AHXAMK-WM

For fixed installations outdoors and may also be buried in soil. Cable is both longitudinally and radially watertight and therefore suitable where wet soil and/or water permanently occurs. Also suitable for aerial installations due to sheathed carrier cable. Suitable for ploughing. Not for submarine or similar applications

Standards HD 620 S2:2010 Part 10 Section F, SFS 5636:2017
Conductor Watertight, circular, stranded aluminium, EN/IEC 60228 class 2
Conductor screen Semiconducting cross-linked polyethylene XLPE
Insulation Cross-linked polyethylene XLPE
Insulation screen Semiconducting cross-linked polyethylene XLPE
Core Identification (all color combinations in the cable family) Black insulation, white numbers
Metal screen Aluminium/plastic laminate, which acts also as a radial water barrier.
Oversheath PE-plastic
Colour of the oversheath Black

3x50+62

Electric number Size Packaging Voltage

3x50+62

Nominal diameter of complete cable mm 57
Nominal weight of cable kg/km 1826
Conductor material Aluminum
Nominal diameter of conductor mm 8
Nominal cross-sectional area of conductor mm2 50
Nominal thickness of insulation mm 3.4
Nominal diameter over the insulation without insulation screen mm 15.3
Nominal thickness of aluminium laminated foil mm 0.2
Nominal diameter of messenger mm 13.1
Min. bending radius
During handling and installation, cable mm 684
In final installation, cable mm 479
During handling and installation, phase conductor mm 0.35
In final installation, phase conductor mm 0.24
During handling and installation, cable cm 68
In final installation, cable cm 48
During handling and installation, cable m 0.68
In final installation, cable m 0.48
Max. pulling force
Pulling-eye kN 7.5
Pulling-stocking kN 2.3
Resistance 20 °C Ω/km 0.641
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006022373
Reka code 1187122
Nominal diameter of complete cable mm 65
Nominal weight of cable kg/km 2257
Conductor material Aluminum
Nominal diameter of conductor mm 8
Nominal cross-sectional area of conductor mm2 50
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 19.3
Nominal thickness of aluminium laminated foil mm 0.2
Nominal diameter of messenger mm 13.1
Min. bending radius
During handling and installation, cable mm 780
In final installation, cable mm 546
During handling and installation, phase conductor mm 0.41
In final installation, phase conductor mm 0.28
During handling and installation, cable cm 78
In final installation, cable cm 55
During handling and installation, cable m 0.78
In final installation, cable m 0.55
Max. pulling force
Pulling-eye kN 7.5
Pulling-stocking kN 2.3
Resistance 20 °C Ω/km 0.641
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006022441
Reka code 1187142

3x70+62

Electric number Size Packaging Voltage

3x70+62

Nominal diameter of complete cable mm 59
Nominal weight of cable kg/km 2079
Conductor material Aluminum
Nominal diameter of conductor mm 9.6
Nominal cross-sectional area of conductor mm2 70
Nominal thickness of insulation mm 3.4
Nominal diameter over the insulation without insulation screen mm 16.7
Nominal thickness of aluminium laminated foil mm 0.2
Nominal diameter of messenger mm 13.1
Min. bending radius
During handling and installation, cable mm 708
In final installation, cable mm 496
During handling and installation, phase conductor mm 0.36
In final installation, phase conductor mm 0.25
During handling and installation, cable cm 71
In final installation, cable cm 50
During handling and installation, cable m 0.71
In final installation, cable m 0.5
Max. pulling force
Pulling-eye kN 10.5
Pulling-stocking kN 3.2
Resistance 20 °C Ω/km 0.443
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006022380
Reka code 1187123
Nominal diameter of complete cable mm 69
Nominal weight of cable kg/km 2552
Conductor material Aluminum
Nominal diameter of conductor mm 9.6
Nominal cross-sectional area of conductor mm2 70
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 20.7
Nominal thickness of aluminium laminated foil mm 0.2
Nominal diameter of messenger mm 13.1
Min. bending radius
During handling and installation, cable mm 828
In final installation, cable mm 580
During handling and installation, phase conductor mm 0.42
In final installation, phase conductor mm 0.29
During handling and installation, cable cm 83
In final installation, cable cm 58
During handling and installation, cable m 0.83
In final installation, cable m 0.58
Max. pulling force
Pulling-eye kN 10.5
Pulling-stocking kN 3.2
Resistance 20 °C Ω/km 0.443
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006022458
Reka code 1187143

