FRHF Power

For fixed installations indoors and outdoors. Not to be laid in soil nor directly in cast concrete. For locations where safety requires the operation of alarm, control, signalling and energy circuits also during a fire. Halogen free and flame retardant.

Standards HD 604 S1:1994/A3:2005 5-D; IEC 60502-1:2004
Conductor 1,5…4 mm² circular solid copper, EN/IEC 60228 class 1
6…50 mm² circular stranded copper, EN/IEC 60228 class 2
Insulation Halogen free XLPE, mica tape
Core Identification (all color combinations in the cable family) blue, brown



brown, black, grey



yellowgreen, blue, brown



yellowgreen, blue, brown, black (1,5 and 2,5 mm²)



yellowgreen, brown, black, grey (4 mm²)



yellowgreen, blue, brown, black, grey
Separation sheath Halogen-free filling compound
Oversheath UV-protected, halogen free polyolefin compound
Colour of the oversheath orange

2x1,5 N

Electric number Size Packing (m) Voltage

2x1,5 N

Nominal diameter of complete cable (mm) 11
Nominal weight of cable (kg/km) 165
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 132
In final installation, cable (cm) 92
During handling and installation, cable (cm) 11
In final installation, cable (cm) 9
Pulling force
Pulling-eye (kN) 0.05
Pulling-stocking (kN) 0.06
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.21
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301708
Reka code 1146542
Nominal diameter of complete cable (mm) 11
Nominal weight of cable (kg/km) 165
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 132
In final installation, cable (cm) 92
During handling and installation, cable (cm) 11
In final installation, cable (cm) 9
Pulling force
Pulling-eye (kN) 0.05
Pulling-stocking (kN) 0.06
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.21
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301692
Reka code 1146542

2x2,5 N

Electric number Size Packing (m) Voltage

2x2,5 N

Nominal diameter of complete cable (mm) 12
Nominal weight of cable (kg/km) 200
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 144
In final installation, cable (cm) 101
During handling and installation, cable (cm) 12
In final installation, cable (cm) 10
Pulling force
Pulling-eye (kN) 0.08
Pulling-stocking (kN) 0.1
Resistance 20 °C (ohm/km) 7.41
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.36
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301739
Reka code 1146543
Nominal diameter of complete cable (mm) 12
Nominal weight of cable (kg/km) 200
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 144
In final installation, cable (cm) 101
During handling and installation, cable (cm) 12
In final installation, cable (cm) 10
Pulling force
Pulling-eye (kN) 0.08
Pulling-stocking (kN) 0.1
Resistance 20 °C (ohm/km) 7.41
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.36
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301746
Reka code 1146543

2x4 N

Electric number Size Packing (m) Voltage

2x4 N

Nominal diameter of complete cable (mm) 13
Nominal weight of cable (kg/km) 254
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 156
In final installation, cable (cm) 109
During handling and installation, cable (cm) 13
In final installation, cable (cm) 11
Pulling force
Pulling-eye (kN) 0.12
Pulling-stocking (kN) 0.16
Resistance 20 °C (ohm/km) 4.61
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.57
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301760
Reka code 1146544

2x6 N

Electric number Size Packing (m) Voltage

2x6 N

Nominal diameter of complete cable (mm) 14
Nominal weight of cable (kg/km) 339
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 168
In final installation, cable (cm) 118
During handling and installation, cable (cm) 14
In final installation, cable (cm) 12
Pulling force
Pulling-eye (kN) 0.18
Pulling-stocking (kN) 0.24
Resistance 20 °C (ohm/km) 3.08
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.86
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301784
Reka code 1146545

3G1,5

Electric number Size Packing (m) Voltage

3G1,5

Nominal diameter of complete cable (mm) 11
Nominal weight of cable (kg/km) 181
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 132
In final installation, cable (cm) 92
During handling and installation, cable (cm) 11
In final installation, cable (cm) 9
Pulling force
Pulling-eye (kN) 0.07
Pulling-stocking (kN) 0.09
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.21
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301869
Reka code 1146547
Nominal diameter of complete cable (mm) 11
Nominal weight of cable (kg/km) 181
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 132
In final installation, cable (cm) 92
During handling and installation, cable (cm) 11
In final installation, cable (cm) 9
Pulling force
Pulling-eye (kN) 0.07
Pulling-stocking (kN) 0.09
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.21
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301876
Reka code 1146547
Nominal diameter of complete cable (mm) 11
Nominal weight of cable (kg/km) 181
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 132
In final installation, cable (cm) 92
During handling and installation, cable (cm) 11
In final installation, cable (cm) 9
Pulling force
Pulling-eye (kN) 0.07
Pulling-stocking (kN) 0.09
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.21
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301852
Reka code 1146547

