AXLJ-F TT

For fixed installations outdoors. Cable is both longitudinally and radially watertight and therefore suitable for extremely wet conditions. It may be buried directly into soil. Not for submarine or similar applications.

Standards HD 620 S2:2010 Part 10 Section M; SS 424 14 16
Conductor Watertight, circular, stranded aluminium, EN/IEC 60228 class 2
Insulation Conductor screen, semiconducting XLPE,
Insulation XLPE,
Insulation screen, semiconducting XLPE
Colour of the oversheath Black

1x150/25

Electric number Size Packaging Voltage

1x150/25

Nominal diameter of complete cable mm 38
Nominal weight of cable kg/km 1360
Conductor material Aluminum
Nominal diameter of conductor mm 13.9
Nominal cross-sectional area of conductor mm2 150
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 29.5
Nominal size of metal screen mm2 25
Nominal thickness of aluminium laminated foil mm 0.2
Bending radius
During handling and installation, cable mm 570
In final installation, cable mm 399
During handling and installation, phase conductor mm 0.62
In final installation, phase conductor mm 0.43
During handling and installation, cable cm 57
In final installation, cable cm 40
During handling and installation, cable m 0.57
In final installation, cable m 0.4
Pulling force
Pulling-eye kN 7.5
Pulling-stocking kN 2.3
Resistance 20 °C Ω/km 0.206
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0.727
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176217498
Reka code 1186376

1x240/35

Electric number Size Packaging Voltage

1x240/35

Nominal diameter of complete cable mm 43
Nominal weight of cable kg/km 1829
Conductor material Aluminum
Nominal diameter of conductor mm 18
Nominal cross-sectional area of conductor mm2 240
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 33.6
Nominal size of metal screen mm2 35
Nominal thickness of aluminium laminated foil mm 0.2
Bending radius
During handling and installation, cable mm 645
In final installation, cable mm 452
During handling and installation, phase conductor mm 0.69
In final installation, phase conductor mm 0.48
During handling and installation, cable cm 65
In final installation, cable cm 45
During handling and installation, cable m 0.65
In final installation, cable m 0.45
Pulling force
Pulling-eye kN 12
Pulling-stocking kN 3.6
Resistance 20 °C Ω/km 0.125
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0.524
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176217559
Reka code 1186238

1x400/35

Electric number Size Packaging Voltage

1x400/35

Nominal diameter of complete cable mm 48
Nominal weight of cable kg/km 2319
Conductor material Aluminum
Nominal diameter of conductor mm 22.4
Nominal cross-sectional area of conductor mm2 400
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 38
Nominal size of metal screen mm2 35
Nominal thickness of aluminium laminated foil mm 0.2
Bending radius
During handling and installation, cable mm 720
In final installation, cable mm 504
During handling and installation, phase conductor mm 0.74
In final installation, phase conductor mm 0.51
During handling and installation, cable cm 72
In final installation, cable cm 50
During handling and installation, cable m 0.72
In final installation, cable m 0.5
Pulling force
Pulling-eye kN 20
Pulling-stocking kN 6
Resistance 20 °C Ω/km 0.0778
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0.524
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176217634
Reka code 1186380

1x500/35

Electric number Size Packaging Voltage

1x500/35

Nominal diameter of complete cable mm 51
Nominal weight of cable kg/km 2797
Conductor material Aluminum
Nominal diameter of conductor mm 25.7
Nominal cross-sectional area of conductor mm2 500
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 41.3
Nominal size of metal screen mm2 35
Nominal thickness of aluminium laminated foil mm 0.2
Bending radius
During handling and installation, cable mm 765
In final installation, cable mm 536
During handling and installation, phase conductor mm 0.81
In final installation, phase conductor mm 0.57
During handling and installation, cable cm 77
In final installation, cable cm 54
During handling and installation, cable m 0.77
In final installation, cable m 0.54
Pulling force
Pulling-eye kN 20
Pulling-stocking kN 7.5
Resistance 20 °C Ω/km 0.0605
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0.524
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176217672
Reka code 1186699

1x630/35

Electric number Size Packaging Voltage

1x630/35

Nominal diameter of complete cable mm 55
Nominal weight of cable kg/km 3360
Conductor material Aluminum
Nominal diameter of conductor mm 29.3
Nominal cross-sectional area of conductor mm2 630
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 45.1
Nominal size of metal screen mm2 35
Nominal thickness of aluminium laminated foil mm 0.2
Bending radius
During handling and installation, cable mm 825
In final installation, cable mm 578
During handling and installation, phase conductor mm 0.84
In final installation, phase conductor mm 0.62
During handling and installation, cable cm 83
In final installation, cable cm 58
During handling and installation, cable m 0.83
In final installation, cable m 0.58
Pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0.0469
Maximum d.c. resistance at 20 °C, metal screen Ω/km 0.524
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176217696
Reka code 1186672