AXQJ

For fixed installations indoors and oudoors. Direct burial in soil is allowed, as long as the relevant national rules of installations are followed. Where needed halogen free, non corrosive gases and low smoke density cables. Self extinquishing, no after-burning.

Standards SFS 5546:2020, SS 424 14 18:2007, HD 604 S1:1994/A3:2005 Part 5 Section I and D, IEC 60502-1:2004
Reaction to fire Dca-s2,d2,a2
CPR - DoP 2021013_DOP.pdf
Conductor 25 mm² circular stranded aluminium, EN/IEC 60228 class 2
35…300 mm² sector shaped, stranded aluminium, EN/IEC 60228 class 2
Insulation Halogen free XLPE
Core Identification (all color combinations in the cable family) brown, black, grey
blue, brown, black, grey
Inner covering plastic tape
Metal screen Copper wires and copper tape
Oversheath UV-protected halogen free polyolefin compound
Colour of the oversheath Black

3x25/16

Electric number Size Packing (m) Voltage

3x25/16

Nominal diameter of complete cable (mm) 22
Nominal weight of cable (kg/km) 591
Conductor material Aluminum
Nominal diameter of conductor (mm) 1094
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 0.9
Nominal diameter over the insulation without insulation screen (mm) 3010
Nominal diameter over the screen (mm) 3017
Nominal size of metal screen (mm2) 16
Nominal thickness of aluminium laminated foil (mm) 3012
Nominal diameter of messenger (mm) 3019
Nominal diameter of earth conductor (mm) 1082
Nominal diameter of a sheathed phase conductor (mm) 3021
Nominal thickness of semi-conducting layer (mm) 3025
Bending radius
During handling and installation, cable (cm) 267
In final installation, cable (cm) 187
During handling and installation, phase conductor (cm) 3028
In final installation, phase conductor (cm) 3029
During handling and installation, phase conductor (cm) 1070
During handling and installation, cable (cm) 27
In final installation, phase conductor (cm) 1071
In final installation, cable (cm) 19
During handling and installation, phase conductor (m) 3027
During handling and installation, cable (m) 0.27
In final installation, phase conductor (m) 3026
In final installation, cable (m) 0.19
Pulling force
Pulling-eye (kN) 1.1
Pulling-stocking (kN) 1.1
Resistance 20 °C (ohm/km) 1.2
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.83
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 2.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
Metal screen (initial temperature 60 °C, final temperature 250 °C) (°C) 1054
EAN code 6438176114124
Reka code 1256512

3x35/16

Electric number Size Packing (m) Voltage

3x35/16

Nominal diameter of complete cable (mm) 22
Nominal weight of cable (kg/km) 678
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 0.9
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 266
In final installation, cable (cm) 186
During handling and installation, cable (cm) 27
In final installation, cable (cm) 19
During handling and installation, cable (m) 0.27
In final installation, cable (m) 0.19
Pulling force
Pulling-eye (kN) 1.6
Pulling-stocking (kN) 1.6
Resistance 20 °C (ohm/km) 0.868
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 3.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176114148
Reka code 1256513
Nominal diameter of complete cable (mm) 22
Nominal weight of cable (kg/km) 678
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 0.9
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 266
In final installation, cable (cm) 186
During handling and installation, cable (cm) 27
In final installation, cable (cm) 19
During handling and installation, cable (m) 0.27
In final installation, cable (m) 0.19
Pulling force
Pulling-eye (kN) 1.6
Pulling-stocking (kN) 1.6
Resistance 20 °C (ohm/km) 0.868
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 3.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176114155
Reka code 1256513

3x50/16

Electric number Size Packing (m) Voltage

3x50/16

Nominal diameter of complete cable (mm) 24
Nominal weight of cable (kg/km) 817
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 1
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 285
In final installation, cable (cm) 200
During handling and installation, cable (cm) 29
In final installation, cable (cm) 20
During handling and installation, cable (m) 0.29
In final installation, cable (m) 0.2
Pulling force
Pulling-eye (kN) 2.3
Pulling-stocking (kN) 2.3
Resistance 20 °C (ohm/km) 0.641
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 4.8
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176114179
Reka code 1256514
Nominal diameter of complete cable (mm) 24
Nominal weight of cable (kg/km) 817
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 1
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 285
In final installation, cable (cm) 200
During handling and installation, cable (cm) 29
In final installation, cable (cm) 20
During handling and installation, cable (m) 0.29
In final installation, cable (m) 0.2
Pulling force
Pulling-eye (kN) 2.3
Pulling-stocking (kN) 2.3
Resistance 20 °C (ohm/km) 0.641
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 4.8
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176114162
Reka code 1256514