3G2,5

Electric number Size Packing (m) Voltage

3G2,5

Nominal diameter of complete cable (mm) 12
Nominal weight of cable (kg/km) 223
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 144
In final installation, cable (cm) 101
During handling and installation, cable (cm) 12
In final installation, cable (cm) 10
Pulling force
Pulling-eye (kN) 0.11
Pulling-stocking (kN) 0.15
Resistance 20 °C (ohm/km) 7.41
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.36
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301913
Reka code 1146548
Nominal diameter of complete cable (mm) 12
Nominal weight of cable (kg/km) 223
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 144
In final installation, cable (cm) 101
During handling and installation, cable (cm) 12
In final installation, cable (cm) 10
Pulling force
Pulling-eye (kN) 0.11
Pulling-stocking (kN) 0.15
Resistance 20 °C (ohm/km) 7.41
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.36
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301906
Reka code 1146548
Nominal diameter of complete cable (mm) 12
Nominal weight of cable (kg/km) 223
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 144
In final installation, cable (cm) 101
During handling and installation, cable (cm) 12
In final installation, cable (cm) 10
Pulling force
Pulling-eye (kN) 0.11
Pulling-stocking (kN) 0.15
Resistance 20 °C (ohm/km) 7.41
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.36
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301890
Reka code 1146548

3x1,5

Electric number Size Packing (m) Voltage

3x1,5

Nominal diameter of complete cable (mm) 11
Nominal weight of cable (kg/km) 181
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 132
In final installation, cable (cm) 92
During handling and installation, cable (cm) 11
In final installation, cable (cm) 9
Pulling force
Pulling-eye (kN) 0.07
Pulling-stocking (kN) 0.09
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.21
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301814
Reka code 1146546
Nominal diameter of complete cable (mm) 11
Nominal weight of cable (kg/km) 181
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 132
In final installation, cable (cm) 92
During handling and installation, cable (cm) 11
In final installation, cable (cm) 9
Pulling force
Pulling-eye (kN) 0.07
Pulling-stocking (kN) 0.09
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.21
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301821
Reka code 1146546

3G4

Electric number Size Packing (m) Voltage

3G4

Nominal diameter of complete cable (mm) 13
Nominal weight of cable (kg/km) 291
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 156
In final installation, cable (cm) 109
During handling and installation, cable (cm) 13
In final installation, cable (cm) 11
Pulling force
Pulling-eye (kN) 0.18
Pulling-stocking (kN) 0.24
Resistance 20 °C (ohm/km) 4.61
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.57
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301920
Reka code 1146549

3G6

Electric number Size Packing (m) Voltage

3G6

Nominal diameter of complete cable (mm) 15
Nominal weight of cable (kg/km) 391
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 180
In final installation, cable (cm) 126
During handling and installation, cable (cm) 15
In final installation, cable (cm) 13
Pulling force
Pulling-eye (kN) 0.27
Pulling-stocking (kN) 0.36
Resistance 20 °C (ohm/km) 3.08
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.86
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301944
Reka code 1146550

3G10

Electric number Size Packing (m) Voltage

3G10

Nominal diameter of complete cable (mm) 17
Nominal weight of cable (kg/km) 541
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 204
In final installation, cable (cm) 143
During handling and installation, cable (cm) 17
In final installation, cable (cm) 14
Pulling force
Pulling-eye (kN) 0.45
Pulling-stocking (kN) 0.6
Resistance 20 °C (ohm/km) 1.83
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 1.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301968
Reka code 1146551

