AHXAMK-WP

For fixed installations outdoors and may also be buried in soil. Cable is both longitudinally and radially watertight and therefore suitable where wet soil and/or water permanently occurs. Suitable for ploughing. Not for submarine or similar applications.

Standards HD 620 S2:2010 Part 10F, SFS
Conductor Watertight, circular, stranded aluminium, EN/IEC 60228 class 2
Insulation Conductor screen, semiconducting XLPE,
Insulation XLPE,
Insulation screen, semiconducting XLPE
Core Identification (all color combinations in the cable family) Black insulation, white numbers
Metal screen Aluminium/plastic laminate, which acts also as a radial water barrier.
Oversheath PE-plastic
Colour of the oversheath Black

3x50

Electric number Size Packing (m) Voltage

3x50

Nominal diameter of complete cable (mm) 59
Nominal weight of cable (kg/km) 1939
Conductor material Aluminum
Nominal diameter of conductor (mm) 8
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 5.5
Nominal diameter over the insulation without insulation screen (mm) 19.3
Number of wires 3
Nominal thickness of aluminium laminated foil (mm) 0.2
Bending radius
During handling and installation, cable (cm) 708
In final installation, cable (cm) 496
During handling and installation, phase conductor (cm) 0.44
In final installation, phase conductor (cm) 0.3
Pulling force
Pulling-eye (kN) 7.5
Pulling-stocking (kN) 2.3
Resistance 20 °C (ohm/km) 0.641
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 4.7
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
Metal screen (initial temperature 60 °C, final temperature 250 °C) (°C) 2.4
EAN code 6410006224005
Reka code 1187052

3x70

Electric number Size Packing (m) Voltage

3x70

Nominal diameter of complete cable (mm) 62
Nominal weight of cable (kg/km) 2226
Conductor material Aluminum
Nominal diameter of conductor (mm) 9.6
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 5.5
Nominal diameter over the insulation without insulation screen (mm) 20.7
Number of wires 3
Nominal thickness of aluminium laminated foil (mm) 0.2
Bending radius
During handling and installation, cable (cm) 744
In final installation, cable (cm) 521
During handling and installation, phase conductor (cm) 0.45
In final installation, phase conductor (cm) 0.32
Pulling force
Pulling-eye (kN) 10.5
Pulling-stocking (kN) 3.2
Resistance 20 °C (ohm/km) 0.443
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 6.6
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
Metal screen (initial temperature 60 °C, final temperature 250 °C) (°C) 2.5
EAN code 6410006224012
Reka code 1187103

3x95

Electric number Size Packing (m) Voltage

3x95

Nominal diameter of complete cable (mm) 66
Nominal weight of cable (kg/km) 2598
Conductor material Aluminum
Nominal diameter of conductor (mm) 11.1
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 5.5
Nominal diameter over the insulation without insulation screen (mm) 22.4
Number of wires 3
Nominal thickness of aluminium laminated foil (mm) 0.2
Bending radius
During handling and installation, cable (cm) 792
In final installation, cable (cm) 554
During handling and installation, phase conductor (cm) 0.48
In final installation, phase conductor (cm) 0.34
Pulling force
Pulling-eye (kN) 14.3
Pulling-stocking (kN) 4.3
Resistance 20 °C (ohm/km) 0.32
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 8.9
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
Metal screen (initial temperature 60 °C, final temperature 250 °C) (°C) 2.7
EAN code 6410006224036
Reka code 1187104

3x150

Electric number Size Packing (m) Voltage

3x150

Nominal diameter of complete cable (mm) 71
Nominal weight of cable (kg/km) 3268
Conductor material Aluminum
Nominal diameter of conductor (mm) 13.9
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 5.5
Nominal diameter over the insulation without insulation screen (mm) 25.1
Number of wires 3
Nominal thickness of aluminium laminated foil (mm) 0.2
Bending radius
During handling and installation, cable (cm) 852
In final installation, cable (cm) 596
During handling and installation, phase conductor (cm) 0.53
In final installation, phase conductor (cm) 0.37
Pulling force
Pulling-eye (kN) 20
Pulling-stocking (kN) 6.8
Resistance 20 °C (ohm/km) 0.206
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 14.1
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
Metal screen (initial temperature 60 °C, final temperature 250 °C) (°C) 3
EAN code 6410006224050
Reka code 1187106

3x185

Electric number Size Packing (m) Voltage

3x185

Nominal diameter of complete cable (mm) 76
Nominal weight of cable (kg/km) 3784
Conductor material Aluminum
Nominal diameter of conductor (mm) 15.6
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 5.5
Nominal diameter over the insulation without insulation screen (mm) 27
Number of wires 3
Nominal thickness of aluminium laminated foil (mm) 0.2
Bending radius
During handling and installation, cable (cm) 912
In final installation, cable (cm) 638
During handling and installation, phase conductor (cm) 0.56
In final installation, phase conductor (cm) 0.39
Pulling force
Pulling-eye (kN) 20
Pulling-stocking (kN) 8.3
Resistance 20 °C (ohm/km) 0.164
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 17.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
Metal screen (initial temperature 60 °C, final temperature 250 °C) (°C) 3.2
EAN code 6410006224074
Reka code 1187107

3x300

Electric number Size Packing (m) Voltage

3x300

Nominal diameter of complete cable (mm) 86
Nominal weight of cable (kg/km) 5301
Conductor material Aluminum
Nominal diameter of conductor (mm) 19.8
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 5.5
Nominal diameter over the insulation without insulation screen (mm) 31
Number of wires 3
Nominal thickness of aluminium laminated foil (mm) 0.3
Bending radius
During handling and installation, cable (cm) 1032
In final installation, cable (cm) 722
During handling and installation, phase conductor (cm) 0.62
In final installation, phase conductor (cm) 0.43
Pulling force
Pulling-eye (kN) 20
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.1
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 28.3
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
Metal screen (initial temperature 60 °C, final temperature 250 °C) (°C) 4.4
EAN code 6438176300077
Reka code 1187109

3x240

Electric number Size Packing (m) Voltage

3x240

Nominal diameter of complete cable (mm) 82
Nominal weight of cable (kg/km) 4563
Conductor material Aluminum
Nominal diameter of conductor (mm) 18
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 5.5
Nominal diameter over the insulation without insulation screen (mm) 29.2
Number of wires 3
Nominal thickness of aluminium laminated foil (mm) 0.3
Bending radius
During handling and installation, cable (cm) 984
In final installation, cable (cm) 689
During handling and installation, phase conductor (cm) 0.59
In final installation, phase conductor (cm) 0.41
Pulling force
Pulling-eye (kN) 20
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.125
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 22.6
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
Metal screen (initial temperature 60 °C, final temperature 250 °C) (°C) 4.8
EAN code 6410006224098
Reka code 1187108