3x50 | 1187052 | 500 K26 |
Voltage | 12/20 (24) kV |
Diameter (mm) | 60 |
Weight | 1990 |
Minimum allowed bending radius in installation (cm) | 70,44 |
Minimum allowed bending radius in final installation (cm) | 46,96 |
Maximum allowed pulling force when pulling from conductors (kN) | 7,5 |
Maximum DC resistance of phase conductor, +20°C (ohm/km) | 0,641 |
Minimum handling temperature (°C) | -20 |
Maximum conductor temperature (°C) | 90 |
Conductor short-circuit temperature, 5 s (°C) | 250 |
Product number | 1187052 |
GTIN code | 6410006224005 |
|
3x70 | 1187103 | 500 K26 |
Voltage | 12/20 (24) kV |
Diameter (mm) | 63 |
Weight | 2280 |
Minimum allowed bending radius in installation (cm) | 74,052 |
Minimum allowed bending radius in final installation (cm) | 49,368 |
Maximum allowed pulling force when pulling from conductors (kN) | 10,5 |
Maximum DC resistance of phase conductor, +20°C (ohm/km) | 0,443 |
Minimum handling temperature (°C) | -20 |
Maximum conductor temperature (°C) | 90 |
Conductor short-circuit temperature, 5 s (°C) | 250 |
Product number | 1187103 |
GTIN code | 6410006224012 |
|
3x95 | 1187104 | 500 K26 |
Voltage | 12/20 (24) kV |
Diameter (mm) | 67 |
Weight | 2650 |
Minimum allowed bending radius in installation (cm) | 78,948 |
Minimum allowed bending radius in final installation (cm) | 52,632 |
Maximum allowed pulling force when pulling from conductors (kN) | 14,3 |
Maximum DC resistance of phase conductor, +20°C (ohm/km) | 0,320 |
Minimum handling temperature (°C) | -20 |
Maximum conductor temperature (°C) | 90 |
Conductor short-circuit temperature, 5 s (°C) | 250 |
Product number | 1187104 |
GTIN code | 6410006224036 |
|
3x150 | 1187106 | 500 K26 |
Voltage | 12/20 (24) kV |
Diameter (mm) | 73 |
Weight | 3320 |
Minimum allowed bending radius in installation (cm) | 85,788 |
Minimum allowed bending radius in final installation (cm) | 57,192 |
Maximum allowed pulling force when pulling from conductors (kN) | 20 |
Maximum DC resistance of phase conductor, +20°C (ohm/km) | 0,206 |
Minimum handling temperature (°C) | -20 |
Maximum conductor temperature (°C) | 90 |
Conductor short-circuit temperature, 5 s (°C) | 250 |
Product number | 1187106 |
GTIN code | 6410006224050 |
|
3x185 | 1187107 | 500 K26 |
Voltage | 12/20 (24) kV |
Diameter (mm) | 77 |
Weight | 3840 |
Minimum allowed bending radius in installation (cm) | 91,2 |
Minimum allowed bending radius in final installation (cm) | 60,8 |
Maximum allowed pulling force when pulling from conductors (kN) | 20 |
Maximum DC resistance of phase conductor, +20°C (ohm/km) | 0,164 |
Minimum handling temperature (°C) | -20 |
Maximum conductor temperature (°C) | 90 |
Conductor short-circuit temperature, 5 s (°C) | 250 |
Product number | 1187107 |
GTIN code | 6410006224074 |
|
3x240 | 1187108 | 500 K28 |
Voltage | 12/20 (24) kV |
Diameter (mm) | 83 |
Weight | 4620 |
Minimum allowed bending radius in installation (cm) | 98,04 |
Minimum allowed bending radius in final installation (cm) | 65,36 |
Maximum allowed pulling force when pulling from conductors (kN) | 20 |
Maximum DC resistance of phase conductor, +20°C (ohm/km) | 0,125 |
Minimum handling temperature (°C) | -20 |
Maximum conductor temperature (°C) | 90 |
Conductor short-circuit temperature, 5 s (°C) | 250 |
Product number | 1187108 |
GTIN code | 6410006224098 |
|
3x300 | 1187109 | 500 K28 |
Voltage | 12/20 (24) kV |
Diameter (mm) | 87 |
Weight | 5360 |
Minimum allowed bending radius in installation (cm) | 103,068 |
Minimum allowed bending radius in final installation (cm) | 68,712 |
Maximum allowed pulling force when pulling from conductors (kN) | 20 |
Maximum DC resistance of phase conductor, +20°C (ohm/km) | 0,100 |
Minimum handling temperature (°C) | -20 |
Maximum conductor temperature (°C) | 90 |
Conductor short-circuit temperature, 5 s (°C) | 250 |
Product number | 1187109 |
GTIN code | 6438176300077 |
|