3x95+62

Electric number Size Packaging Voltage

3x95+62

Nominal diameter of complete cable mm 63
Nominal weight of cable kg/km 2400
Conductor material Aluminum
Nominal diameter of conductor mm 11.1
Nominal cross-sectional area of conductor mm2 95
Nominal thickness of insulation mm 3.4
Nominal diameter over the insulation without insulation screen mm 18.4
Nominal thickness of aluminium laminated foil mm 0.2
Nominal diameter of messenger mm 13.1
Min. bending radius
During handling and installation, cable mm 756
In final installation, cable mm 529
During handling and installation, phase conductor mm 0.39
In final installation, phase conductor mm 0.27
During handling and installation, cable cm 76
In final installation, cable cm 53
During handling and installation, cable m 0.76
In final installation, cable m 0.53
Max. pulling force
Pulling-eye kN 14.3
Pulling-stocking kN 4.3
Resistance 20 °C Ω/km 0,320
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006022397
Reka code 1187124
Nominal diameter of complete cable mm 72
Nominal weight of cable kg/km 2882
Conductor material Aluminum
Nominal diameter of conductor mm 11.1
Nominal cross-sectional area of conductor mm2 95
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 22.4
Nominal thickness of aluminium laminated foil mm 0.2
Nominal diameter of messenger mm 13.1
Min. bending radius
During handling and installation, cable mm 864
In final installation, cable mm 605
During handling and installation, phase conductor mm 0.45
In final installation, phase conductor mm 0.32
During handling and installation, cable cm 86
In final installation, cable cm 61
During handling and installation, cable m 0.86
In final installation, cable m 0.61
Max. pulling force
Pulling-eye kN 14.3
Pulling-stocking kN 4.3
Resistance 20 °C Ω/km 0,320
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006022465
Reka code 1187144

3x120+62

Electric number Size Packaging Voltage

3x120+62

Nominal diameter of complete cable mm 65
Nominal weight of cable kg/km 2710
Conductor material Aluminum
Nominal diameter of conductor mm 12.6
Nominal cross-sectional area of conductor mm2 120
Nominal thickness of insulation mm 3.4
Nominal diameter over the insulation without insulation screen mm 20.4
Nominal thickness of aluminium laminated foil mm 0.2
Nominal diameter of messenger mm 13.1
Min. bending radius
During handling and installation, cable mm 780
In final installation, cable mm 546
During handling and installation, phase conductor mm 0.42
In final installation, phase conductor mm 0.29
During handling and installation, cable cm 78
In final installation, cable cm 55
During handling and installation, cable m 0.78
In final installation, cable m 0.55
Max. pulling force
Pulling-eye kN 18
Pulling-stocking kN 5.4
Resistance 20 °C Ω/km 0.253
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006022403
Reka code 1187125
Nominal diameter of complete cable mm 75
Nominal weight of cable kg/km 3254
Conductor material Aluminum
Nominal diameter of conductor mm 12.6
Nominal cross-sectional area of conductor mm2 120
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 23.8
Nominal thickness of aluminium laminated foil mm 0.2
Nominal diameter of messenger mm 13.1
Min. bending radius
During handling and installation, cable mm 900
In final installation, cable mm 630
During handling and installation, phase conductor mm 0.48
In final installation, phase conductor mm 0.34
During handling and installation, cable cm 90
In final installation, cable cm 63
During handling and installation, cable m 0.9
In final installation, cable m 0.63
Max. pulling force
Pulling-eye kN 18
Pulling-stocking kN 5.4
Resistance 20 °C Ω/km 0.253
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006022472
Reka code 1187145

