AXCMK-HF C

For fixed installations indoors and oudoors. Direct burial in soil is allowed, as long as the relevant national rules of installations are followed. Where needed halogen free, non corrosive gases and low smoke density cables. Self extinquishing, no after-burning.

Standards SFS 5546:2020, SS 424 14 18:2007, HD 604 S1:1994/A3:2005 Part 5 Section I and D, IEC 60502-1:2004
Reaction to fire Cca-s1,d1,a1
CPR - DoP 2018011_DOP.pdf
Conductor 25 mm² circular stranded aluminium, EN/IEC 60228 class 2
35…300 mm² sector shaped, stranded aluminium, EN/IEC 60228 class 2
Insulation Halogen free XLPE
Core Identification (all color combinations in the cable family) brown, black, grey
blue, brown, black, grey
Inner covering plastic tape
Metal screen Copper wires and copper tape
Oversheath UV-protected halogen free polyolefin compound
Colour of the oversheath Black

3x35/16

Electric number Size Packing (m) Voltage

3x35/16

Nominal diameter of complete cable (mm) 22
Nominal weight of cable (kg/km) 682
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 266
In final installation, cable (cm) 186
During handling and installation, cable (cm) 27
In final installation, cable (cm) 19
During handling and installation, cable (m) 0.27
In final installation, cable (m) 0.19
Pulling force
Pulling-eye (kN) 1.6
Pulling-stocking (kN) 1.6
Resistance 20 °C (ohm/km) 0.868
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 3.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300756
Reka code 1149242
Nominal diameter of complete cable (mm) 22
Nominal weight of cable (kg/km) 682
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 266
In final installation, cable (cm) 186
During handling and installation, cable (cm) 27
In final installation, cable (cm) 19
During handling and installation, cable (m) 0.27
In final installation, cable (m) 0.19
Pulling force
Pulling-eye (kN) 1.6
Pulling-stocking (kN) 1.6
Resistance 20 °C (ohm/km) 0.868
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 3.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300749
Reka code 1149242

3x50/16

Electric number Size Packing (m) Voltage

3x50/16

Nominal diameter of complete cable (mm) 24
Nominal weight of cable (kg/km) 821
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 285
In final installation, cable (cm) 200
During handling and installation, cable (cm) 29
In final installation, cable (cm) 20
During handling and installation, cable (m) 0.29
In final installation, cable (m) 0.2
Pulling force
Pulling-eye (kN) 2.3
Pulling-stocking (kN) 2.3
Resistance 20 °C (ohm/km) 0.641
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 4.8
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300770
Reka code 1149243
Nominal diameter of complete cable (mm) 24
Nominal weight of cable (kg/km) 821
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 285
In final installation, cable (cm) 200
During handling and installation, cable (cm) 29
In final installation, cable (cm) 20
During handling and installation, cable (m) 0.29
In final installation, cable (m) 0.2
Pulling force
Pulling-eye (kN) 2.3
Pulling-stocking (kN) 2.3
Resistance 20 °C (ohm/km) 0.641
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 4.8
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300763
Reka code 1149243

3x70/21

Electric number Size Packing (m) Voltage

3x70/21

Nominal diameter of complete cable (mm) 28
Nominal weight of cable (kg/km) 1133
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 21
Bending radius
During handling and installation, cable (cm) 332
In final installation, cable (cm) 232
During handling and installation, cable (cm) 33
In final installation, cable (cm) 23
During handling and installation, cable (m) 0.33
In final installation, cable (m) 0.23
Pulling force
Pulling-eye (kN) 3.2
Pulling-stocking (kN) 3.2
Resistance 20 °C (ohm/km) 0.443
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.868
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 6.7
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300794
Reka code 1149244
Nominal diameter of complete cable (mm) 28
Nominal weight of cable (kg/km) 1133
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 21
Bending radius
During handling and installation, cable (cm) 332
In final installation, cable (cm) 232
During handling and installation, cable (cm) 33
In final installation, cable (cm) 23
During handling and installation, cable (m) 0.33
In final installation, cable (m) 0.23
Pulling force
Pulling-eye (kN) 3.2
Pulling-stocking (kN) 3.2
Resistance 20 °C (ohm/km) 0.443
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.868
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 6.7
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300787
Reka code 1149244

