HXCMK

For fixed installations outdoors. May be buried directly into soil. Not for submarine or similar applications. HXCMK 1x35/16 Eca is CPR-classified.

Standards HD 620 S2:2010 Part 10 Section F, SFS 5636:2017
Reaction to fire Eca
CPR - DoP 2017076_DOP.pdf
Conductor Circular stranded copper, EN/IEC 60228 class 2
Conductor screen Semiconducting cross-linked polyethylene XLPE
Insulation Cross-linked polyethylene XLPE
Insulation screen Semiconducting cross-linked polyethylene XLPE
Colour of the oversheath Black

1x35/16

Electric number Size Packaging Voltage

1x35/16

Nominal diameter of complete cable mm 26
Nominal weight of cable kg/km 902
Conductor material Copper
Nominal diameter of conductor mm 6.9
Nominal cross-sectional area of conductor mm2 35
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 18.1
Nominal size of metal screen mm2 16
Min. bending radius
During handling and installation, cable mm 390
In final installation, cable mm 273
During handling and installation, phase conductor mm 0.41
In final installation, phase conductor mm 0.28
During handling and installation, cable cm 39
In final installation, cable cm 27
During handling and installation, cable m 0.39
In final installation, cable m 0.27
Max. pulling force
Pulling-eye kN 3.5
Pulling-stocking kN 0.7
Resistance 20 °C Ω/km 0.524
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1.15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006030101
Reka code 1188221
Nominal diameter of complete cable mm 26
Nominal weight of cable kg/km 902
Conductor material Copper
Nominal diameter of conductor mm 6.9
Nominal cross-sectional area of conductor mm2 35
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 18.1
Nominal size of metal screen mm2 16
Min. bending radius
During handling and installation, cable mm 390
In final installation, cable mm 273
During handling and installation, phase conductor mm 0.41
In final installation, phase conductor mm 0.28
During handling and installation, cable cm 39
In final installation, cable cm 27
During handling and installation, cable m 0.39
In final installation, cable m 0.27
Max. pulling force
Pulling-eye kN 3.5
Pulling-stocking kN 0.7
Resistance 20 °C Ω/km 0.524
Maximum d.c. resistance at 20 °C, metal screen Ω/km 1.15
Minimum cable temperature during transport °C -25
Minimum cable temperature during handling and installation °C -15
Minimum cable temperature during operation °C -40
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006030095
Reka code 1188221