AEMCMK-HF

For fixed installations indoors and outdoors. Collective screen gives an excellent protection against electromagnetic radiation from the cable.

Standards SFS 5546:2020, SS 424 14 18:2007, HD 604 S1:1994/A3:2005 Part 5 Section I and D, IEC 60502-1:2004
Reaction to fire Dca-s2,d2,a2
CPR - DoP 2021005_DOP.pdf
Conductor 16...25 mm² circular stranded aluminium, EN/IEC 60228 class 2
35…300 mm² sector shaped, stranded aluminium, EN/IEC 60228 class 2
Insulation Halogen free XLPE
Core Identification (all color combinations in the cable family) brown, black, grey
blue, brown, black, grey
Inner covering plastic tape
Metal screen EMC-copper foil and copper wires
Oversheath UV-protected halogen free polyolefin compound
Colour of the oversheath Black

3x16/10

Electric number Size Packing (m) Voltage

3x16/10

Nominal diameter of complete cable (mm) 21
Nominal weight of cable (kg/km) 613
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 10
Bending radius
During handling and installation, cable (cm) 248
In final installation, cable (cm) 174
During handling and installation, cable (cm) 25
In final installation, cable (cm) 17
During handling and installation, cable (m) 0.25
In final installation, cable (m) 0.17
Pulling force
Pulling-eye (kN) 0.7
Pulling-stocking (kN) 0.7
Resistance 20 °C (ohm/km) 1.91
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.83
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 1.5
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176225653
Reka code 1149200

3x120/41

Electric number Size Packing (m) Voltage

3x120/41

Nominal diameter of complete cable (mm) 36
Nominal weight of cable (kg/km) 1977
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 41
Bending radius
During handling and installation, cable (cm) 431
In final installation, cable (cm) 302
During handling and installation, cable (cm) 43
In final installation, cable (cm) 30
During handling and installation, cable (m) 0.43
In final installation, cable (m) 0.3
Pulling force
Pulling-eye (kN) 5.4
Pulling-stocking (kN) 5.4
Resistance 20 °C (ohm/km) 0.253
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.443
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 11.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176225776
Reka code 1149206

3x185/57

Electric number Size Packing (m) Voltage

3x185/57

Nominal diameter of complete cable (mm) 44
Nominal weight of cable (kg/km) 2882
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 57
Bending radius
During handling and installation, cable (cm) 534
In final installation, cable (cm) 373
During handling and installation, cable (cm) 53
In final installation, cable (cm) 37
During handling and installation, cable (m) 0.53
In final installation, cable (m) 0.37
Pulling force
Pulling-eye (kN) 8.3
Pulling-stocking (kN) 8.3
Resistance 20 °C (ohm/km) 0.164
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.32
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 17.5
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176225813
Reka code 1149208

3x240/72

Electric number Size Packing (m) Voltage

3x240/72

Nominal diameter of complete cable (mm) 48
Nominal weight of cable (kg/km) 3660
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 72
Bending radius
During handling and installation, cable (cm) 577
In final installation, cable (cm) 404
During handling and installation, cable (cm) 58
In final installation, cable (cm) 40
During handling and installation, cable (m) 0.58
In final installation, cable (m) 0.4
Pulling force
Pulling-eye (kN) 10.8
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.125
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.253
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 22.6
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176225837
Reka code 1149209

4x16/10

Electric number Size Packing (m) Voltage

4x16/10

Nominal diameter of complete cable (mm) 22
Nominal weight of cable (kg/km) 709
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 10
Bending radius
During handling and installation, cable (cm) 268
In final installation, cable (cm) 187
During handling and installation, cable (cm) 27
In final installation, cable (cm) 19
During handling and installation, cable (m) 0.27
In final installation, cable (m) 0.19
Pulling force
Pulling-eye (kN) 1
Pulling-stocking (kN) 1
Resistance 20 °C (ohm/km) 1.91
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.83
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 1.5
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176225875
Reka code 1149214

