AHXAMK-WP 36 kV 1-core

Cable is intended for fixed installations outdoors and may also be buried in soil. Cable is both longitudinally and radially watertight and therefore suitable where















































wet soil and/or water permanently occurs. Suitable for ploughing. Not for submarine or similar applications

Standards HD 620 S2:2010 Part 10 Section F, SFS 5636:2017
Conductor Watertight, circular, stranded aluminium EN/IEC 60228 class 2
Conductor screen Semiconducting cross-linked polyethylene XLPE
Insulation Cross-linked polyethylene XLPE
Insulation screen Semiconducting cross-linked polyethylene XLPE
Core Identification (all color combinations in the cable family) Black cores with white numbers
Metal screen PE-laminated aluminium foil bonded to the sheath
Oversheath Polyethylene
Colour of the oversheath Black

1x400

Electric number Size Packaging Voltage

1x400

Nominal diameter of complete cable mm 46
Nominal weight of cable kg/km 2193
Conductor material Aluminum
Nominal diameter of conductor mm 22
Nominal cross-sectional area of conductor mm2 400
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 38
Number of wires 1
Nominal thickness of aluminium laminated foil mm 0.3
Bending radius
During handling and installation, cable mm 690
In final installation, cable mm 483
During handling and installation, cable cm 69
In final installation, cable cm 48
During handling and installation, cable m 0.69
In final installation, cable m 0.48
Pulling force
Pulling-eye kN 20
Pulling-stocking kN 6
Resistance 20 °C Ω/km 0.0778
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176306062
Reka code 1181881

1x500

Electric number Size Packaging Voltage

1x500

Nominal diameter of complete cable mm 49
Nominal weight of cable kg/km 2671
Conductor material Aluminum
Nominal diameter of conductor mm 26
Nominal cross-sectional area of conductor mm2 500
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 41.3
Number of wires 1
Nominal thickness of aluminium laminated foil mm 0.3
Bending radius
During handling and installation, cable mm 735
In final installation, cable mm 515
During handling and installation, cable cm 74
In final installation, cable cm 52
During handling and installation, cable m 0.74
In final installation, cable m 0.52
Pulling force
Pulling-eye kN 20
Pulling-stocking kN 7.5
Resistance 20 °C Ω/km 0.0605
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176306079
Reka code 1181882

1x630

Electric number Size Packaging Voltage

1x630

Nominal diameter of complete cable mm 53
Nominal weight of cable kg/km 3266
Conductor material Aluminum
Nominal diameter of conductor mm 29
Nominal cross-sectional area of conductor mm2 630
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 45.2
Number of wires 1
Nominal thickness of aluminium laminated foil mm 0.3
Bending radius
During handling and installation, cable mm 795
In final installation, cable mm 557
During handling and installation, cable cm 80
In final installation, cable cm 56
During handling and installation, cable m 0.8
In final installation, cable m 0.56
Pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0.0469
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176306086
Reka code 1181883

1x800

Electric number Size Packaging Voltage

1x800

Nominal diameter of complete cable mm 57
Nominal weight of cable kg/km 3946
Conductor material Aluminum
Nominal diameter of conductor mm 33
Nominal cross-sectional area of conductor mm2 800
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 49.1
Number of wires 1
Nominal thickness of aluminium laminated foil mm 0.3
Bending radius
During handling and installation, cable mm 855
In final installation, cable mm 599
During handling and installation, cable cm 86
In final installation, cable cm 60
During handling and installation, cable m 0.86
In final installation, cable m 0.6
Pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0.0367
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176306093
Reka code 1181884

1x1000

Electric number Size Packaging Voltage

1x1000

Nominal diameter of complete cable mm 64
Nominal weight of cable kg/km 4722
Conductor material Aluminum
Nominal diameter of conductor mm 39
Nominal cross-sectional area of conductor mm2 1000
Nominal thickness of insulation mm 8
Nominal diameter over the insulation without insulation screen mm 55
Number of wires 1
Nominal thickness of aluminium laminated foil mm 0.3
Bending radius
During handling and installation, cable mm 960
In final installation, cable mm 672
During handling and installation, cable cm 96
In final installation, cable cm 67
During handling and installation, cable m 0.96
In final installation, cable m 0.67
Pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0.0291
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176306109
Reka code 1181885