3x95/29

Electric number Size Packing (m) Voltage

3x95/29

Nominal diameter of complete cable (mm) 32
Nominal weight of cable (kg/km) 1474
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 29
Bending radius
During handling and installation, cable (cm) 385
In final installation, cable (cm) 270
During handling and installation, cable (cm) 39
In final installation, cable (cm) 27
During handling and installation, cable (m) 0.39
In final installation, cable (m) 0.27
Pulling force
Pulling-eye (kN) 4.3
Pulling-stocking (kN) 4.3
Resistance 20 °C (ohm/km) 0.32
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.641
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 9
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300800
Reka code 1149245

3x120/41

Electric number Size Packing (m) Voltage

3x120/41

Nominal diameter of complete cable (mm) 36
Nominal weight of cable (kg/km) 1907
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 41
Bending radius
During handling and installation, cable (cm) 433
In final installation, cable (cm) 303
During handling and installation, cable (cm) 43
In final installation, cable (cm) 30
During handling and installation, cable (m) 0.43
In final installation, cable (m) 0.3
Pulling force
Pulling-eye (kN) 5.4
Pulling-stocking (kN) 5.4
Resistance 20 °C (ohm/km) 0.253
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.443
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 11.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300817
Reka code 1149246

3x150/41

Electric number Size Packing (m) Voltage

3x150/41

Nominal diameter of complete cable (mm) 40
Nominal weight of cable (kg/km) 2215
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 41
Bending radius
During handling and installation, cable (cm) 475
In final installation, cable (cm) 332
During handling and installation, cable (cm) 47
In final installation, cable (cm) 33
During handling and installation, cable (m) 0.47
In final installation, cable (m) 0.33
Pulling force
Pulling-eye (kN) 6.8
Pulling-stocking (kN) 6.8
Resistance 20 °C (ohm/km) 0.206
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.443
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 14.2
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300824
Reka code 1149247

3x185/57

Electric number Size Packing (m) Voltage

3x185/57

Nominal diameter of complete cable (mm) 45
Nominal weight of cable (kg/km) 2765
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 57
Bending radius
During handling and installation, cable (cm) 538
In final installation, cable (cm) 377
During handling and installation, cable (cm) 54
In final installation, cable (cm) 38
During handling and installation, cable (m) 0.54
In final installation, cable (m) 0.38
Pulling force
Pulling-eye (kN) 8.3
Pulling-stocking (kN) 8.3
Resistance 20 °C (ohm/km) 0.164
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.32
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 17.5
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300831
Reka code 1149248

3x240/72

Electric number Size Packing (m) Voltage

3x240/72

Nominal diameter of complete cable (mm) 48
Nominal weight of cable (kg/km) 3562
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 72
Bending radius
During handling and installation, cable (cm) 581
In final installation, cable (cm) 407
During handling and installation, cable (cm) 58
In final installation, cable (cm) 41
During handling and installation, cable (m) 0.58
In final installation, cable (m) 0.41
Pulling force
Pulling-eye (kN) 10.8
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.125
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.253
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 22.6
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300848
Reka code 1149249

3x300/88

Electric number Size Packing (m) Voltage

3x300/88

Nominal diameter of complete cable (mm) 56
Nominal weight of cable (kg/km) 4364
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 88
Bending radius
During handling and installation, cable (cm) 673
In final installation, cable (cm) 471
During handling and installation, cable (cm) 67
In final installation, cable (cm) 47
During handling and installation, cable (m) 0.67
In final installation, cable (m) 0.47
Pulling force
Pulling-eye (kN) 13.5
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.1
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.206
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 28.2
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300855
Reka code 1149250