3x70/21

Electric number Size Packing (m) Voltage

3x70/21

Nominal diameter of complete cable (mm) 28
Nominal weight of cable (kg/km) 1127
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 1.1
Nominal size of metal screen (mm2) 21
Bending radius
During handling and installation, cable (cm) 332
In final installation, cable (cm) 232
During handling and installation, cable (cm) 33
In final installation, cable (cm) 23
During handling and installation, cable (m) 0.33
In final installation, cable (m) 0.23
Pulling force
Pulling-eye (kN) 3.2
Pulling-stocking (kN) 3.2
Resistance 20 °C (ohm/km) 0.443
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.868
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 6.7
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176114193
Reka code 1256515
Nominal diameter of complete cable (mm) 28
Nominal weight of cable (kg/km) 1127
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 1.1
Nominal size of metal screen (mm2) 21
Bending radius
During handling and installation, cable (cm) 332
In final installation, cable (cm) 232
During handling and installation, cable (cm) 33
In final installation, cable (cm) 23
During handling and installation, cable (m) 0.33
In final installation, cable (m) 0.23
Pulling force
Pulling-eye (kN) 3.2
Pulling-stocking (kN) 3.2
Resistance 20 °C (ohm/km) 0.443
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.868
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 6.7
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176114186
Reka code 1256515

3x95/29

Electric number Size Packing (m) Voltage

3x95/29

Nominal diameter of complete cable (mm) 32
Nominal weight of cable (kg/km) 1480
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 1.1
Nominal size of metal screen (mm2) 29
Bending radius
During handling and installation, cable (cm) 385
In final installation, cable (cm) 270
During handling and installation, cable (cm) 39
In final installation, cable (cm) 27
During handling and installation, cable (m) 0.39
In final installation, cable (m) 0.27
Pulling force
Pulling-eye (kN) 4.3
Pulling-stocking (kN) 4.3
Resistance 20 °C (ohm/km) 0.32
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.641
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 9
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176114209
Reka code 1256516

3x120/41

Electric number Size Packing (m) Voltage

3x120/41

Nominal diameter of complete cable (mm) 36
Nominal weight of cable (kg/km) 1898
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 1.2
Nominal size of metal screen (mm2) 41
Bending radius
During handling and installation, cable (cm) 433
In final installation, cable (cm) 303
During handling and installation, cable (cm) 43
In final installation, cable (cm) 30
During handling and installation, cable (m) 0.43
In final installation, cable (m) 0.3
Pulling force
Pulling-eye (kN) 5.4
Pulling-stocking (kN) 5.4
Resistance 20 °C (ohm/km) 0.253
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.443
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 11.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176114223
Reka code 1256517

3x150/41

Electric number Size Packing (m) Voltage

3x150/41

Nominal diameter of complete cable (mm) 40
Nominal weight of cable (kg/km) 2223
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 1.4
Nominal size of metal screen (mm2) 41
Bending radius
During handling and installation, cable (cm) 475
In final installation, cable (cm) 332
During handling and installation, cable (cm) 47
In final installation, cable (cm) 33
During handling and installation, cable (m) 0.47
In final installation, cable (m) 0.33
Pulling force
Pulling-eye (kN) 6.8
Pulling-stocking (kN) 6.8
Resistance 20 °C (ohm/km) 0.206
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.443
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 14.2
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176114247
Reka code 1256518

3x185/57

Electric number Size Packing (m) Voltage

3x185/57

Nominal diameter of complete cable (mm) 45
Nominal weight of cable (kg/km) 2794
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 1.6
Nominal size of metal screen (mm2) 57
Bending radius
During handling and installation, cable (cm) 538
In final installation, cable (cm) 377
During handling and installation, cable (cm) 54
In final installation, cable (cm) 38
During handling and installation, cable (m) 0.54
In final installation, cable (m) 0.38
Pulling force
Pulling-eye (kN) 8.3
Pulling-stocking (kN) 8.3
Resistance 20 °C (ohm/km) 0.164
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.32
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 17.5
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176114261
Reka code 1256519

3x240/72

Electric number Size Packing (m) Voltage

3x240/72

Nominal diameter of complete cable (mm) 48
Nominal weight of cable (kg/km) 3563
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 2.7
Nominal size of metal screen (mm2) 72
Bending radius
During handling and installation, cable (cm) 581
In final installation, cable (cm) 407
During handling and installation, cable (cm) 58
In final installation, cable (cm) 41
During handling and installation, cable (m) 0.58
In final installation, cable (m) 0.41
Pulling force
Pulling-eye (kN) 10.8
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.125
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.253
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 22.6
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176114285
Reka code 1256520

