HXCMK

For fixed installations outdoors. May be buried directly into soil. Not for submarine or similar applications. HXCMK 1x35/16 Eca is CPR-classified.

Standards HD 620 S2:2010 Part 10 Secti
Reaction to fire Eca
CPR - DoP 2017076_DOP.pdf
Conductor Circular stranded copper, EN/IEC 60228 class 2
Insulation Conductor screen, semiconducting XLPE,
Insulation XLPE,
Insulation screen, semiconducting XLPE
Colour of the oversheath Black

1x35/16

Electric number Size Packing (m) Voltage

1x35/16

Nominal diameter of complete cable (mm) 26
Nominal weight of cable (kg/km) 902
Conductor material Copper
Nominal diameter of conductor (mm) 6.9
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 5.5
Nominal diameter over the insulation without insulation screen (mm) 18.1
Number of wires 1
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 390
In final installation, cable (cm) 273
During handling and installation, phase conductor (cm) 0.41
In final installation, phase conductor (cm) 0.28
Pulling force
Pulling-eye (kN) 3.5
Pulling-stocking (kN) 0.7
Resistance 20 °C (ohm/km) 0.524
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 5
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6410006030101
Reka code 1188221
Nominal diameter of complete cable (mm) 26
Nominal weight of cable (kg/km) 902
Conductor material Copper
Nominal diameter of conductor (mm) 6.9
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 5.5
Nominal diameter over the insulation without insulation screen (mm) 18.1
Number of wires 1
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 390
In final installation, cable (cm) 273
During handling and installation, phase conductor (cm) 0.41
In final installation, phase conductor (cm) 0.28
Pulling force
Pulling-eye (kN) 3.5
Pulling-stocking (kN) 0.7
Resistance 20 °C (ohm/km) 0.524
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 5
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6410006030095
Reka code 1188221