AMCMK

For fixed installations indoors and oudoors. Direct burial in soil is allowed, as long as the relevant national rules of installations are followed.

Standards SFS 4880:2018, SS 424 14 18:2007, HD 603 S1:1994/A3:2007 Part 3 Section F and L
Reaction to fire Eca
CPR - DoP 2017081_DOP.pdf
Conductor 16 mm² circular solid aluminium, EN/IEC 60228 class 1
25 mm² circular stranded aluminium, EN/IEC 60228 class 2
35…300 mm² sector shaped, stranded aluminium, EN/IEC 60228 class 2
Insulation PVC-compound
Core Identification (all color combinations in the cable family) brown, black, grey
blue, brown, black, grey
Inner covering plastic tape
Metal screen Copper wires and copper tape
Oversheath UV-protected PVC-compound
Colour of the oversheath Black

3x16/10

Electric number Size Packing (m) Voltage

3x16/10

Nominal diameter of complete cable (mm) 19
Nominal weight of cable (kg/km) 439
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 10
Bending radius
During handling and installation, cable (cm) 230
In final installation, cable (cm) 161
During handling and installation, cable (cm) 23
In final installation, cable (cm) 16
During handling and installation, cable (m) 0.23
In final installation, cable (m) 0.16
Pulling force
Pulling-eye (kN) 0.7
Pulling-stocking (kN) 0.7
Resistance 20 °C (ohm/km) 1.91
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.83
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223572
Reka code 1111210
Nominal diameter of complete cable (mm) 19
Nominal weight of cable (kg/km) 439
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 10
Bending radius
During handling and installation, cable (cm) 230
In final installation, cable (cm) 161
During handling and installation, cable (cm) 23
In final installation, cable (cm) 16
During handling and installation, cable (m) 0.23
In final installation, cable (m) 0.16
Pulling force
Pulling-eye (kN) 0.7
Pulling-stocking (kN) 0.7
Resistance 20 °C (ohm/km) 1.91
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.83
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223473
Reka code 1111210

3x25/16

Electric number Size Packing (m) Voltage

3x25/16

Nominal diameter of complete cable (mm) 24
Nominal weight of cable (kg/km) 669
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 287
In final installation, cable (cm) 201
During handling and installation, cable (cm) 29
In final installation, cable (cm) 20
During handling and installation, cable (m) 0.29
In final installation, cable (m) 0.2
Pulling force
Pulling-eye (kN) 1.1
Pulling-stocking (kN) 1.1
Resistance 20 °C (ohm/km) 1.2
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223480
Reka code 1111231
Nominal diameter of complete cable (mm) 24
Nominal weight of cable (kg/km) 669
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 287
In final installation, cable (cm) 201
During handling and installation, cable (cm) 29
In final installation, cable (cm) 20
During handling and installation, cable (m) 0.29
In final installation, cable (m) 0.2
Pulling force
Pulling-eye (kN) 1.1
Pulling-stocking (kN) 1.1
Resistance 20 °C (ohm/km) 1.2
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223589
Reka code 1111231

3x35/16

Electric number Size Packing (m) Voltage

3x35/16

Nominal diameter of complete cable (mm) 24
Nominal weight of cable (kg/km) 763
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 284
In final installation, cable (cm) 198
During handling and installation, cable (cm) 28
In final installation, cable (cm) 20
During handling and installation, cable (m) 0.28
In final installation, cable (m) 0.2
Pulling force
Pulling-eye (kN) 1.6
Pulling-stocking (kN) 1.6
Resistance 20 °C (ohm/km) 0.868
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223596
Reka code 1111312
Nominal diameter of complete cable (mm) 24
Nominal weight of cable (kg/km) 763
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 284
In final installation, cable (cm) 198
During handling and installation, cable (cm) 28
In final installation, cable (cm) 20
During handling and installation, cable (m) 0.28
In final installation, cable (m) 0.2
Pulling force
Pulling-eye (kN) 1.6
Pulling-stocking (kN) 1.6
Resistance 20 °C (ohm/km) 0.868
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223497
Reka code 1111312