3x300/88

Electric number Size Packing (m) Voltage

3x300/88

Nominal diameter of complete cable (mm) 56
Nominal weight of cable (kg/km) 4424
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 1.8
Nominal size of metal screen (mm2) 88
Bending radius
During handling and installation, cable (cm) 673
In final installation, cable (cm) 471
During handling and installation, cable (cm) 67
In final installation, cable (cm) 47
During handling and installation, cable (m) 0.67
In final installation, cable (m) 0.47
Pulling force
Pulling-eye (kN) 13.5
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.1
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.206
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 28.2
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176114308
Reka code 1256521

4x25/16

Electric number Size Packing (m) Voltage

4x25/16

Nominal diameter of complete cable (mm) 24
Nominal weight of cable (kg/km) 695
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 0.9
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 291
In final installation, cable (cm) 203
During handling and installation, cable (cm) 29
In final installation, cable (cm) 20
During handling and installation, cable (m) 0.29
In final installation, cable (m) 0.2
Pulling force
Pulling-eye (kN) 1.5
Pulling-stocking (kN) 1.5
Resistance 20 °C (ohm/km) 1.2
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 2.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176114407
Reka code 1256523
Nominal diameter of complete cable (mm) 24
Nominal weight of cable (kg/km) 695
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 0.9
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 291
In final installation, cable (cm) 203
During handling and installation, cable (cm) 29
In final installation, cable (cm) 20
During handling and installation, cable (m) 0.29
In final installation, cable (m) 0.2
Pulling force
Pulling-eye (kN) 1.5
Pulling-stocking (kN) 1.5
Resistance 20 °C (ohm/km) 1.2
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 2.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176114414
Reka code 1256523

4x35/16

Electric number Size Packing (m) Voltage

4x35/16

Nominal diameter of complete cable (mm) 24
Nominal weight of cable (kg/km) 811
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 0.9
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 291
In final installation, cable (cm) 204
During handling and installation, cable (cm) 29
In final installation, cable (cm) 20
During handling and installation, cable (m) 0.29
In final installation, cable (m) 0.2
Pulling force
Pulling-eye (kN) 2.1
Pulling-stocking (kN) 2.1
Resistance 20 °C (ohm/km) 0.868
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 3.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176114438
Reka code 1256524
Nominal diameter of complete cable (mm) 24
Nominal weight of cable (kg/km) 811
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 0.9
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 291
In final installation, cable (cm) 204
During handling and installation, cable (cm) 29
In final installation, cable (cm) 20
During handling and installation, cable (m) 0.29
In final installation, cable (m) 0.2
Pulling force
Pulling-eye (kN) 2.1
Pulling-stocking (kN) 2.1
Resistance 20 °C (ohm/km) 0.868
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 3.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176114421
Reka code 1256524

4x50/16

Electric number Size Packing (m) Voltage

4x50/16

Nominal diameter of complete cable (mm) 28
Nominal weight of cable (kg/km) 1025
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 1
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 337
In final installation, cable (cm) 236
During handling and installation, cable (cm) 34
In final installation, cable (cm) 24
During handling and installation, cable (m) 0.34
In final installation, cable (m) 0.24
Pulling force
Pulling-eye (kN) 3
Pulling-stocking (kN) 3
Resistance 20 °C (ohm/km) 0.641
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 4.8
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176114445
Reka code 1256525
Nominal diameter of complete cable (mm) 28
Nominal weight of cable (kg/km) 1025
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 1
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 337
In final installation, cable (cm) 236
During handling and installation, cable (cm) 34
In final installation, cable (cm) 24
During handling and installation, cable (m) 0.34
In final installation, cable (m) 0.24
Pulling force
Pulling-eye (kN) 3
Pulling-stocking (kN) 3
Resistance 20 °C (ohm/km) 0.641
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 4.8
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176114452
Reka code 1256525

4x70/21

Electric number Size Packing (m) Voltage

4x70/21

Nominal diameter of complete cable (mm) 31
Nominal weight of cable (kg/km) 1394
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 1.1
Nominal size of metal screen (mm2) 21
Bending radius
During handling and installation, cable (cm) 378
In final installation, cable (cm) 264
During handling and installation, cable (cm) 38
In final installation, cable (cm) 26
During handling and installation, cable (m) 0.38
In final installation, cable (m) 0.26
Pulling force
Pulling-eye (kN) 4.2
Pulling-stocking (kN) 4.2
Resistance 20 °C (ohm/km) 0.443
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.868
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 6.7
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176114476
Reka code 1256526