3x150+62

Electric number Size Packaging Voltage

3x150+62

Nominal diameter of complete cable mm 68
Nominal weight of cable kg/km 3015
Conductor material Aluminum
Nominal diameter of conductor mm 13.9
Nominal cross-sectional area of conductor mm2 150
Nominal thickness of insulation mm 3.4
Nominal diameter over the insulation without insulation screen mm 21.9
Nominal thickness of aluminium laminated foil mm 0.2
Nominal diameter of messenger mm 13.1
Min. bending radius
During handling and installation, cable mm 816
In final installation, cable mm 571
During handling and installation, phase conductor mm 0.45
In final installation, phase conductor mm 0.32
During handling and installation, cable cm 82
In final installation, cable cm 57
During handling and installation, cable m 0.82
In final installation, cable m 0.57
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 6.8
Resistance 20 °C Ω/km 0.206
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006022410
Reka code 1187126
Nominal diameter of complete cable mm 78
Nominal weight of cable kg/km 3568
Conductor material Aluminum
Nominal diameter of conductor mm 13.9
Nominal cross-sectional area of conductor mm2 150
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 25.3
Nominal thickness of aluminium laminated foil mm 0.2
Nominal diameter of messenger mm 13.1
Min. bending radius
During handling and installation, cable mm 936
In final installation, cable mm 655
During handling and installation, phase conductor mm 0.5
In final installation, phase conductor mm 0.35
During handling and installation, cable cm 94
In final installation, cable cm 66
During handling and installation, cable m 0.94
In final installation, cable m 0.66
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 6.8
Resistance 20 °C Ω/km 0.206
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006022489
Reka code 1187146

3x240+62

Electric number Size Packaging Voltage

3x240+62

Nominal diameter of complete cable mm 77
Nominal weight of cable kg/km 4084
Conductor material Aluminum
Nominal diameter of conductor mm 18
Nominal cross-sectional area of conductor mm2 240
Nominal thickness of insulation mm 3.4
Nominal diameter over the insulation without insulation screen mm 25.8
Nominal thickness of aluminium laminated foil mm 0.2
Nominal diameter of messenger mm 13.1
Min. bending radius
During handling and installation, cable mm 924
In final installation, cable mm 647
During handling and installation, phase conductor mm 0.51
In final installation, phase conductor mm 0.36
During handling and installation, cable cm 92
In final installation, cable cm 65
During handling and installation, cable m 0.92
In final installation, cable m 0.65
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0.125
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006022434
Reka code 1187128
Nominal diameter of complete cable mm 86
Nominal weight of cable kg/km 4815
Conductor material Aluminum
Nominal diameter of conductor mm 18
Nominal cross-sectional area of conductor mm2 240
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 29.2
Nominal thickness of aluminium laminated foil mm 0.2
Nominal diameter of messenger mm 13.1
Min. bending radius
During handling and installation, cable mm 1032
In final installation, cable mm 722
During handling and installation, phase conductor mm 0.57
In final installation, phase conductor mm 0.4
During handling and installation, cable cm 103
In final installation, cable cm 72
During handling and installation, cable m 1.03
In final installation, cable m 0.72
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0.125
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6438176300107
Reka code 1187148

3x185+62

Electric number Size Packaging Voltage

3x185+62

Nominal diameter of complete cable mm 80
Nominal weight of cable kg/km 4100
Conductor material Aluminum
Nominal diameter of conductor mm 15.6
Nominal cross-sectional area of conductor mm2 185
Nominal thickness of insulation mm 5.5
Nominal diameter over the insulation without insulation screen mm 26.8
Nominal thickness of aluminium laminated foil mm 0.2
Nominal diameter of messenger mm 13.1
Min. bending radius
During handling and installation, cable mm 960
In final installation, cable mm 672
During handling and installation, phase conductor mm 0.54
In final installation, phase conductor mm 0.38
During handling and installation, cable cm 96
In final installation, cable cm 67
During handling and installation, cable m 0.96
In final installation, cable m 0.67
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.3
Resistance 20 °C Ω/km 0.164
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006022694
Reka code 1187147