3x50/16

Electric number Size Packing (m) Voltage

3x50/16

Nominal diameter of complete cable (mm) 26
Nominal weight of cable (kg/km) 953
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 312
In final installation, cable (cm) 218
During handling and installation, cable (cm) 31
In final installation, cable (cm) 22
During handling and installation, cable (m) 0.31
In final installation, cable (m) 0.22
Pulling force
Pulling-eye (kN) 2.3
Pulling-stocking (kN) 2.3
Resistance 20 °C (ohm/km) 0.641
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223602
Reka code 1111313
Nominal diameter of complete cable (mm) 26
Nominal weight of cable (kg/km) 953
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 312
In final installation, cable (cm) 218
During handling and installation, cable (cm) 31
In final installation, cable (cm) 22
During handling and installation, cable (m) 0.31
In final installation, cable (m) 0.22
Pulling force
Pulling-eye (kN) 2.3
Pulling-stocking (kN) 2.3
Resistance 20 °C (ohm/km) 0.641
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223503
Reka code 1111313

3x70/21

Electric number Size Packing (m) Voltage

3x70/21

Nominal diameter of complete cable (mm) 29
Nominal weight of cable (kg/km) 1241
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 21
Bending radius
During handling and installation, cable (cm) 346
In final installation, cable (cm) 242
During handling and installation, cable (cm) 35
In final installation, cable (cm) 24
During handling and installation, cable (m) 0.35
In final installation, cable (m) 0.24
Pulling force
Pulling-eye (kN) 3.2
Pulling-stocking (kN) 3.2
Resistance 20 °C (ohm/km) 0.443
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.868
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223619
Reka code 1111314
Nominal diameter of complete cable (mm) 29
Nominal weight of cable (kg/km) 1241
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 21
Bending radius
During handling and installation, cable (cm) 346
In final installation, cable (cm) 242
During handling and installation, cable (cm) 35
In final installation, cable (cm) 24
During handling and installation, cable (m) 0.35
In final installation, cable (m) 0.24
Pulling force
Pulling-eye (kN) 3.2
Pulling-stocking (kN) 3.2
Resistance 20 °C (ohm/km) 0.443
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.868
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223510
Reka code 1111314

3x95/29

Electric number Size Packing (m) Voltage

3x95/29

Nominal diameter of complete cable (mm) 34
Nominal weight of cable (kg/km) 1683
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 29
Bending radius
During handling and installation, cable (cm) 411
In final installation, cable (cm) 288
During handling and installation, cable (cm) 41
In final installation, cable (cm) 29
During handling and installation, cable (m) 0.41
In final installation, cable (m) 0.29
Pulling force
Pulling-eye (kN) 4.3
Pulling-stocking (kN) 4.3
Resistance 20 °C (ohm/km) 0.32
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.641
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223626
Reka code 1111315
Nominal diameter of complete cable (mm) 34
Nominal weight of cable (kg/km) 1683
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 29
Bending radius
During handling and installation, cable (cm) 411
In final installation, cable (cm) 288
During handling and installation, cable (cm) 41
In final installation, cable (cm) 29
During handling and installation, cable (m) 0.41
In final installation, cable (m) 0.29
Pulling force
Pulling-eye (kN) 4.3
Pulling-stocking (kN) 4.3
Resistance 20 °C (ohm/km) 0.32
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.641
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223527
Reka code 1111315

3x120/41

Electric number Size Packing (m) Voltage

3x120/41

Nominal diameter of complete cable (mm) 38
Nominal weight of cable (kg/km) 2090
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 41
Bending radius
During handling and installation, cable (cm) 452
In final installation, cable (cm) 317
During handling and installation, cable (cm) 45
In final installation, cable (cm) 32
During handling and installation, cable (m) 0.45
In final installation, cable (m) 0.32
Pulling force
Pulling-eye (kN) 5.4
Pulling-stocking (kN) 5.4
Resistance 20 °C (ohm/km) 0.253
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.443
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223633
Reka code 1111316
Nominal diameter of complete cable (mm) 38
Nominal weight of cable (kg/km) 2090
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 41
Bending radius
During handling and installation, cable (cm) 452
In final installation, cable (cm) 317
During handling and installation, cable (cm) 45
In final installation, cable (cm) 32
During handling and installation, cable (m) 0.45
In final installation, cable (m) 0.32
Pulling force
Pulling-eye (kN) 5.4
Pulling-stocking (kN) 5.4
Resistance 20 °C (ohm/km) 0.253
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.443
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223534
Reka code 1111316

