FRHF-EMC

For fixed installations indoors and outdoors. Can be buried into ground. For installations where circuit integrity is required in case of fire. Halogen free and flame retardant. EMC-protected, suitable for connection between frequency converter and motor on variable speed drive systems.

Standards SFS 5547, HD 604 S1:1994/A3:2005 Part 5 Section I
Conductor 1,5...6 mm² circular solid copper, EN/IEC 60228 class 1
10…25 mm² circular stranded copper, EN/IEC 60228 class 2
35…240 mm² sector shaped stranded copper, EN/IEC 60228 class 2
Insulation Halogen free XLPE, mica tape
Core Identification (all color combinations in the cable family) blue, brown
brown, black, grey
blue, brown, black, grey
Separation sheath Halogen-free filling compound
Metal screen EMC-copper foil and copper wires
Oversheath UV-protected, halogen free polyolefin compound
Colour of the oversheath orange

2x1,5/1,5

Electric number Size Packing (m) Voltage

2x1,5/1,5

Nominal diameter of complete cable (mm) 12
Nominal weight of cable (kg/km) 205
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 1.5
Bending radius
During handling and installation, cable (cm) 144
In final installation, cable (cm) 101
During handling and installation, cable (cm) 12
In final installation, cable (cm) 10
Pulling force
Pulling-eye (kN) 0.05
Pulling-stocking (kN) 0.06
Resistance 20 °C (ohm/km) 12.1
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 12.1
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.21
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176009338
Reka code 1146620

2x2,5/2,5

Electric number Size Packing (m) Voltage

2x2,5/2,5

Nominal diameter of complete cable (mm) 13
Nominal weight of cable (kg/km) 251
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 2.5
Bending radius
During handling and installation, cable (cm) 156
In final installation, cable (cm) 109
During handling and installation, cable (cm) 13
In final installation, cable (cm) 11
Pulling force
Pulling-eye (kN) 0.08
Pulling-stocking (kN) 0.1
Resistance 20 °C (ohm/km) 7.41
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 7.41
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.36
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176009352
Reka code 1146621

2x4/4

Electric number Size Packing (m) Voltage

2x4/4

Nominal diameter of complete cable (mm) 15
Nominal weight of cable (kg/km) 340
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 4
Bending radius
During handling and installation, cable (cm) 180
In final installation, cable (cm) 126
During handling and installation, cable (cm) 15
In final installation, cable (cm) 13
Pulling force
Pulling-eye (kN) 0.12
Pulling-stocking (kN) 0.16
Resistance 20 °C (ohm/km) 4.61
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 4.61
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.57
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176009376
Reka code 1146622

2x6/6

Electric number Size Packing (m) Voltage

2x6/6

Nominal diameter of complete cable (mm) 16
Nominal weight of cable (kg/km) 444
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 6
Bending radius
During handling and installation, cable (cm) 192
In final installation, cable (cm) 134
During handling and installation, cable (cm) 16
In final installation, cable (cm) 13
Pulling force
Pulling-eye (kN) 0.18
Pulling-stocking (kN) 0.24
Resistance 20 °C (ohm/km) 3.08
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 3.08
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.86
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176009383
Reka code 1146623

2x10/10

Electric number Size Packing (m) Voltage

2x10/10

Nominal diameter of complete cable (mm) 19
Nominal weight of cable (kg/km) 636
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 10
Bending radius
During handling and installation, cable (cm) 228
In final installation, cable (cm) 160
During handling and installation, cable (cm) 19
In final installation, cable (cm) 16
Pulling force
Pulling-eye (kN) 0.3
Pulling-stocking (kN) 0.4
Resistance 20 °C (ohm/km) 1.83
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.83
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 1.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176009390
Reka code 1146624

