AHXAMK-W 36 kV

Cable is intended for fixed installations outdoors and may also be buried in soil. Cable is both longitudinally and radially watertight and therefore suitable where
wet soil and/or water permanently occurs. Suitable for ploughing. Not for submarine or similar applications

Conductor Watertight, circular, stranded aluminium EN/IEC 60228 class 2
Conductor screen Semiconducting cross-linked polyethylene XLPE
Insulation Cross-linked polyethylene XLPE
Insulation screen Semiconducting cross-linked polyethylene XLPE
Core Identification (all color combinations in the cable family) Black cores with white numbers
Cable lay up Three sheathed cores are laid up around a bare earth conductor
Metal screen PE-laminated aluminium foil bonded to the sheath
Oversheath Polyethylene
Colour of the oversheath Black

3x95+35 Cu

Electric number Size Packing (m) Voltage

3x95+35 Cu

Nominal diameter of complete cable (mm) 76
Nominal weight of cable (kg/km) 3634
Conductor material Aluminum
Nominal diameter of conductor (mm) 11
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 8
Nominal diameter over the insulation without insulation screen (mm) 26.7
Nominal thickness of aluminium laminated foil (mm) 0.3
Nominal diameter of messenger (mm) 14
Nominal diameter of earth conductor (mm) 7
Nominal diameter of a sheathed phase conductor (mm) 35
Bending radius
During handling and installation, cable (cm) 912
In final installation, cable (cm) 638
During handling and installation, phase conductor (m) 0.53
During handling and installation, cable (m) 0.91
In final installation, phase conductor (m) 0.37
In final installation, cable (m) 0.64
Pulling force
Pulling-eye (kN) 14.3
Pulling-stocking (kN) 4.3
Resistance 20 °C (ohm/km) 0.32
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 8.9
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176306161
Reka code 1181895

3x150+35 Cu

Electric number Size Packing (m) Voltage

3x150+35 Cu

Nominal diameter of complete cable (mm) 82
Nominal weight of cable (kg/km) 4410
Conductor material Aluminum
Nominal diameter of conductor (mm) 14
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 8
Nominal diameter over the insulation without insulation screen (mm) 29.5
Nominal thickness of aluminium laminated foil (mm) 0.3
Nominal diameter of messenger (mm) 14
Nominal diameter of earth conductor (mm) 7
Nominal diameter of a sheathed phase conductor (mm) 38
Bending radius
During handling and installation, cable (cm) 984
In final installation, cable (cm) 689
During handling and installation, phase conductor (m) 0.57
During handling and installation, cable (m) 0.99
In final installation, phase conductor (m) 0.4
In final installation, cable (m) 0.69
Pulling force
Pulling-eye (kN) 20
Pulling-stocking (kN) 6.8
Resistance 20 °C (ohm/km) 0.206
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 14.1
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176306185
Reka code 1181897

3x185+35 Cu

Electric number Size Packing (m) Voltage

3x185+35 Cu

Nominal diameter of complete cable (mm) 86
Nominal weight of cable (kg/km) 4927
Conductor material Aluminum
Nominal diameter of conductor (mm) 16
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 8
Nominal diameter over the insulation without insulation screen (mm) 31.2
Nominal thickness of aluminium laminated foil (mm) 0.3
Nominal diameter of messenger (mm) 14
Nominal diameter of earth conductor (mm) 7
Nominal diameter of a sheathed phase conductor (mm) 40
Bending radius
During handling and installation, cable (cm) 1032
In final installation, cable (cm) 722
During handling and installation, phase conductor (m) 0.6
During handling and installation, cable (m) 1.03
In final installation, phase conductor (m) 0.42
In final installation, cable (m) 0.72
Pulling force
Pulling-eye (kN) 20
Pulling-stocking (kN) 8.3
Resistance 20 °C (ohm/km) 0.164
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 17.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176306208
Reka code 1181899

3x240+35 Cu

Electric number Size Packing (m) Voltage

3x240+35 Cu

Nominal diameter of complete cable (mm) 92
Nominal weight of cable (kg/km) 5693
Conductor material Aluminum
Nominal diameter of conductor (mm) 18
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 8
Nominal diameter over the insulation without insulation screen (mm) 33.6
Nominal thickness of aluminium laminated foil (mm) 0.3
Nominal diameter of messenger (mm) 14
Nominal diameter of earth conductor (mm) 7
Nominal diameter of a sheathed phase conductor (mm) 43
Bending radius
During handling and installation, cable (cm) 1104
In final installation, cable (cm) 773
During handling and installation, phase conductor (m) 0.64
During handling and installation, cable (m) 1.1
In final installation, phase conductor (m) 0.45
In final installation, cable (m) 0.77
Pulling force
Pulling-eye (kN) 20
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.125
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 22.6
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176306222
Reka code 1181901

3x300+35 Cu

Electric number Size Packing (m) Voltage

3x300+35 Cu

Nominal diameter of complete cable (mm) 96
Nominal weight of cable (kg/km) 6468
Conductor material Aluminum
Nominal diameter of conductor (mm) 20
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 8
Nominal diameter over the insulation without insulation screen (mm) 35.4
Nominal thickness of aluminium laminated foil (mm) 0.3
Nominal diameter of messenger (mm) 14
Nominal diameter of earth conductor (mm) 7
Nominal diameter of a sheathed phase conductor (mm) 45
Bending radius
During handling and installation, cable (cm) 1152
In final installation, cable (cm) 806
During handling and installation, phase conductor (m) 0.67
During handling and installation, cable (m) 1.15
In final installation, phase conductor (m) 0.47
In final installation, cable (m) 0.8
Pulling force
Pulling-eye (kN) 20
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.1
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 28.3
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176306246
Reka code 1181903

3x300+70 Cu

Electric number Size Packing (m) Voltage

3x300+70 Cu

Nominal diameter of complete cable (mm) 96
Nominal weight of cable (kg/km) 6758
Conductor material Aluminum
Nominal diameter of conductor (mm) 20
Nominal cross-sectional area of conductor (mm2) 0
Nominal thickness of insulation (mm) 8
Nominal diameter over the insulation without insulation screen (mm) 35.4
Nominal thickness of aluminium laminated foil (mm) 0.3
Nominal diameter of messenger (mm) 20
Nominal diameter of earth conductor (mm) 10
Nominal diameter of a sheathed phase conductor (mm) 45
Bending radius
During handling and installation, cable (cm) 1152
In final installation, cable (cm) 806
During handling and installation, phase conductor (m) 0.67
During handling and installation, cable (m) 1.15
In final installation, phase conductor (m) 0.47
In final installation, cable (m) 0.8
Pulling force
Pulling-eye (kN) 20
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.1
Minimum cable temperature during transport (°C) -40
Minimum cable temperature during handling and installation (°C) -20
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 28.3
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176306253
Reka code 1181904