3G16

Electric number Size Packing (m) Voltage

3G16

Nominal diameter of complete cable (mm) 19
Nominal weight of cable (kg/km) 758
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 228
In final installation, cable (cm) 160
During handling and installation, cable (cm) 19
In final installation, cable (cm) 16
Pulling force
Pulling-eye (kN) 0.72
Pulling-stocking (kN) 0.96
Resistance 20 °C (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 2.3
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176301982
Reka code 1146552

3G25

Electric number Size Packing (m) Voltage

3G25

Nominal diameter of complete cable (mm) 24
Nominal weight of cable (kg/km) 1172
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 288
In final installation, cable (cm) 202
During handling and installation, cable (cm) 24
In final installation, cable (cm) 20
Pulling force
Pulling-eye (kN) 1.13
Pulling-stocking (kN) 1.5
Resistance 20 °C (ohm/km) 0.727
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 3.6
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176302002
Reka code 1146553

3G35

Electric number Size Packing (m) Voltage

3G35

Nominal diameter of complete cable (mm) 25
Nominal weight of cable (kg/km) 1514
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 300
In final installation, cable (cm) 210
During handling and installation, cable (cm) 25
In final installation, cable (cm) 21
Pulling force
Pulling-eye (kN) 1.58
Pulling-stocking (kN) 2.1
Resistance 20 °C (ohm/km) 0.524
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 5
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176302026
Reka code 1146554

3G50

Electric number Size Packing (m) Voltage

3G50

Nominal diameter of complete cable (mm) 29
Nominal weight of cable (kg/km) 1993
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 348
In final installation, cable (cm) 244
During handling and installation, cable (cm) 29
In final installation, cable (cm) 24
Pulling force
Pulling-eye (kN) 2.25
Pulling-stocking (kN) 3
Resistance 20 °C (ohm/km) 0.387
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 7.2
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176302040
Reka code 1146555

4G1,5

Electric number Size Packing (m) Voltage

4G1,5

Nominal diameter of complete cable (mm) 12
Nominal weight of cable (kg/km) 213
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 144
In final installation, cable (cm) 101
During handling and installation, cable (cm) 12
In final installation, cable (cm) 10
Pulling force
Pulling-eye (kN) 0.09
Pulling-stocking (kN) 0.12
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.21
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176302071
Reka code 1146558
Nominal diameter of complete cable (mm) 12
Nominal weight of cable (kg/km) 213
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 144
In final installation, cable (cm) 101
During handling and installation, cable (cm) 12
In final installation, cable (cm) 10
Pulling force
Pulling-eye (kN) 0.09
Pulling-stocking (kN) 0.12
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.21
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176302088
Reka code 1146558

4G2,5

Electric number Size Packing (m) Voltage

4G2,5

Nominal diameter of complete cable (mm) 13
Nominal weight of cable (kg/km) 266
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 156
In final installation, cable (cm) 109
During handling and installation, cable (cm) 13
In final installation, cable (cm) 11
Pulling force
Pulling-eye (kN) 0.15
Pulling-stocking (kN) 0.2
Resistance 20 °C (ohm/km) 7.41
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.36
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176302125
Reka code 1146559
Nominal diameter of complete cable (mm) 13
Nominal weight of cable (kg/km) 266
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 156
In final installation, cable (cm) 109
During handling and installation, cable (cm) 13
In final installation, cable (cm) 11
Pulling force
Pulling-eye (kN) 0.15
Pulling-stocking (kN) 0.2
Resistance 20 °C (ohm/km) 7.41
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.36
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176302118
Reka code 1146559

4G4

Electric number Size Packing (m) Voltage

4G4

Nominal diameter of complete cable (mm) 14
Nominal weight of cable (kg/km) 351
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 168
In final installation, cable (cm) 118
During handling and installation, cable (cm) 14
In final installation, cable (cm) 12
Pulling force
Pulling-eye (kN) 0.24
Pulling-stocking (kN) 0.32
Resistance 20 °C (ohm/km) 4.61
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.57
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176302149
Reka code 1146560

4G6

Electric number Size Packing (m) Voltage

4G6

Nominal diameter of complete cable (mm) 16
Nominal weight of cable (kg/km) 473
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 192
In final installation, cable (cm) 134
During handling and installation, cable (cm) 16
In final installation, cable (cm) 13
Pulling force
Pulling-eye (kN) 0.36
Pulling-stocking (kN) 0.48
Resistance 20 °C (ohm/km) 3.08
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.86
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176302163
Reka code 1146561