3x150/41

Electric number Size Packing (m) Voltage

3x150/41

Nominal diameter of complete cable (mm) 41
Nominal weight of cable (kg/km) 2450
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 41
Bending radius
During handling and installation, cable (cm) 492
In final installation, cable (cm) 344
During handling and installation, cable (cm) 49
In final installation, cable (cm) 34
During handling and installation, cable (m) 0.49
In final installation, cable (m) 0.34
Pulling force
Pulling-eye (kN) 6.8
Pulling-stocking (kN) 6.8
Resistance 20 °C (ohm/km) 0.206
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.443
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223565
Reka code 1111317
Nominal diameter of complete cable (mm) 41
Nominal weight of cable (kg/km) 2450
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 41
Bending radius
During handling and installation, cable (cm) 492
In final installation, cable (cm) 344
During handling and installation, cable (cm) 49
In final installation, cable (cm) 34
During handling and installation, cable (m) 0.49
In final installation, cable (m) 0.34
Pulling force
Pulling-eye (kN) 6.8
Pulling-stocking (kN) 6.8
Resistance 20 °C (ohm/km) 0.206
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.443
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223640
Reka code 1111317

3x185/57

Electric number Size Packing (m) Voltage

3x185/57

Nominal diameter of complete cable (mm) 45
Nominal weight of cable (kg/km) 3048
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 57
Bending radius
During handling and installation, cable (cm) 544
In final installation, cable (cm) 381
During handling and installation, cable (cm) 54
In final installation, cable (cm) 38
During handling and installation, cable (m) 0.54
In final installation, cable (m) 0.38
Pulling force
Pulling-eye (kN) 8.3
Pulling-stocking (kN) 8.3
Resistance 20 °C (ohm/km) 0.164
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.32
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223657
Reka code 1111318

3x240/72

Electric number Size Packing (m) Voltage

3x240/72

Nominal diameter of complete cable (mm) 51
Nominal weight of cable (kg/km) 3933
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 72
Bending radius
During handling and installation, cable (cm) 608
In final installation, cable (cm) 426
During handling and installation, cable (cm) 61
In final installation, cable (cm) 43
During handling and installation, cable (m) 0.61
In final installation, cable (m) 0.43
Pulling force
Pulling-eye (kN) 10.8
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.125
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.253
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223664
Reka code 1111319

3x300/88

Electric number Size Packing (m) Voltage

3x300/88

Nominal diameter of complete cable (mm) 55
Nominal weight of cable (kg/km) 4802
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 88
Bending radius
During handling and installation, cable (cm) 664
In final installation, cable (cm) 465
During handling and installation, cable (cm) 66
In final installation, cable (cm) 46
During handling and installation, cable (m) 0.66
In final installation, cable (m) 0.46
Pulling force
Pulling-eye (kN) 13.5
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.1
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.206
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223671
Reka code 1111320

4x16/10

Electric number Size Packing (m) Voltage

4x16/10

Nominal diameter of complete cable (mm) 21
Nominal weight of cable (kg/km) 520
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 10
Bending radius
During handling and installation, cable (cm) 250
In final installation, cable (cm) 175
During handling and installation, cable (cm) 25
In final installation, cable (cm) 17
During handling and installation, cable (m) 0.25
In final installation, cable (m) 0.17
Pulling force
Pulling-eye (kN) 1
Pulling-stocking (kN) 1
Resistance 20 °C (ohm/km) 1.91
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.83
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223374
Reka code 1111410

