Packing (m) Voltage

4x50/25

Nominal diameter of complete cable (mm) 30
Nominal weight of cable (kg/km) 2319
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 25
Bending radius
During handling and installation, cable (cm) 355
In final installation, cable (cm) 248
During handling and installation, cable (cm) 35
In final installation, cable (cm) 25
During handling and installation, cable (m) 0.35
In final installation, cable (m) 0.25
Pulling force
Pulling-eye (kN) 3
Pulling-stocking (kN) 4
Resistance 20 °C (ohm/km) 0.387
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.727
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 7.2
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301593
Reka code 1146443
Nominal diameter of complete cable (mm) 30
Nominal weight of cable (kg/km) 2319
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 25
Bending radius
During handling and installation, cable (cm) 355
In final installation, cable (cm) 248
During handling and installation, cable (cm) 35
In final installation, cable (cm) 25
During handling and installation, cable (m) 0.35
In final installation, cable (m) 0.25
Pulling force
Pulling-eye (kN) 3
Pulling-stocking (kN) 4
Resistance 20 °C (ohm/km) 0.387
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.727
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 7.2
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301586
Reka code 1146443

4x70/35

Electric number Size Packing (m) Voltage

4x70/35

Nominal diameter of complete cable (mm) 34
Nominal weight of cable (kg/km) 3208
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 35
Bending radius
During handling and installation, cable (cm) 409
In final installation, cable (cm) 287
During handling and installation, cable (cm) 41
In final installation, cable (cm) 29
During handling and installation, cable (m) 0.41
In final installation, cable (m) 0.29
Pulling force
Pulling-eye (kN) 4.2
Pulling-stocking (kN) 5.6
Resistance 20 °C (ohm/km) 0.268
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.524
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 10
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301616
Reka code 1146444
Nominal diameter of complete cable (mm) 34
Nominal weight of cable (kg/km) 3208
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 35
Bending radius
During handling and installation, cable (cm) 409
In final installation, cable (cm) 287
During handling and installation, cable (cm) 41
In final installation, cable (cm) 29
During handling and installation, cable (m) 0.41
In final installation, cable (m) 0.29
Pulling force
Pulling-eye (kN) 4.2
Pulling-stocking (kN) 5.6
Resistance 20 °C (ohm/km) 0.268
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.524
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 10
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301609
Reka code 1146444

4x95/50

Electric number Size Packing (m) Voltage

4x95/50

Nominal diameter of complete cable (mm) 38
Nominal weight of cable (kg/km) 4329
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 50
Bending radius
During handling and installation, cable (cm) 450
In final installation, cable (cm) 315
During handling and installation, cable (cm) 45
In final installation, cable (cm) 32
During handling and installation, cable (m) 0.45
In final installation, cable (m) 0.32
Pulling force
Pulling-eye (kN) 5.7
Pulling-stocking (kN) 7.6
Resistance 20 °C (ohm/km) 0.193
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.387
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 13.6
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301623
Reka code 1146445

4x120/70

Electric number Size Packing (m) Voltage

4x120/70

Nominal diameter of complete cable (mm) 42
Nominal weight of cable (kg/km) 5495
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 70
Bending radius
During handling and installation, cable (cm) 501
In final installation, cable (cm) 351
During handling and installation, cable (cm) 50
In final installation, cable (cm) 35
During handling and installation, cable (m) 0.5
In final installation, cable (m) 0.35
Pulling force
Pulling-eye (kN) 7.2
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.153
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.268
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 17.2
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301630
Reka code 1146446

4x150/70

Electric number Size Packing (m) Voltage

4x150/70

Nominal diameter of complete cable (mm) 46
Nominal weight of cable (kg/km) 6639
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 70
Bending radius
During handling and installation, cable (cm) 546
In final installation, cable (cm) 382
During handling and installation, cable (cm) 55
In final installation, cable (cm) 38
During handling and installation, cable (m) 0.55
In final installation, cable (m) 0.38
Pulling force
Pulling-eye (kN) 9
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.124
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.268
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 21.5
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301647
Reka code 1146447

4x185/95

Electric number Size Packing (m) Voltage

4x185/95

Nominal diameter of complete cable (mm) 51
Nominal weight of cable (kg/km) 8382
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 95
Bending radius
During handling and installation, cable (cm) 612
In final installation, cable (cm) 429
During handling and installation, cable (cm) 61
In final installation, cable (cm) 43
During handling and installation, cable (m) 0.61
In final installation, cable (m) 0.43
Pulling force
Pulling-eye (kN) 11.1
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.0991
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.193
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 26.5
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301654
Reka code 1146448

4x240/120

Electric number Size Packing (m) Voltage

4x240/120

Nominal diameter of complete cable (mm) 57
Nominal weight of cable (kg/km) 10904
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 120
Bending radius
During handling and installation, cable (cm) 679
In final installation, cable (cm) 476
During handling and installation, cable (cm) 68
In final installation, cable (cm) 48
During handling and installation, cable (m) 0.68
In final installation, cable (m) 0.48
Pulling force
Pulling-eye (kN) 14.4
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.0754
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.153
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 34.3
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301661
Reka code 1146449

4x300/150

Electric number Size Packing (m) Voltage

4x300/150

Nominal diameter of complete cable (mm) 61
Nominal weight of cable (kg/km) 13554
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 150
Bending radius
During handling and installation, cable (cm) 734
In final installation, cable (cm) 514
During handling and installation, cable (cm) 73
In final installation, cable (cm) 51
During handling and installation, cable (m) 0.73
In final installation, cable (m) 0.51
Pulling force
Pulling-eye (kN) 18
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.0601
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.124
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 43.1
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301678
Reka code 1146450