4G10

Electric number Size Packing (m) Voltage

4G10

Nominal diameter of complete cable (mm) 18
Nominal weight of cable (kg/km) 673
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 216
In final installation, cable (cm) 151
During handling and installation, cable (cm) 18
In final installation, cable (cm) 15
Pulling force
Pulling-eye (kN) 0.6
Pulling-stocking (kN) 0.8
Resistance 20 °C (ohm/km) 1.83
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 1.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176302187
Reka code 1146562

4G16

Electric number Size Packing (m) Voltage

4G16

Nominal diameter of complete cable (mm) 21
Nominal weight of cable (kg/km) 949
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 252
In final installation, cable (cm) 176
During handling and installation, cable (cm) 21
In final installation, cable (cm) 18
Pulling force
Pulling-eye (kN) 0.96
Pulling-stocking (kN) 1.28
Resistance 20 °C (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 2.3
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176302200
Reka code 1146563

4G25

Electric number Size Packing (m) Voltage

4G25

Nominal diameter of complete cable (mm) 26
Nominal weight of cable (kg/km) 1489
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 312
In final installation, cable (cm) 218
During handling and installation, cable (cm) 26
In final installation, cable (cm) 22
Pulling force
Pulling-eye (kN) 1.5
Pulling-stocking (kN) 2
Resistance 20 °C (ohm/km) 0.727
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 3.6
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176302224
Reka code 1146564

4G35

Electric number Size Packing (m) Voltage

4G35

Nominal diameter of complete cable (mm) 27
Nominal weight of cable (kg/km) 1854
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 324
In final installation, cable (cm) 227
During handling and installation, cable (cm) 27
In final installation, cable (cm) 23
Pulling force
Pulling-eye (kN) 2.1
Pulling-stocking (kN) 2.8
Resistance 20 °C (ohm/km) 0.524
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 5
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176302248
Reka code 1146565

4G50

Electric number Size Packing (m) Voltage

4G50

Nominal diameter of complete cable (mm) 31
Nominal weight of cable (kg/km) 2472
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 372
In final installation, cable (cm) 260
During handling and installation, cable (cm) 31
In final installation, cable (cm) 26
Pulling force
Pulling-eye (kN) 3
Pulling-stocking (kN) 4
Resistance 20 °C (ohm/km) 0.387
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 7.2
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176302262
Reka code 1146566

5G1,5

Electric number Size Packing (m) Voltage

5G1,5

Nominal diameter of complete cable (mm) 13
Nominal weight of cable (kg/km) 244
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 156
In final installation, cable (cm) 109
During handling and installation, cable (cm) 13
In final installation, cable (cm) 11
Pulling force
Pulling-eye (kN) 0.11
Pulling-stocking (kN) 0.15
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.21
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176302316
Reka code 1146569
Nominal diameter of complete cable (mm) 13
Nominal weight of cable (kg/km) 244
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 156
In final installation, cable (cm) 109
During handling and installation, cable (cm) 13
In final installation, cable (cm) 11
Pulling force
Pulling-eye (kN) 0.11
Pulling-stocking (kN) 0.15
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.21
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176302309
Reka code 1146569
Nominal diameter of complete cable (mm) 13
Nominal weight of cable (kg/km) 244
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 156
In final installation, cable (cm) 109
During handling and installation, cable (cm) 13
In final installation, cable (cm) 11
Pulling force
Pulling-eye (kN) 0.11
Pulling-stocking (kN) 0.15
Resistance 20 °C (ohm/km) 12.1
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.21
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176302293
Reka code 1146569