4x25/16

Electric number Size Packing (m) Voltage

4x25/16

Nominal diameter of complete cable (mm) 26
Nominal weight of cable (kg/km) 798
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 312
In final installation, cable (cm) 219
During handling and installation, cable (cm) 31
In final installation, cable (cm) 22
During handling and installation, cable (m) 0.31
In final installation, cable (m) 0.22
Pulling force
Pulling-eye (kN) 1.5
Pulling-stocking (kN) 1.5
Resistance 20 °C (ohm/km) 1.2
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223381
Reka code 1111411

4x35/16

Electric number Size Packing (m) Voltage

4x35/16

Nominal diameter of complete cable (mm) 26
Nominal weight of cable (kg/km) 929
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 312
In final installation, cable (cm) 218
During handling and installation, cable (cm) 31
In final installation, cable (cm) 22
During handling and installation, cable (m) 0.31
In final installation, cable (m) 0.22
Pulling force
Pulling-eye (kN) 2.1
Pulling-stocking (kN) 2.1
Resistance 20 °C (ohm/km) 0.868
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223794
Reka code 1111412
Nominal diameter of complete cable (mm) 26
Nominal weight of cable (kg/km) 929
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 312
In final installation, cable (cm) 218
During handling and installation, cable (cm) 31
In final installation, cable (cm) 22
During handling and installation, cable (m) 0.31
In final installation, cable (m) 0.22
Pulling force
Pulling-eye (kN) 2.1
Pulling-stocking (kN) 2.1
Resistance 20 °C (ohm/km) 0.868
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223688
Reka code 1111412

4x50/16

Electric number Size Packing (m) Voltage

4x50/16

Nominal diameter of complete cable (mm) 30
Nominal weight of cable (kg/km) 1203
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 363
In final installation, cable (cm) 254
During handling and installation, cable (cm) 36
In final installation, cable (cm) 25
During handling and installation, cable (m) 0.36
In final installation, cable (m) 0.25
Pulling force
Pulling-eye (kN) 3
Pulling-stocking (kN) 3
Resistance 20 °C (ohm/km) 0.641
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223404
Reka code 1111413
Nominal diameter of complete cable (mm) 30
Nominal weight of cable (kg/km) 1203
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 363
In final installation, cable (cm) 254
During handling and installation, cable (cm) 36
In final installation, cable (cm) 25
During handling and installation, cable (m) 0.36
In final installation, cable (m) 0.25
Pulling force
Pulling-eye (kN) 3
Pulling-stocking (kN) 3
Resistance 20 °C (ohm/km) 0.641
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223367
Reka code 1111413

4x70/21

Electric number Size Packing (m) Voltage

4x70/21

Nominal diameter of complete cable (mm) 33
Nominal weight of cable (kg/km) 1572
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 21
Bending radius
During handling and installation, cable (cm) 398
In final installation, cable (cm) 279
During handling and installation, cable (cm) 40
In final installation, cable (cm) 28
During handling and installation, cable (m) 0.4
In final installation, cable (m) 0.28
Pulling force
Pulling-eye (kN) 4.2
Pulling-stocking (kN) 4.2
Resistance 20 °C (ohm/km) 0.443
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.868
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223817
Reka code 1111414
Nominal diameter of complete cable (mm) 33
Nominal weight of cable (kg/km) 1572
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 21
Bending radius
During handling and installation, cable (cm) 398
In final installation, cable (cm) 279
During handling and installation, cable (cm) 40
In final installation, cable (cm) 28
During handling and installation, cable (m) 0.4
In final installation, cable (m) 0.28
Pulling force
Pulling-eye (kN) 4.2
Pulling-stocking (kN) 4.2
Resistance 20 °C (ohm/km) 0.443
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.868
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223800
Reka code 1111414