2x16/16

Electric number Size Packing (m) Voltage

2x16/16

Nominal diameter of complete cable (mm) 21
Nominal weight of cable (kg/km) 877
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 252
In final installation, cable (cm) 176
During handling and installation, cable (cm) 21
In final installation, cable (cm) 18
Pulling force
Pulling-eye (kN) 0.48
Pulling-stocking (kN) 0.64
Resistance 20 °C (ohm/km) 1.15
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 2.3
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176009406
Reka code 1146625

3x1,5/1,5

Electric number Size Packing (m) Voltage

3x1,5/1,5

Nominal diameter of complete cable (mm) 13
Nominal weight of cable (kg/km) 229
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 1.5
Bending radius
During handling and installation, cable (cm) 156
In final installation, cable (cm) 109
During handling and installation, cable (cm) 13
In final installation, cable (cm) 11
Pulling force
Pulling-eye (kN) 0.07
Pulling-stocking (kN) 0.09
Resistance 20 °C (ohm/km) 12.1
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 12.1
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.21
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176009413
Reka code 1146630

3x2,5/2,5

Electric number Size Packing (m) Voltage

3x2,5/2,5

Nominal diameter of complete cable (mm) 14
Nominal weight of cable (kg/km) 283
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 2.5
Bending radius
During handling and installation, cable (cm) 168
In final installation, cable (cm) 118
During handling and installation, cable (cm) 14
In final installation, cable (cm) 12
Pulling force
Pulling-eye (kN) 0.11
Pulling-stocking (kN) 0.15
Resistance 20 °C (ohm/km) 7.41
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 7.41
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.36
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176009437
Reka code 1146631

3x4/4

Electric number Size Packing (m) Voltage

3x4/4

Nominal diameter of complete cable (mm) 16
Nominal weight of cable (kg/km) 395
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 4
Bending radius
During handling and installation, cable (cm) 192
In final installation, cable (cm) 134
During handling and installation, cable (cm) 16
In final installation, cable (cm) 13
Pulling force
Pulling-eye (kN) 0.18
Pulling-stocking (kN) 0.24
Resistance 20 °C (ohm/km) 4.61
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 4.61
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.57
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176009451
Reka code 1146632

3x6/6

Electric number Size Packing (m) Voltage

3x6/6

Nominal diameter of complete cable (mm) 17
Nominal weight of cable (kg/km) 501
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 6
Bending radius
During handling and installation, cable (cm) 204
In final installation, cable (cm) 143
During handling and installation, cable (cm) 17
In final installation, cable (cm) 14
Pulling force
Pulling-eye (kN) 0.27
Pulling-stocking (kN) 0.36
Resistance 20 °C (ohm/km) 3.08
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 3.08
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.86
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176009468
Reka code 1146633

3x10/10

Electric number Size Packing (m) Voltage

3x10/10

Nominal diameter of complete cable (mm) 20
Nominal weight of cable (kg/km) 720
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 10
Bending radius
During handling and installation, cable (cm) 240
In final installation, cable (cm) 168
During handling and installation, cable (cm) 20
In final installation, cable (cm) 17
Pulling force
Pulling-eye (kN) 0.45
Pulling-stocking (kN) 0.6
Resistance 20 °C (ohm/km) 1.83
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.83
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 1.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176009475
Reka code 1146634

3x25/16

Electric number Size Packing (m) Voltage

3x25/16

Nominal diameter of complete cable (mm) 26
Nominal weight of cable (kg/km) 1427
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 312
In final installation, cable (cm) 218
During handling and installation, cable (cm) 26
In final installation, cable (cm) 22
Pulling force
Pulling-eye (kN) 1.13
Pulling-stocking (kN) 1.5
Resistance 20 °C (ohm/km) 0.727
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 3.6
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176009499
Reka code 1146636

3x35/16

Electric number Size Packing (m) Voltage

3x35/16

Nominal diameter of complete cable (mm) 26
Nominal weight of cable (kg/km) 1534
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 312
In final installation, cable (cm) 218
During handling and installation, cable (cm) 26
In final installation, cable (cm) 22
Pulling force
Pulling-eye (kN) 1.58
Pulling-stocking (kN) 2.1
Resistance 20 °C (ohm/km) 0.524
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 5
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176009505
Reka code 1146637

