Medium-voltage cable for fixed installations outdoors. May be buried directly in soil. Installations must be in accordance with national regulations and rules of installations. Cable is longitudinally and radially watertight and therefore it is suitable where wet soil and / or fresh water permanently occurs. The cable is halogen-free, but without fire protection. The cable is not CPR-classified.

Standards HD 620 10 K
Conductor Watertight, circular, stranded aluminium, EN/IEC 60228 class 2
Conductor screen Semiconducting cross-linked polyethylene XLPE
Insulation Cross-linked polyethylene XLPE
Insulation screen Semiconducting cross-linked polyethylene XLPE
Core Identification (all color combinations in the cable family) Black insulation, white numbers
Inner covering Water swellable tape under and over screen
Metal screen Copper wires and aluminium foil (CAS). Polyethylene laminated aluminium foil acts as a part of the metallic screen and needs to be connected in cable joints and terminations
Oversheath PE-plastic
Colour of the oversheath Black

1x400/35

Electric number Size Packaging Voltage

1x400/35

Nominal diameter of complete cable mm 48
Nominal weight of cable kg/km 2403
Conductor material Aluminum
Nominal diameter of conductor mm 22.5
Nominal cross-sectional area of conductor mm2 400
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 38.1
Number of wires 1
Nominal size of metal screen mm2 35
Nominal thickness of aluminium laminated foil mm 0.2
Nominal thickness of semi-conducting layer mm 0.3
Min. bending radius
In final installation, phase conductor mm 0.53
During handling and installation, cable cm 72
In final installation, cable cm 50
During handling and installation, cable m 0.72
In final installation, phase conductor m 0.53
In final installation, cable m 0.5
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 6
Resistance 20 °C Ω/km 0.0778
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176014851
Reka code 1181233

1x630/50

Electric number Size Packaging Voltage

1x630/50

Nominal diameter of complete cable mm 56
Nominal weight of cable kg/km 3574
Conductor material Aluminum
Nominal diameter of conductor mm 29.4
Nominal cross-sectional area of conductor mm2 630
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 45.2
Number of wires 1
Nominal size of metal screen mm2 50
Nominal thickness of aluminium laminated foil mm 0.2
Nominal thickness of semi-conducting layer mm 0.3
Min. bending radius
In final installation, phase conductor mm 0.6
During handling and installation, cable cm 84
In final installation, cable cm 59
During handling and installation, cable m 0.84
In final installation, phase conductor m 0.6
In final installation, cable m 0.59
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0.0469
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176014868
Reka code 1181235