AXLJ-F / AHXCMK-WTC/PE 12/20 (24) kV 3-core


Medium-voltage cable for fixed installations outdoors. May be buried directly in soil. Installations must be in accordance with national regulations and rules of installations. The cable is halogen-free, but without fire protection. The cable is not CPR-classified.
Standards | HD 620 10 M & F, SS 424 14 16, SFS 5636 |
---|---|
Conductor | Watertight, circular, stranded aluminium, EN/IEC 60228 class 2 |
Conductor screen | Semiconducting cross-linked polyethylene XLPE |
Insulation | Cross-linked polyethylene XLPE |
Insulation screen | Semiconducting cross-linked polyethylene XLPE |
Core Identification (all color combinations in the cable family) | White phase numbering: L1, L2, L3 |
Inner covering | Semiconducting tape |
Metal screen | Layer of helically wound copper wires with a counter helix copper tape |
Oversheath | PE-plastic PELLD |
Colour of the oversheath | Black |
3x50/16
Electric number
Size
Packaging
Voltage
3x50/16
Nominal diameter of complete cable mm
51
Nominal weight of cable kg/km
1725
Conductor material
Aluminium
Nominal diameter of conductor mm
8
Nominal cross-sectional area of conductor mm2
50
Nominal thickness of insulation mm
5.5
Nominal diameter over the insulation without insulation screen mm
19.3
Number of wires
3
Nominal size of metal screen mm2
16
Min. bending radius
During handling and installation, cable cm
61
In final installation, cable cm
43
During handling and installation, cable m
0.61
In final installation, cable m
0.43
Max. pulling force
Pulling-eye kN
7.5
Pulling-stocking kN
2.3
Resistance 20 °C Ω/km
0,641
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,2
Minimum cable temperature during transport °C
-40
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6438176205570
Reka code
1187773
3x70/16
Electric number
Size
Packaging
Voltage
3x70/16
Nominal diameter of complete cable mm
55
Nominal weight of cable kg/km
1995
Conductor material
Aluminium
Nominal diameter of conductor mm
9.5
Nominal cross-sectional area of conductor mm2
70
Nominal thickness of insulation mm
5.5
Nominal diameter over the insulation without insulation screen mm
20.7
Number of wires
3
Nominal size of metal screen mm2
16
Min. bending radius
During handling and installation, cable cm
66
In final installation, cable cm
46
During handling and installation, cable m
0.66
In final installation, cable m
0.46
Max. pulling force
Pulling-eye kN
10.5
Pulling-stocking kN
3.2
Resistance 20 °C Ω/km
0,443
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,2
Minimum cable temperature during transport °C
-40
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006224401
Reka code
1187774
3x95/16
Electric number
Size
Packaging
Voltage
3x95/16
Nominal diameter of complete cable mm
59
Nominal weight of cable kg/km
2345
Conductor material
Aluminium
Nominal diameter of conductor mm
11.1
Nominal cross-sectional area of conductor mm2
95
Nominal thickness of insulation mm
5.5
Nominal diameter over the insulation without insulation screen mm
22.4
Number of wires
3
Nominal size of metal screen mm2
16
Min. bending radius
During handling and installation, cable cm
71
In final installation, cable cm
50
During handling and installation, cable m
0.71
In final installation, cable m
0.5
Max. pulling force
Pulling-eye kN
14.3
Pulling-stocking kN
4.3
Resistance 20 °C Ω/km
0,320
Maximum d.c. resistance at 20 °C, metal screen Ω/km
1,2
Minimum cable temperature during transport °C
-40
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006224470
Reka code
1187585
3x120/25
Electric number
Size
Packaging
Voltage
3x120/25
Nominal diameter of complete cable mm
62
Nominal weight of cable kg/km
2763
Conductor material
Aluminium
Nominal diameter of conductor mm
12.6
Nominal cross-sectional area of conductor mm2
120
Nominal thickness of insulation mm
5.5
Nominal diameter over the insulation without insulation screen mm
23.8
Number of wires
3
Nominal size of metal screen mm2
25
Min. bending radius
During handling and installation, cable cm
74
In final installation, cable cm
52
During handling and installation, cable m
0.74
In final installation, cable m
0.52
Max. pulling force
Pulling-eye kN
18
Pulling-stocking kN
5.4
Resistance 20 °C Ω/km
0,253
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,8
Minimum cable temperature during transport °C
-40
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006224425
Reka code
1187776
3x150/25
Electric number
Size
Packaging
Voltage
3x150/25
Nominal diameter of complete cable mm
65
Nominal weight of cable kg/km
3107
Conductor material
Aluminium
Nominal diameter of conductor mm
13.9
Nominal cross-sectional area of conductor mm2
150
Nominal thickness of insulation mm
5.5
Nominal diameter over the insulation without insulation screen mm
25.3
Number of wires
3
Nominal size of metal screen mm2
25
Min. bending radius
During handling and installation, cable cm
78
In final installation, cable cm
55
During handling and installation, cable m
0.78
In final installation, cable m
0.55
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
6.8
Resistance 20 °C Ω/km
0,206
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,8
Minimum cable temperature during transport °C
-40
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006224432
Reka code
1187777
3x240/25
Electric number
Size
Packaging
Voltage
3x240/25
Nominal diameter of complete cable mm
74
Nominal weight of cable kg/km
4245
Conductor material
Aluminium
Nominal diameter of conductor mm
18
Nominal cross-sectional area of conductor mm2
240
Nominal thickness of insulation mm
5.5
Nominal diameter over the insulation without insulation screen mm
29.2
Number of wires
3
Nominal size of metal screen mm2
25
Min. bending radius
During handling and installation, cable cm
89
In final installation, cable cm
62
During handling and installation, cable m
0.89
In final installation, cable m
0.62
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,125
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,8
Minimum cable temperature during transport °C
-40
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006224463
Reka code
1187589
3x300/35
Electric number
Size
Packaging
Voltage
3x300/35
Nominal diameter of complete cable mm
80
Nominal weight of cable kg/km
5066
Conductor material
Aluminium
Nominal diameter of conductor mm
19.8
Nominal cross-sectional area of conductor mm2
300
Nominal thickness of insulation mm
5.5
Nominal diameter over the insulation without insulation screen mm
31.5
Number of wires
3
Nominal size of metal screen mm2
35
Min. bending radius
During handling and installation, cable cm
96
In final installation, cable cm
67
During handling and installation, cable m
0.96
In final installation, cable m
0.67
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,100
Maximum d.c. resistance at 20 °C, metal screen Ω/km
0,6
Minimum cable temperature during transport °C
-40
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006224494
Reka code