3x50/25

Electric number Size Packing (m) Voltage

3x50/25

Nominal diameter of complete cable (mm) 30
Nominal weight of cable (kg/km) 2149
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 25
Bending radius
During handling and installation, cable (cm) 360
In final installation, cable (cm) 252
During handling and installation, cable (cm) 30
In final installation, cable (cm) 25
Pulling force
Pulling-eye (kN) 2.25
Pulling-stocking (kN) 3
Resistance 20 °C (ohm/km) 0.387
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.727
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 7.2
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176009512
Reka code 1146638

3x70/35

Electric number Size Packing (m) Voltage

3x70/35

Nominal diameter of complete cable (mm) 34
Nominal weight of cable (kg/km) 2976
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 35
Bending radius
During handling and installation, cable (cm) 408
In final installation, cable (cm) 286
During handling and installation, cable (cm) 34
In final installation, cable (cm) 29
Pulling force
Pulling-eye (kN) 3.15
Pulling-stocking (kN) 4.2
Resistance 20 °C (ohm/km) 0.268
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.524
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 10
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176009529
Reka code 1146639

3x95/50

Electric number Size Packing (m) Voltage

3x95/50

Nominal diameter of complete cable (mm) 37
Nominal weight of cable (kg/km) 3732
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 50
Bending radius
During handling and installation, cable (cm) 444
In final installation, cable (cm) 311
During handling and installation, cable (cm) 37
In final installation, cable (cm) 31
Pulling force
Pulling-eye (kN) 4.28
Pulling-stocking (kN) 5.7
Resistance 20 °C (ohm/km) 0.193
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.387
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 13.6
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176009536
Reka code 1146640

3x120/70

Electric number Size Packing (m) Voltage

3x120/70

Nominal diameter of complete cable (mm) 40
Nominal weight of cable (kg/km) 4734
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 70
Bending radius
During handling and installation, cable (cm) 480
In final installation, cable (cm) 336
During handling and installation, cable (cm) 40
In final installation, cable (cm) 34
Pulling force
Pulling-eye (kN) 5.4
Pulling-stocking (kN) 7.2
Resistance 20 °C (ohm/km) 0.153
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.268
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 17.2
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176009543
Reka code 1146641

3x185/95

Electric number Size Packing (m) Voltage

3x185/95

Nominal diameter of complete cable (mm) 50
Nominal weight of cable (kg/km) 7244
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 95
Bending radius
During handling and installation, cable (cm) 600
In final installation, cable (cm) 420
During handling and installation, cable (cm) 50
In final installation, cable (cm) 42
Pulling force
Pulling-eye (kN) 8.32
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.0991
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.193
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 26.5
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176009567
Reka code 1146643

4x1,5/1,5

Electric number Size Packing (m) Voltage

4x1,5/1,5

Nominal diameter of complete cable (mm) 14
Nominal weight of cable (kg/km) 284
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 1.5
Bending radius
During handling and installation, cable (cm) 168
In final installation, cable (cm) 118
During handling and installation, cable (cm) 14
In final installation, cable (cm) 12
Pulling force
Pulling-eye (kN) 0.09
Pulling-stocking (kN) 0.12
Resistance 20 °C (ohm/km) 12.1
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 12.1
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.21
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6410006534012
Reka code 1146660

4x2,5/2,5

Electric number Size Packing (m) Voltage

4x2,5/2,5

Nominal diameter of complete cable (mm) 15
Nominal weight of cable (kg/km) 351
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 2.5
Bending radius
During handling and installation, cable (cm) 180
In final installation, cable (cm) 126
During handling and installation, cable (cm) 15
In final installation, cable (cm) 13
Pulling force
Pulling-eye (kN) 0.15
Pulling-stocking (kN) 0.2
Resistance 20 °C (ohm/km) 7.41
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 7.41
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.36
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6410006534029
Reka code 1146661

