AHXAMK-WM 6/10 (12) kV 3-core

Download product group datasheet

Medium-voltage cable for fixed installations outdoors. May be buried directly in soil, also by ploughing. Cable is longitudinally and radially watertight and therefore it is suitable where wet soil and / or fresh water permanently occurs. Installations must be in accordance with national regulations and rules of installations. The cable is halogen-free, but without fire protection. The cable is not CPR-classified.

Standards HD 620 10 F, SFS 5636
Conductor Watertight, circular, stranded aluminium, EN/IEC 60228 class 2
Conductor screen Semiconducting cross-linked polyethylene XLPE
Insulation Cross-linked polyethylene XLPE
Insulation screen Semiconducting cross-linked polyethylene XLPE
Core Identification (all color combinations in the cable family) White phase numbering: L1, L2, L3
Inner covering Semiconducting waterswellable tape against longitudinal water penetration
Metal screen Aluminium/plastic laminate, which acts also as a radial water barrier.
Oversheath PE-plastic PELLD
Colour of the oversheath Black

3x50+62

Electric number Size Packaging Voltage

3x50+62

Nominal diameter of complete cable mm 57
Nominal weight of cable kg/km 1826
Conductor material Aluminium
Nominal diameter of conductor mm 8
Nominal cross-sectional area of conductor mm2 50
Nominal thickness of insulation mm 3.4
Nominal diameter over the insulation without insulation screen mm 15.3
Number of wires 3
Nominal diameter of messenger mm 13.1
Min. bending radius
During handling and installation, phase conductor cm 32
During handling and installation, cable cm 68
In final installation, phase conductor cm 22
In final installation, cable cm 48
During handling and installation, phase conductor m 0.32
During handling and installation, cable m 0.68
In final installation, phase conductor m 0.22
In final installation, cable m 0.48
Max. pulling force
Pulling-eye kN 7.5
Pulling-stocking kN 2.3
Resistance 20 °C Ω/km 0,641
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006022373
Reka code 1187122

3x70+62

Electric number Size Packaging Voltage

3x70+62

Nominal diameter of complete cable mm 59
Nominal weight of cable kg/km 2079
Conductor material Aluminium
Nominal diameter of conductor mm 9.5
Nominal cross-sectional area of conductor mm2 70
Nominal thickness of insulation mm 3.4
Nominal diameter over the insulation without insulation screen mm 16.7
Number of wires 3
Nominal diameter of messenger mm 13.1
Min. bending radius
During handling and installation, phase conductor cm 35
During handling and installation, cable cm 71
In final installation, phase conductor cm 24
In final installation, cable cm 50
During handling and installation, phase conductor m 0.35
During handling and installation, cable m 0.71
In final installation, phase conductor m 0.24
In final installation, cable m 0.5
Max. pulling force
Pulling-eye kN 10.5
Pulling-stocking kN 3.2
Resistance 20 °C Ω/km 0,443
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006022380
Reka code 1187123

3x95+62

Electric number Size Packaging Voltage

3x95+62

Nominal diameter of complete cable mm 63
Nominal weight of cable kg/km 2400
Conductor material Aluminium
Nominal diameter of conductor mm 11.1
Nominal cross-sectional area of conductor mm2 95
Nominal thickness of insulation mm 3.4
Nominal diameter over the insulation without insulation screen mm 18.4
Number of wires 3
Nominal diameter of messenger mm 13.1
Min. bending radius
During handling and installation, phase conductor cm 36
During handling and installation, cable cm 76
In final installation, phase conductor cm 25
In final installation, cable cm 53
During handling and installation, phase conductor m 0.36
During handling and installation, cable m 0.76
In final installation, phase conductor m 0.25
In final installation, cable m 0.53
Max. pulling force
Pulling-eye kN 14.3
Pulling-stocking kN 4.3
Resistance 20 °C Ω/km 0,320
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006022397
Reka code 1187124

3x120+62

Electric number Size Packaging Voltage

3x120+62

Nominal diameter of complete cable mm 65
Nominal weight of cable kg/km 2710
Conductor material Aluminium
Nominal diameter of conductor mm 12.6
Nominal cross-sectional area of conductor mm2 120
Nominal thickness of insulation mm 3.4
Nominal diameter over the insulation without insulation screen mm 19.8
Number of wires 3
Nominal diameter of messenger mm 13.1
Min. bending radius
During handling and installation, phase conductor cm 39
During handling and installation, cable cm 78
In final installation, phase conductor cm 27
In final installation, cable cm 55
During handling and installation, phase conductor m 0.39
During handling and installation, cable m 0.78
In final installation, phase conductor m 0.27
In final installation, cable m 0.55
Max. pulling force
Pulling-eye kN 18
Pulling-stocking kN 5.4
Resistance 20 °C Ω/km 0,253
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006022403
Reka code 1187125

3x150+62

Electric number Size Packaging Voltage

3x150+62

Nominal diameter of complete cable mm 68
Nominal weight of cable kg/km 3015
Conductor material Aluminium
Nominal diameter of conductor mm 13.9
Nominal cross-sectional area of conductor mm2 150
Nominal thickness of insulation mm 3.4
Nominal diameter over the insulation without insulation screen mm 21.1
Number of wires 3
Nominal diameter of messenger mm 13.1
Min. bending radius
During handling and installation, phase conductor cm 41
During handling and installation, cable cm 82
In final installation, phase conductor cm 28
In final installation, cable cm 57
During handling and installation, phase conductor m 0.41
During handling and installation, cable m 0.82
In final installation, phase conductor m 0.28
In final installation, cable m 0.57
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 6.8
Resistance 20 °C Ω/km 0,206
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006022410
Reka code 1187126

3x240+62

Electric number Size Packaging Voltage

3x240+62

Nominal diameter of complete cable mm 77
Nominal weight of cable kg/km 4084
Conductor material Aluminium
Nominal diameter of conductor mm 18
Nominal cross-sectional area of conductor mm2 240
Nominal thickness of insulation mm 3.4
Nominal diameter over the insulation without insulation screen mm 25.2
Number of wires 3
Nominal diameter of messenger mm 13.1
Min. bending radius
During handling and installation, phase conductor cm 48
During handling and installation, cable cm 92
In final installation, phase conductor cm 34
In final installation, cable cm 65
During handling and installation, phase conductor m 0.48
During handling and installation, cable m 0.92
In final installation, phase conductor m 0.34
In final installation, cable m 0.65
Max. pulling force
Pulling-eye kN 20
Pulling-stocking kN 8.5
Resistance 20 °C Ω/km 0,125
Minimum cable temperature during transport °C -40
Minimum cable temperature during handling and installation °C -20
Minimum cable temperature during operation °C -50
Maximum conductor temperature in normal operation °C 90
Maximum conductor temperature during short circuit (not exceeding 5 sec.) °C 250
EAN code 6410006022434
Reka code 1187128