4x25/16

Electric number Size Packing (m) Voltage

4x25/16

Nominal diameter of complete cable (mm) 26
Nominal weight of cable (kg/km) 936
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 316
In final installation, cable (cm) 221
During handling and installation, cable (cm) 32
In final installation, cable (cm) 22
During handling and installation, cable (m) 0.32
In final installation, cable (m) 0.22
Pulling force
Pulling-eye (kN) 1.5
Pulling-stocking (kN) 1.5
Resistance 20 °C (ohm/km) 1.2
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 2.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300879
Reka code 1149253
Nominal diameter of complete cable (mm) 26
Nominal weight of cable (kg/km) 936
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 316
In final installation, cable (cm) 221
During handling and installation, cable (cm) 32
In final installation, cable (cm) 22
During handling and installation, cable (m) 0.32
In final installation, cable (m) 0.22
Pulling force
Pulling-eye (kN) 1.5
Pulling-stocking (kN) 1.5
Resistance 20 °C (ohm/km) 1.2
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 2.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300862
Reka code 1149253

4x35/16

Electric number Size Packing (m) Voltage

4x35/16

Nominal diameter of complete cable (mm) 24
Nominal weight of cable (kg/km) 816
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 291
In final installation, cable (cm) 204
During handling and installation, cable (cm) 29
In final installation, cable (cm) 20
During handling and installation, cable (m) 0.29
In final installation, cable (m) 0.2
Pulling force
Pulling-eye (kN) 2.1
Pulling-stocking (kN) 2.1
Resistance 20 °C (ohm/km) 0.868
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 3.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300886
Reka code 1149254
Nominal diameter of complete cable (mm) 24
Nominal weight of cable (kg/km) 816
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 291
In final installation, cable (cm) 204
During handling and installation, cable (cm) 29
In final installation, cable (cm) 20
During handling and installation, cable (m) 0.29
In final installation, cable (m) 0.2
Pulling force
Pulling-eye (kN) 2.1
Pulling-stocking (kN) 2.1
Resistance 20 °C (ohm/km) 0.868
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 3.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300893
Reka code 1149254

4x50/16

Electric number Size Packing (m) Voltage

4x50/16

Nominal diameter of complete cable (mm) 28
Nominal weight of cable (kg/km) 1030
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 337
In final installation, cable (cm) 236
During handling and installation, cable (cm) 34
In final installation, cable (cm) 24
During handling and installation, cable (m) 0.34
In final installation, cable (m) 0.24
Pulling force
Pulling-eye (kN) 3
Pulling-stocking (kN) 3
Resistance 20 °C (ohm/km) 0.641
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 4.8
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300916
Reka code 1149255
Nominal diameter of complete cable (mm) 28
Nominal weight of cable (kg/km) 1030
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 337
In final installation, cable (cm) 236
During handling and installation, cable (cm) 34
In final installation, cable (cm) 24
During handling and installation, cable (m) 0.34
In final installation, cable (m) 0.24
Pulling force
Pulling-eye (kN) 3
Pulling-stocking (kN) 3
Resistance 20 °C (ohm/km) 0.641
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 4.8
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300909
Reka code 1149255

4x70/21

Electric number Size Packing (m) Voltage

4x70/21

Nominal diameter of complete cable (mm) 31
Nominal weight of cable (kg/km) 1409
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 21
Bending radius
During handling and installation, cable (cm) 378
In final installation, cable (cm) 264
During handling and installation, cable (cm) 38
In final installation, cable (cm) 26
During handling and installation, cable (m) 0.38
In final installation, cable (m) 0.26
Pulling force
Pulling-eye (kN) 4.2
Pulling-stocking (kN) 4.2
Resistance 20 °C (ohm/km) 0.443
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.868
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 6.7
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300930
Reka code 1149256
Nominal diameter of complete cable (mm) 31
Nominal weight of cable (kg/km) 1409
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 21
Bending radius
During handling and installation, cable (cm) 378
In final installation, cable (cm) 264
During handling and installation, cable (cm) 38
In final installation, cable (cm) 26
During handling and installation, cable (m) 0.38
In final installation, cable (m) 0.26
Pulling force
Pulling-eye (kN) 4.2
Pulling-stocking (kN) 4.2
Resistance 20 °C (ohm/km) 0.443
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.868
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 6.7
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300923
Reka code 1149256