4x4/4

Electric number Size Packing (m) Voltage

4x4/4

Nominal diameter of complete cable (mm) 17
Nominal weight of cable (kg/km) 458
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 4
Bending radius
During handling and installation, cable (cm) 204
In final installation, cable (cm) 143
During handling and installation, cable (cm) 17
In final installation, cable (cm) 14
Pulling force
Pulling-eye (kN) 0.24
Pulling-stocking (kN) 0.32
Resistance 20 °C (ohm/km) 4.61
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 4.61
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.57
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176009628
Reka code 1146662

4x6/6

Electric number Size Packing (m) Voltage

4x6/6

Nominal diameter of complete cable (mm) 18
Nominal weight of cable (kg/km) 586
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 6
Bending radius
During handling and installation, cable (cm) 216
In final installation, cable (cm) 151
During handling and installation, cable (cm) 18
In final installation, cable (cm) 15
Pulling force
Pulling-eye (kN) 0.36
Pulling-stocking (kN) 0.48
Resistance 20 °C (ohm/km) 3.08
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 3.08
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 0.86
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6410006534067
Reka code 1146663

4x10/10

Electric number Size Packing (m) Voltage

4x10/10

Nominal diameter of complete cable (mm) 21
Nominal weight of cable (kg/km) 849
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 10
Bending radius
During handling and installation, cable (cm) 252
In final installation, cable (cm) 176
During handling and installation, cable (cm) 21
In final installation, cable (cm) 18
Pulling force
Pulling-eye (kN) 0.6
Pulling-stocking (kN) 0.8
Resistance 20 °C (ohm/km) 1.83
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.83
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 1.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6410006534104
Reka code 1146664

4x16/16

Electric number Size Packing (m) Voltage

4x16/16

Nominal diameter of complete cable (mm) 24
Nominal weight of cable (kg/km) 1193
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 288
In final installation, cable (cm) 202
During handling and installation, cable (cm) 24
In final installation, cable (cm) 20
Pulling force
Pulling-eye (kN) 0.96
Pulling-stocking (kN) 1.28
Resistance 20 °C (ohm/km) 1.15
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 2.3
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6410006022274
Reka code 1146676

4x25/16

Electric number Size Packing (m) Voltage

4x25/16

Nominal diameter of complete cable (mm) 29
Nominal weight of cable (kg/km) 1722
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 348
In final installation, cable (cm) 244
During handling and installation, cable (cm) 29
In final installation, cable (cm) 24
Pulling force
Pulling-eye (kN) 1.5
Pulling-stocking (kN) 2
Resistance 20 °C (ohm/km) 0.727
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 3.6
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6410006022281
Reka code 1146666

4x35/16

Electric number Size Packing (m) Voltage

4x35/16

Nominal diameter of complete cable (mm) 29
Nominal weight of cable (kg/km) 1940
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 348
In final installation, cable (cm) 244
During handling and installation, cable (cm) 29
In final installation, cable (cm) 24
Pulling force
Pulling-eye (kN) 2.1
Pulling-stocking (kN) 2.8
Resistance 20 °C (ohm/km) 0.524
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 5
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6410006022298
Reka code 1146667
Nominal diameter of complete cable (mm) 29
Nominal weight of cable (kg/km) 1940
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 348
In final installation, cable (cm) 244
During handling and installation, cable (cm) 29
In final installation, cable (cm) 24
Pulling force
Pulling-eye (kN) 2.1
Pulling-stocking (kN) 2.8
Resistance 20 °C (ohm/km) 0.524
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 5
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6410006022007
Reka code 1146667