4x25/16

Electric number Size Packing (m) Voltage

4x25/16

Nominal diameter of complete cable (mm) 26
Nominal weight of cable (kg/km) 1003
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 312
In final installation, cable (cm) 219
During handling and installation, cable (cm) 31
In final installation, cable (cm) 22
During handling and installation, cable (m) 0.31
In final installation, cable (m) 0.22
Pulling force
Pulling-eye (kN) 1.5
Pulling-stocking (kN) 1.5
Resistance 20 °C (ohm/km) 1.2
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 2.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176225899
Reka code 1149215

4x35/16

Electric number Size Packing (m) Voltage

4x35/16

Nominal diameter of complete cable (mm) 24
Nominal weight of cable (kg/km) 859
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 16
Bending radius
During handling and installation, cable (cm) 289
In final installation, cable (cm) 202
During handling and installation, cable (cm) 29
In final installation, cable (cm) 20
During handling and installation, cable (m) 0.29
In final installation, cable (m) 0.2
Pulling force
Pulling-eye (kN) 2.1
Pulling-stocking (kN) 2.1
Resistance 20 °C (ohm/km) 0.868
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 1.15
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 3.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176225912
Reka code 1149216

4x70/21

Electric number Size Packing (m) Voltage

4x70/21

Nominal diameter of complete cable (mm) 31
Nominal weight of cable (kg/km) 1464
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 21
Bending radius
During handling and installation, cable (cm) 376
In final installation, cable (cm) 263
During handling and installation, cable (cm) 38
In final installation, cable (cm) 26
During handling and installation, cable (m) 0.38
In final installation, cable (m) 0.26
Pulling force
Pulling-eye (kN) 4.2
Pulling-stocking (kN) 4.2
Resistance 20 °C (ohm/km) 0.443
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.868
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 6.7
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176225950
Reka code 1149218

4x120/41

Electric number Size Packing (m) Voltage

4x120/41

Nominal diameter of complete cable (mm) 40
Nominal weight of cable (kg/km) 2425
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 41
Bending radius
During handling and installation, cable (cm) 486
In final installation, cable (cm) 340
During handling and installation, cable (cm) 49
In final installation, cable (cm) 34
During handling and installation, cable (m) 0.49
In final installation, cable (m) 0.34
Pulling force
Pulling-eye (kN) 7.2
Pulling-stocking (kN) 7.2
Resistance 20 °C (ohm/km) 0.253
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.443
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 11.4
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176225998
Reka code 1149220

4x150/41

Electric number Size Packing (m) Voltage

4x150/41

Nominal diameter of complete cable (mm) 45
Nominal weight of cable (kg/km) 2875
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 41
Bending radius
During handling and installation, cable (cm) 536
In final installation, cable (cm) 375
During handling and installation, cable (cm) 54
In final installation, cable (cm) 38
During handling and installation, cable (m) 0.54
In final installation, cable (m) 0.38
Pulling force
Pulling-eye (kN) 9
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.206
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.443
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 14.2
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176226018
Reka code 1149221

4x300/88

Electric number Size Packing (m) Voltage

4x300/88

Nominal diameter of complete cable (mm) 60
Nominal weight of cable (kg/km) 5554
Conductor material Aluminum
Nominal cross-sectional area of conductor (mm2) 0
Nominal size of metal screen (mm2) 88
Bending radius
During handling and installation, cable (cm) 719
In final installation, cable (cm) 503
During handling and installation, cable (cm) 72
In final installation, cable (cm) 50
During handling and installation, cable (m) 0.72
In final installation, cable (m) 0.5
Pulling force
Pulling-eye (kN) 18
Pulling-stocking (kN) 8.5
Resistance 20 °C (ohm/km) 0.1
Maximum d.c. resistance at 20 °C, metal screen (ohm/km) 0.206
Minimum cable temperature during transport (°C) -25
Minimum cable temperature during handling and installation (°C) -15
Minimum cable temperature during operation (°C) -50
Maximum conductor temperature in normal operation (°C) 90
Phase (initial temperature 70 °C, final temperature 160 °C) 28.2
Maximum conductor temperature during short circuit (not exceeding 5 sec.) (°C) 250
EAN code 6438176226070
Reka code 1149224