4x95/29

Electric number Size Packing (m) Voltage

4x95/29

Nominal diameter of complete cable (mm) 35
Nominal weight of cable (kg/km) 1825
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 29
Bending radius
During handling and installation, cable (cm) 425
In final installation, cable (cm) 298
During handling and installation, cable (cm) 43
In final installation, cable (cm) 30
During handling and installation, cable (m) 0.43
In final installation, cable (m) 0.3
Pulling force
Pulling-eye (kN) 5.7
Pulling-stocking (kN) 5.7
Resistance 20 °C (ohm/km) 0.32
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.641
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 9
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300947
Reka code 1149257

4x120/41

Electric number Size Packing (m) Voltage

4x120/41

Nominal diameter of complete cable (mm) 41
Nominal weight of cable (kg/km) 2344
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 41
Bending radius
During handling and installation, cable (cm) 489
In final installation, cable (cm) 342
During handling and installation, cable (cm) 49
In final installation, cable (cm) 34
During handling and installation, cable (m) 0.49
In final installation, cable (m) 0.34
Pulling force
Pulling-eye (kN) 7.2
Pulling-stocking (kN) 7.2
Resistance 20 °C (ohm/km) 0.253
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.443
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 11.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300954
Reka code 1149258

4x185/57

Electric number Size Packing (m) Voltage

4x185/57

Nominal diameter of complete cable (mm) 50
Nominal weight of cable (kg/km) 3471
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 57
Bending radius
During handling and installation, cable (cm) 597
In final installation, cable (cm) 418
During handling and installation, cable (cm) 60
In final installation, cable (cm) 42
During handling and installation, cable (m) 0.6
In final installation, cable (m) 0.42
Pulling force
Pulling-eye (kN) 11.1
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.164
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.32
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 17.5
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300978
Reka code 1149260

4x150/41

Electric number Size Packing (m) Voltage

4x150/41

Nominal diameter of complete cable (mm) 45
Nominal weight of cable (kg/km) 2802
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 41
Bending radius
During handling and installation, cable (cm) 540
In final installation, cable (cm) 378
During handling and installation, cable (cm) 54
In final installation, cable (cm) 38
During handling and installation, cable (m) 0.54
In final installation, cable (m) 0.38
Pulling force
Pulling-eye (kN) 9
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.206
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.443
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 14.2
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300961
Reka code 1149259

4x240/72

Electric number Size Packing (m) Voltage

4x240/72

Nominal diameter of complete cable (mm) 57
Nominal weight of cable (kg/km) 4514
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 72
Bending radius
During handling and installation, cable (cm) 679
In final installation, cable (cm) 475
During handling and installation, cable (cm) 68
In final installation, cable (cm) 48
During handling and installation, cable (m) 0.68
In final installation, cable (m) 0.48
Pulling force
Pulling-eye (kN) 14.4
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.125
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.253
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 22.6
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300985
Reka code 1149261

4x300/88

Electric number Size Packing (m) Voltage

4x300/88

Nominal diameter of complete cable (mm) 60
Nominal weight of cable (kg/km) 5447
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 88
Bending radius
During handling and installation, cable (cm) 724
In final installation, cable (cm) 507
During handling and installation, cable (cm) 72
In final installation, cable (cm) 51
During handling and installation, cable (m) 0.72
In final installation, cable (m) 0.51
Pulling force
Pulling-eye (kN) 18
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.1
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.206
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 28.2
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176300992
Reka code 1149262