4x50/25

Electric number Size Packing (m) Voltage

4x50/25

Nominal diameter of complete cable (mm) 33
Nominal weight of cable (kg/km) 2623
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 25
Bending radius
During handling and installation, cable (cm) 396
In final installation, cable (cm) 277
During handling and installation, cable (cm) 33
In final installation, cable (cm) 28
Pulling force
Pulling-eye (kN) 3
Pulling-stocking (kN) 4
Resistance 20 °C (ohm/km) 0.387
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.727
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 7.2
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6410006022304
Reka code 1146668

4x70/35

Electric number Size Packing (m) Voltage

4x70/35

Nominal diameter of complete cable (mm) 35
Nominal weight of cable (kg/km) 3533
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 35
Bending radius
During handling and installation, cable (cm) 420
In final installation, cable (cm) 294
During handling and installation, cable (cm) 35
In final installation, cable (cm) 29
Pulling force
Pulling-eye (kN) 4.2
Pulling-stocking (kN) 5.6
Resistance 20 °C (ohm/km) 0.268
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.524
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 10
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6410006022311
Reka code 1146669

4x95/50

Electric number Size Packing (m) Voltage

4x95/50

Nominal diameter of complete cable (mm) 41
Nominal weight of cable (kg/km) 4707
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 50
Bending radius
During handling and installation, cable (cm) 492
In final installation, cable (cm) 344
During handling and installation, cable (cm) 41
In final installation, cable (cm) 34
Pulling force
Pulling-eye (kN) 5.7
Pulling-stocking (kN) 7.6
Resistance 20 °C (ohm/km) 0.193
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.387
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 13.6
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6410006022328
Reka code 1146670

4x120/70

Electric number Size Packing (m) Voltage

4x120/70

Nominal diameter of complete cable (mm) 44
Nominal weight of cable (kg/km) 5893
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 70
Bending radius
During handling and installation, cable (cm) 528
In final installation, cable (cm) 370
During handling and installation, cable (cm) 44
In final installation, cable (cm) 37
Pulling force
Pulling-eye (kN) 7.2
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.153
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.268
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 17.2
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6410006022335
Reka code 1146671

4x150/70

Electric number Size Packing (m) Voltage

4x150/70

Nominal diameter of complete cable (mm) 48
Nominal weight of cable (kg/km) 7117
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 70
Bending radius
During handling and installation, cable (cm) 576
In final installation, cable (cm) 403
During handling and installation, cable (cm) 48
In final installation, cable (cm) 40
Pulling force
Pulling-eye (kN) 9
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.124
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.268
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 21.5
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6410006022342
Reka code 1146672

4x185/95

Electric number Size Packing (m) Voltage

4x185/95

Nominal diameter of complete cable (mm) 56
Nominal weight of cable (kg/km) 9197
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 95
Bending radius
During handling and installation, cable (cm) 672
In final installation, cable (cm) 470
During handling and installation, cable (cm) 56
In final installation, cable (cm) 47
Pulling force
Pulling-eye (kN) 11.1
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.0991
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.193
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 26.5
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6410006022359
Reka code 1146673

4x240/120

Electric number Size Packing (m) Voltage

4x240/120

Nominal diameter of complete cable (mm) 62
Nominal weight of cable (kg/km) 11787
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 120
Bending radius
During handling and installation, cable (cm) 744
In final installation, cable (cm) 521
During handling and installation, cable (cm) 62
In final installation, cable (cm) 52
Pulling force
Pulling-eye (kN) 14.4
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.0754
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.153
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 34.3
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176009741
Reka code 1146674
Nominal diameter of complete cable (mm) 62
Nominal weight of cable (kg/km) 11787
Conductor material Copper
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 120
Bending radius
During handling and installation, cable (cm) 744
In final installation, cable (cm) 521
During handling and installation, cable (cm) 62
In final installation, cable (cm) 52
Pulling force
Pulling-eye (kN) 14.4
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.0754
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.153
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 34.3
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6410006022366
Reka code 1146674