4x95/29

Electric number Size Packing (m) Voltage

4x95/29

Nominal diameter of complete cable (mm) 35
Nominal weight of cable (kg/km) 1816
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 1.1
Nominal size of metal screen (mm2) 29
Bending radius
During handling and installation, cable (cm) 425
In final installation, cable (cm) 298
During handling and installation, cable (cm) 43
In final installation, cable (cm) 30
During handling and installation, cable (m) 0.43
In final installation, cable (m) 0.3
Pulling force
Pulling-eye (kN) 5.7
Pulling-stocking (kN) 5.7
Resistance 20 °C (ohm/km) 0.32
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.641
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 9
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176114483
Reka code 1256527

4x120/41

Electric number Size Packing (m) Voltage

4x120/41

Nominal diameter of complete cable (mm) 41
Nominal weight of cable (kg/km) 2341
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 1.2
Nominal size of metal screen (mm2) 41
Bending radius
During handling and installation, cable (cm) 489
In final installation, cable (cm) 342
During handling and installation, cable (cm) 49
In final installation, cable (cm) 34
During handling and installation, cable (m) 0.49
In final installation, cable (m) 0.34
Pulling force
Pulling-eye (kN) 7.2
Pulling-stocking (kN) 7.2
Resistance 20 °C (ohm/km) 0.253
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.443
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 11.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176114506
Reka code 1256528

4x150/41

Electric number Size Packing (m) Voltage

4x150/41

Nominal diameter of complete cable (mm) 45
Nominal weight of cable (kg/km) 2791
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 1.4
Nominal size of metal screen (mm2) 41
Bending radius
During handling and installation, cable (cm) 540
In final installation, cable (cm) 378
During handling and installation, cable (cm) 54
In final installation, cable (cm) 38
During handling and installation, cable (m) 0.54
In final installation, cable (m) 0.38
Pulling force
Pulling-eye (kN) 9
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.206
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.443
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 14.2
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176114520
Reka code 1256529

4x185/57

Electric number Size Packing (m) Voltage

4x185/57

Nominal diameter of complete cable (mm) 50
Nominal weight of cable (kg/km) 3456
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 1.6
Nominal size of metal screen (mm2) 57
Bending radius
During handling and installation, cable (cm) 597
In final installation, cable (cm) 418
During handling and installation, cable (cm) 60
In final installation, cable (cm) 42
During handling and installation, cable (m) 0.6
In final installation, cable (m) 0.42
Pulling force
Pulling-eye (kN) 11.1
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.164
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.32
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 17.5
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176114544
Reka code 1256530

4x240/72

Electric number Size Packing (m) Voltage

4x240/72

Nominal diameter of complete cable (mm) 57
Nominal weight of cable (kg/km) 4495
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 2.7
Nominal size of metal screen (mm2) 72
Bending radius
During handling and installation, cable (cm) 679
In final installation, cable (cm) 475
During handling and installation, cable (cm) 68
In final installation, cable (cm) 48
During handling and installation, cable (m) 0.68
In final installation, cable (m) 0.48
Pulling force
Pulling-eye (kN) 14.4
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.125
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.253
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 22.6
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176114568
Reka code 1256531

4x300/88

Electric number Size Packing (m) Voltage

4x300/88

Nominal diameter of complete cable (mm) 60
Nominal weight of cable (kg/km) 5425
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 1.8
Nominal size of metal screen (mm2) 88
Bending radius
During handling and installation, cable (cm) 724
In final installation, cable (cm) 507
During handling and installation, cable (cm) 72
In final installation, cable (cm) 51
During handling and installation, cable (m) 0.72
In final installation, cable (m) 0.51
Pulling force
Pulling-eye (kN) 18
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.1
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.206
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 28.2
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176012550
Reka code 1256532
Nominal diameter of complete cable (mm) 60
Nominal weight of cable (kg/km) 5425
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 1.8
Nominal size of metal screen (mm2) 88
Bending radius
During handling and installation, cable (cm) 724
In final installation, cable (cm) 507
During handling and installation, cable (cm) 72
In final installation, cable (cm) 51
During handling and installation, cable (m) 0.72
In final installation, cable (m) 0.51
Pulling force
Pulling-eye (kN) 18
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.1
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.206
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 28.2
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176114582