5G2,5

Electric number Size Packing (m) Voltage

5G2,5

Nominal diameter of complete cable (mm) 14
Nominal weight of cable (kg/km) 314
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 168
In final installation, cable (cm) 118
During handling and installation, cable (cm) 14
In final installation, cable (cm) 12
Pulling force
Pulling-eye (kN) 0.19
Pulling-stocking (kN) 0.25
Resistance 20 °C (ohm/km) 7.41
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.36
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176302354
Reka code 1146570
Nominal diameter of complete cable (mm) 14
Nominal weight of cable (kg/km) 314
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 168
In final installation, cable (cm) 118
During handling and installation, cable (cm) 14
In final installation, cable (cm) 12
Pulling force
Pulling-eye (kN) 0.19
Pulling-stocking (kN) 0.25
Resistance 20 °C (ohm/km) 7.41
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.36
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176302323
Reka code 1146570
Nominal diameter of complete cable (mm) 14
Nominal weight of cable (kg/km) 314
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 168
In final installation, cable (cm) 118
During handling and installation, cable (cm) 14
In final installation, cable (cm) 12
Pulling force
Pulling-eye (kN) 0.19
Pulling-stocking (kN) 0.25
Resistance 20 °C (ohm/km) 7.41
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.36
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176302347
Reka code 1146570

5G4

Electric number Size Packing (m) Voltage

5G4

Nominal diameter of complete cable (mm) 15
Nominal weight of cable (kg/km) 417
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 180
In final installation, cable (cm) 126
During handling and installation, cable (cm) 15
In final installation, cable (cm) 13
Pulling force
Pulling-eye (kN) 0.3
Pulling-stocking (kN) 0.4
Resistance 20 °C (ohm/km) 4.61
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.57
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176302361
Reka code 1146571

5G6

Electric number Size Packing (m) Voltage

5G6

Nominal diameter of complete cable (mm) 18
Nominal weight of cable (kg/km) 568
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 216
In final installation, cable (cm) 151
During handling and installation, cable (cm) 18
In final installation, cable (cm) 15
Pulling force
Pulling-eye (kN) 0.45
Pulling-stocking (kN) 0.6
Resistance 20 °C (ohm/km) 3.08
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.86
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176302385
Reka code 1146572

5G10

Electric number Size Packing (m) Voltage

5G10

Nominal diameter of complete cable (mm) 20
Nominal weight of cable (kg/km) 807
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 240
In final installation, cable (cm) 168
During handling and installation, cable (cm) 20
In final installation, cable (cm) 17
Pulling force
Pulling-eye (kN) 0.75
Pulling-stocking (kN) 1
Resistance 20 °C (ohm/km) 1.83
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 1.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176302408
Reka code 1146573

5G16

Electric number Size Packing (m) Voltage

5G16

Nominal diameter of complete cable (mm) 23
Nominal weight of cable (kg/km) 1156
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 276
In final installation, cable (cm) 193
During handling and installation, cable (cm) 23
In final installation, cable (cm) 19
Pulling force
Pulling-eye (kN) 1.2
Pulling-stocking (kN) 1.6
Resistance 20 °C (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 2.3
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176302422
Reka code 1146574

5G25

Electric number Size Packing (m) Voltage

5G25

Nominal diameter of complete cable (mm) 29
Nominal weight of cable (kg/km) 1850
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 348
In final installation, cable (cm) 244
During handling and installation, cable (cm) 29
In final installation, cable (cm) 24
Pulling force
Pulling-eye (kN) 1.88
Pulling-stocking (kN) 2.5
Resistance 20 °C (ohm/km) 0.727
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 3.6
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176302446
Reka code 1146575

5G35

Electric number Size Packing (m) Voltage

5G35

Nominal diameter of complete cable (mm) 31
Nominal weight of cable (kg/km) 2321
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 372
In final installation, cable (cm) 260
During handling and installation, cable (cm) 31
In final installation, cable (cm) 26
Pulling force
Pulling-eye (kN) 2.63
Pulling-stocking (kN) 3.5
Resistance 20 °C (ohm/km) 0.524
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 5
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176302460
Reka code 1146576

5G50

Electric number Size Packing (m) Voltage

5G50

Nominal diameter of complete cable (mm) 35
Nominal weight of cable (kg/km) 3137
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Bending radius
During handling and installation, cable (cm) 420
In final installation, cable (cm) 294
During handling and installation, cable (cm) 35
In final installation, cable (cm) 29
Pulling force
Pulling-eye (kN) 3.75
Pulling-stocking (kN) 5
Resistance 20 °C (ohm/km) 0.387
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 7.2
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176302484
Reka code 1146577