AHXAMK-WM 6/10 (12) kV 3-core


Medium-voltage cable for fixed installations outdoors. May be buried directly in soil, also by ploughing. Cable is longitudinally and radially watertight and therefore it is suitable where wet soil and / or fresh water permanently occurs. Installations must be in accordance with national regulations and rules of installations. The cable is halogen-free, but without fire protection. The cable is not CPR-classified.
Standards | HD 620 10 F, SFS 5636 |
---|---|
Conductor | Watertight, circular, stranded aluminium, EN/IEC 60228 class 2 |
Conductor screen | Semiconducting cross-linked polyethylene XLPE |
Insulation | Cross-linked polyethylene XLPE |
Insulation screen | Semiconducting cross-linked polyethylene XLPE |
Core Identification (all color combinations in the cable family) | White phase numbering: L1, L2, L3 |
Inner covering | Semiconducting waterswellable tape against longitudinal water penetration |
Metal screen | Aluminium/plastic laminate, which acts also as a radial water barrier. |
Oversheath | PE-plastic PELLD |
Colour of the oversheath | Black |
3x50+62
Electric number
Size
Packaging
Voltage
3x50+62
Nominal diameter of complete cable mm
57
Nominal weight of cable kg/km
1826
Conductor material
Aluminium
Nominal diameter of conductor mm
8
Nominal cross-sectional area of conductor mm2
50
Nominal thickness of insulation mm
3.4
Nominal diameter over the insulation without insulation screen mm
15.3
Number of wires
3
Nominal diameter of messenger mm
13.1
Min. bending radius
During handling and installation, phase conductor cm
32
During handling and installation, cable cm
68
In final installation, phase conductor cm
22
In final installation, cable cm
48
During handling and installation, phase conductor m
0.32
During handling and installation, cable m
0.68
In final installation, phase conductor m
0.22
In final installation, cable m
0.48
Max. pulling force
Pulling-eye kN
7.5
Pulling-stocking kN
2.3
Resistance 20 °C Ω/km
0,641
Minimum cable temperature during transport °C
-40
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006022373
Reka code
1187122
3x70+62
Electric number
Size
Packaging
Voltage
3x70+62
Nominal diameter of complete cable mm
59
Nominal weight of cable kg/km
2079
Conductor material
Aluminium
Nominal diameter of conductor mm
9.5
Nominal cross-sectional area of conductor mm2
70
Nominal thickness of insulation mm
3.4
Nominal diameter over the insulation without insulation screen mm
16.7
Number of wires
3
Nominal diameter of messenger mm
13.1
Min. bending radius
During handling and installation, phase conductor cm
35
During handling and installation, cable cm
71
In final installation, phase conductor cm
24
In final installation, cable cm
50
During handling and installation, phase conductor m
0.35
During handling and installation, cable m
0.71
In final installation, phase conductor m
0.24
In final installation, cable m
0.5
Max. pulling force
Pulling-eye kN
10.5
Pulling-stocking kN
3.2
Resistance 20 °C Ω/km
0,443
Minimum cable temperature during transport °C
-40
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006022380
Reka code
1187123
3x95+62
Electric number
Size
Packaging
Voltage
3x95+62
Nominal diameter of complete cable mm
63
Nominal weight of cable kg/km
2400
Conductor material
Aluminium
Nominal diameter of conductor mm
11.1
Nominal cross-sectional area of conductor mm2
95
Nominal thickness of insulation mm
3.4
Nominal diameter over the insulation without insulation screen mm
18.4
Number of wires
3
Nominal diameter of messenger mm
13.1
Min. bending radius
During handling and installation, phase conductor cm
36
During handling and installation, cable cm
76
In final installation, phase conductor cm
25
In final installation, cable cm
53
During handling and installation, phase conductor m
0.36
During handling and installation, cable m
0.76
In final installation, phase conductor m
0.25
In final installation, cable m
0.53
Max. pulling force
Pulling-eye kN
14.3
Pulling-stocking kN
4.3
Resistance 20 °C Ω/km
0,320
Minimum cable temperature during transport °C
-40
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006022397
Reka code
1187124
3x120+62
Electric number
Size
Packaging
Voltage
3x120+62
Nominal diameter of complete cable mm
65
Nominal weight of cable kg/km
2710
Conductor material
Aluminium
Nominal diameter of conductor mm
12.6
Nominal cross-sectional area of conductor mm2
120
Nominal thickness of insulation mm
3.4
Nominal diameter over the insulation without insulation screen mm
19.8
Number of wires
3
Nominal diameter of messenger mm
13.1
Min. bending radius
During handling and installation, phase conductor cm
39
During handling and installation, cable cm
78
In final installation, phase conductor cm
27
In final installation, cable cm
55
During handling and installation, phase conductor m
0.39
During handling and installation, cable m
0.78
In final installation, phase conductor m
0.27
In final installation, cable m
0.55
Max. pulling force
Pulling-eye kN
18
Pulling-stocking kN
5.4
Resistance 20 °C Ω/km
0,253
Minimum cable temperature during transport °C
-40
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006022403
Reka code
1187125
3x150+62
Electric number
Size
Packaging
Voltage
3x150+62
Nominal diameter of complete cable mm
68
Nominal weight of cable kg/km
3015
Conductor material
Aluminium
Nominal diameter of conductor mm
13.9
Nominal cross-sectional area of conductor mm2
150
Nominal thickness of insulation mm
3.4
Nominal diameter over the insulation without insulation screen mm
21.1
Number of wires
3
Nominal diameter of messenger mm
13.1
Min. bending radius
During handling and installation, phase conductor cm
41
During handling and installation, cable cm
82
In final installation, phase conductor cm
28
In final installation, cable cm
57
During handling and installation, phase conductor m
0.41
During handling and installation, cable m
0.82
In final installation, phase conductor m
0.28
In final installation, cable m
0.57
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
6.8
Resistance 20 °C Ω/km
0,206
Minimum cable temperature during transport °C
-40
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006022410
Reka code
1187126
3x240+62
Electric number
Size
Packaging
Voltage
3x240+62
Nominal diameter of complete cable mm
77
Nominal weight of cable kg/km
4084
Conductor material
Aluminium
Nominal diameter of conductor mm
18
Nominal cross-sectional area of conductor mm2
240
Nominal thickness of insulation mm
3.4
Nominal diameter over the insulation without insulation screen mm
25.2
Number of wires
3
Nominal diameter of messenger mm
13.1
Min. bending radius
During handling and installation, phase conductor cm
48
During handling and installation, cable cm
92
In final installation, phase conductor cm
34
In final installation, cable cm
65
During handling and installation, phase conductor m
0.48
During handling and installation, cable m
0.92
In final installation, phase conductor m
0.34
In final installation, cable m
0.65
Max. pulling force
Pulling-eye kN
20
Pulling-stocking kN
8.5
Resistance 20 °C Ω/km
0,125
Minimum cable temperature during transport °C
-40
Minimum cable temperature during handling and installation °C
-20
Minimum cable temperature during operation °C
-50
Maximum conductor temperature in normal operation °C
90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C
250
EAN code
6410006022434
Reka code
1187128