AHXAMK-WP

For fixed installations outdoors and may also be buried in soil. Cable is both longitudinally and radially watertight and therefore suitable where wet soil and/or water permanently occurs. Suitable for ploughing. Not for submarine or similar applications.

Standards HD 620 S2:2010 Part 10 Section F, SFS 5636:2017
Conductor Watertight, circular, stranded aluminium, EN/IEC 60228 class 2
Conductor screen Semiconducting cross-linked polyethylene XLPE
Insulation Cross-linked polyethylene XLPE
Insulation screen Semiconducting cross-linked polyethylene XLPE
Core Identification (all color combinations in the cable family) Black insulation, white numbers
Metal screen Aluminium/plastic laminate, which acts also as a radial water barrier.
Oversheath PE-plastic
Colour of the oversheath Black

3x50

Electric number Size Packaging Voltage

3x50

Nominal diameter of complete cable mm 59
Nominal weight of cable kg/km 1939
Conductor material Aluminum
Nominal diameter of conductor mm 8
Nominal cross-sectional area of conductor mm2 50
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 19.3
Nominal thickness of aluminium laminated foil mm 0.2
Min. bending radius
During handling and installation, cable mm 708
In final installation, cable mm 496
During handling and installation, phase conductor mm 0.44
In final installation, phase conductor mm 0.3
During handling and installation, cable cm 71
In final installation, cable cm 50
During handling and installation, cable m 0.71
In final installation, cable m 0.5
Max. pulling force
Pulling-eye kN 7.5
Pulling-stocking kN 2.3
Resistance 20 °C Ω/km 0.641
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006224005
Reka code 1187052

3x70

Electric number Size Packaging Voltage

3x70

Nominal diameter of complete cable mm 62
Nominal weight of cable kg/km 2226
Conductor material Aluminum
Nominal diameter of conductor mm 9.6
Nominal cross-sectional area of conductor mm2 70
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 20.7
Nominal thickness of aluminium laminated foil mm 0.2
Min. bending radius
During handling and installation, cable mm 744
In final installation, cable mm 521
During handling and installation, phase conductor mm 0.45
In final installation, phase conductor mm 0.32
During handling and installation, cable cm 74
In final installation, cable cm 52
During handling and installation, cable m 0.74
In final installation, cable m 0.52
Max. pulling force
Pulling-eye kN 10.5
Pulling-stocking kN 3.2
Resistance 20 °C Ω/km 0.443
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006224012
Reka code 1187103

3x95

Electric number Size Packaging Voltage

3x95

Nominal diameter of complete cable mm 66
Nominal weight of cable kg/km 2598
Conductor material Aluminum
Nominal diameter of conductor mm 11.1
Nominal cross-sectional area of conductor mm2 95
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 22.4
Nominal thickness of aluminium laminated foil mm 0.2
Min. bending radius
During handling and installation, cable mm 792
In final installation, cable mm 554
During handling and installation, phase conductor mm 0.48
In final installation, phase conductor mm 0.34
During handling and installation, cable cm 79
In final installation, cable cm 55
During handling and installation, cable m 0.79
In final installation, cable m 0.55
Max. pulling force
Pulling-eye kN 14.3
Pulling-stocking kN 4.3
Resistance 20 °C Ω/km 0,320
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006224036
Reka code 1187104

3x150

Electric number Size Packaging Voltage

3x150

Nominal diameter of complete cable mm 71
Nominal weight of cable kg/km 3268
Conductor material Aluminum
Nominal diameter of conductor mm 13.9
Nominal cross-sectional area of conductor mm2 150
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 25.1
Nominal thickness of aluminium laminated foil mm 0.2
Min. bending radius
During handling and installation, cable mm 852
In final installation, cable mm 596
During handling and installation, phase conductor mm 0.53
In final installation, phase conductor mm 0.37
During handling and installation, cable cm 85
In final installation, cable cm 60
During handling and installation, cable m 0.85
In final installation, cable m 0.6
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 6.8
Resistance 20 °C Ω/km 0.206
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006224050
Reka code 1187106

3x185

Electric number Size Packaging Voltage

3x185

Nominal diameter of complete cable mm 76
Nominal weight of cable kg/km 3784
Conductor material Aluminum
Nominal diameter of conductor mm 15.6
Nominal cross-sectional area of conductor mm2 185
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 27
Nominal thickness of aluminium laminated foil mm 0.2
Min. bending radius
During handling and installation, cable mm 912
In final installation, cable mm 638
During handling and installation, phase conductor mm 0.56
In final installation, phase conductor mm 0.39
During handling and installation, cable cm 91
In final installation, cable cm 64
During handling and installation, cable m 0.91
In final installation, cable m 0.64
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.3
Resistance 20 °C Ω/km 0.164
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006224074
Reka code 1187107

3x240

Electric number Size Packaging Voltage

3x240

Nominal diameter of complete cable mm 82
Nominal weight of cable kg/km 4563
Conductor material Aluminum
Nominal diameter of conductor mm 18
Nominal cross-sectional area of conductor mm2 240
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 29.2
Nominal thickness of aluminium laminated foil mm 0.3
Min. bending radius
During handling and installation, cable mm 984
In final installation, cable mm 689
During handling and installation, phase conductor mm 0.59
In final installation, phase conductor mm 0.41
During handling and installation, cable cm 98
In final installation, cable cm 69
During handling and installation, cable m 0.98
In final installation, cable m 0.69
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0.125
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006224098
Reka code 1187108

3x300

Electric number Size Packaging Voltage

3x300

Nominal diameter of complete cable mm 86
Nominal weight of cable kg/km 5301
Conductor material Aluminum
Nominal diameter of conductor mm 19.8
Nominal cross-sectional area of conductor mm2 300
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 31
Nominal thickness of aluminium laminated foil mm 0.3
Min. bending radius
During handling and installation, cable mm 1032
In final installation, cable mm 722
During handling and installation, phase conductor mm 0.62
In final installation, phase conductor mm 0.43
During handling and installation, cable cm 103
In final installation, cable cm 72
During handling and installation, cable m 1.03
In final installation, cable m 0.72
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,100
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176300077
Reka code 1187109