4x95/29

Electric number Size Packing (m) Voltage

4x95/29

Nominal diameter of complete cable (mm) 38
Nominal weight of cable (kg/km) 2105
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 29
Bending radius
During handling and installation, cable (cm) 457
In final installation, cable (cm) 320
During handling and installation, cable (cm) 46
In final installation, cable (cm) 32
During handling and installation, cable (m) 0.46
In final installation, cable (m) 0.32
Pulling force
Pulling-eye (kN) 5.7
Pulling-stocking (kN) 5.7
Resistance 20 °C (ohm/km) 0.32
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.641
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223541
Reka code 1111415
Nominal diameter of complete cable (mm) 38
Nominal weight of cable (kg/km) 2105
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 29
Bending radius
During handling and installation, cable (cm) 457
In final installation, cable (cm) 320
During handling and installation, cable (cm) 46
In final installation, cable (cm) 32
During handling and installation, cable (m) 0.46
In final installation, cable (m) 0.32
Pulling force
Pulling-eye (kN) 5.7
Pulling-stocking (kN) 5.7
Resistance 20 °C (ohm/km) 0.32
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.641
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223824
Reka code 1111415

4x120/41

Electric number Size Packing (m) Voltage

4x120/41

Nominal diameter of complete cable (mm) 42
Nominal weight of cable (kg/km) 2577
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 41
Bending radius
During handling and installation, cable (cm) 503
In final installation, cable (cm) 352
During handling and installation, cable (cm) 50
In final installation, cable (cm) 35
During handling and installation, cable (m) 0.5
In final installation, cable (m) 0.35
Pulling force
Pulling-eye (kN) 7.2
Pulling-stocking (kN) 7.2
Resistance 20 °C (ohm/km) 0.253
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.443
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223831
Reka code 1111416

4x150/41

Electric number Size Packing (m) Voltage

4x150/41

Nominal diameter of complete cable (mm) 47
Nominal weight of cable (kg/km) 3093
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 41
Bending radius
During handling and installation, cable (cm) 560
In final installation, cable (cm) 392
During handling and installation, cable (cm) 56
In final installation, cable (cm) 39
During handling and installation, cable (m) 0.56
In final installation, cable (m) 0.39
Pulling force
Pulling-eye (kN) 9
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.206
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.443
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223848
Reka code 1111417

4x185/57

Electric number Size Packing (m) Voltage

4x185/57

Nominal diameter of complete cable (mm) 51
Nominal weight of cable (kg/km) 3798
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 57
Bending radius
During handling and installation, cable (cm) 613
In final installation, cable (cm) 429
During handling and installation, cable (cm) 61
In final installation, cable (cm) 43
During handling and installation, cable (m) 0.61
In final installation, cable (m) 0.43
Pulling force
Pulling-eye (kN) 11.1
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.164
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.32
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223855
Reka code 1111418

4x240/72

Electric number Size Packing (m) Voltage

4x240/72

Nominal diameter of complete cable (mm) 58
Nominal weight of cable (kg/km) 4958
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 72
Bending radius
During handling and installation, cable (cm) 694
In final installation, cable (cm) 486
During handling and installation, cable (cm) 69
In final installation, cable (cm) 49
During handling and installation, cable (m) 0.69
In final installation, cable (m) 0.49
Pulling force
Pulling-eye (kN) 14.4
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.125
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.253
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223862
Reka code 1111419

4x300/88

Electric number Size Packing (m) Voltage

4x300/88

Nominal diameter of complete cable (mm) 64
Nominal weight of cable (kg/km) 6062
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 88
Bending radius
During handling and installation, cable (cm) 763
In final installation, cable (cm) 534
During handling and installation, cable (cm) 76
In final installation, cable (cm) 53
During handling and installation, cable (m) 0.76
In final installation, cable (m) 0.53
Pulling force
Pulling-eye (kN) 18
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.1
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.206
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223879
Reka code 1111420
Nominal diameter of complete cable (mm) 64
Nominal weight of cable (kg/km) 6062
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 88
Bending radius
During handling and installation, cable (cm) 763
In final installation, cable (cm) 534
During handling and installation, cable (cm) 76
In final installation, cable (cm) 53
During handling and installation, cable (m) 0.76
In final installation, cable (m) 0.53
Pulling force
Pulling-eye (kN) 18
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.1
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.206
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -40
Maximum conductor temperature in normal operation (°C) 70
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 160
EAN code 6410006223886
Reka code 1111420