3x50+35 Cu | 1187002 | 500 K26 |
Voltage | 12/20 (24) kV |
Diameter (mm) | 60 |
Weight kg/km | 2300 |
Minimum allowed bending radius in installation (cm) | 70 |
Minimum allowed bending radius in final installation (cm) | 47 |
Maximum allowed pulling force when pulling from conductors (kN) | 7,50 |
Maximum DC resistance of phase conductor, +20°C (ohm/km) | 0,641 |
Minimum handling temperature (°C) | -20 |
Maximum conductor temperature (°C) | 90 |
Conductor short-circuit temperature, 5 s (°C) | 250 |
Product number | 1187002 |
GTIN code | 6410006224302 |
|
3x70+35 Cu | 1187003 | 500 K26 |
Voltage | 12/20 (24) kV |
Diameter (mm) | 63 |
Weight kg/km | 2590 |
Minimum allowed bending radius in installation (cm) | 74 |
Minimum allowed bending radius in final installation (cm) | 49 |
Maximum allowed pulling force when pulling from conductors (kN) | 10,50 |
Maximum DC resistance of phase conductor, +20°C (ohm/km) | 0,443 |
Minimum handling temperature (°C) | -20 |
Maximum conductor temperature (°C) | 90 |
Conductor short-circuit temperature, 5 s (°C) | 250 |
Product number | 1187003 |
GTIN code | 6410006224319 |
|
3x95+35 Cu | 1187004 | 500 K26 |
Voltage | 12/20 (24) kV |
Diameter (mm) | 67 |
Weight kg/km | 2960 |
Minimum allowed bending radius in installation (cm) | 79 |
Minimum allowed bending radius in final installation (cm) | 53 |
Maximum allowed pulling force when pulling from conductors (kN) | 14,25 |
Maximum DC resistance of phase conductor, +20°C (ohm/km) | 0,320 |
Minimum handling temperature (°C) | -20 |
Maximum conductor temperature (°C) | 90 |
Conductor short-circuit temperature, 5 s (°C) | 250 |
Product number | 1187004 |
GTIN code | 6410006224326 |
|
3x120+35 Cu | 1187005 | 500 K26 |
Voltage | 12/20 (24) kV |
Diameter (mm) | 69 |
Weight kg/km | 3250 |
Minimum allowed bending radius in installation (cm) | 82 |
Minimum allowed bending radius in final installation (cm) | 54 |
Maximum allowed pulling force when pulling from conductors (kN) | 18,00 |
Maximum DC resistance of phase conductor, +20°C (ohm/km) | 0,253 |
Minimum handling temperature (°C) | -20 |
Maximum conductor temperature (°C) | 90 |
Conductor short-circuit temperature, 5 s (°C) | 250 |
Product number | 1187005 |
GTIN code | 6410006224333 |
|
3x150+35 Cu | 1187006 | 500 K26 |
Voltage | 12/20 (24) kV |
Diameter (mm) | 73 |
Weight kg/km | 3630 |
Minimum allowed bending radius in installation (cm) | 86 |
Minimum allowed bending radius in final installation (cm) | 57 |
Maximum allowed pulling force when pulling from conductors (kN) | 20,00 |
Maximum DC resistance of phase conductor, +20°C (ohm/km) | 0,206 |
Minimum handling temperature (°C) | -20 |
Maximum conductor temperature (°C) | 90 |
Conductor short-circuit temperature, 5 s (°C) | 250 |
Product number | 1187006 |
GTIN code | 6410006224340 |
|
3x185+35 Cu | 1187007 | 500 K26 |
Voltage | 12/20 (24) kV |
Diameter (mm) | 77 |
Weight kg/km | 4150 |
Minimum allowed bending radius in installation (cm) | 91 |
Minimum allowed bending radius in final installation (cm) | 61 |
Maximum allowed pulling force when pulling from conductors (kN) | 20,00 |
Maximum DC resistance of phase conductor, +20°C (ohm/km) | 0,164 |
Minimum handling temperature (°C) | -20 |
Maximum conductor temperature (°C) | 90 |
Conductor short-circuit temperature, 5 s (°C) | 250 |
Product number | 1187007 |
GTIN code | 6410006224357 |
|
3x240+35 Cu | 1187018 | 500 K28 |
Voltage | 12/20 (24) kV |
Diameter (mm) | 83 |
Weight kg/km | 4920 |
Minimum allowed bending radius in installation (cm) | 98 |
Minimum allowed bending radius in final installation (cm) | 65 |
Maximum allowed pulling force when pulling from conductors (kN) | 20,00 |
Maximum DC resistance of phase conductor, +20°C (ohm/km) | 0,125 |
Minimum handling temperature (°C) | -20 |
Maximum conductor temperature (°C) | 90 |
Conductor short-circuit temperature, 5 s (°C) | 250 |
Product number | 1187018 |
GTIN code | 6410006224500 |
|
3x240+70 Cu | 1187008 | 500 K28 |
Voltage | 12/20 (24) kV |
Diameter (mm) | 83 |
Weight kg/km | 5230 |
Minimum allowed bending radius in installation (cm) | 98 |
Minimum allowed bending radius in final installation (cm) | 65 |
Maximum allowed pulling force when pulling from conductors (kN) | 20,00 |
Maximum DC resistance of phase conductor, +20°C (ohm/km) | 0,125 |
Minimum handling temperature (°C) | -20 |
Maximum conductor temperature (°C) | 90 |
Conductor short-circuit temperature, 5 s (°C) | 250 |
Product number | 1187008 |
GTIN code | 6410006224364 |
|
3x300+35 Cu | 1187019 | 500 K28 |
Voltage | 12/20 (24) kV |
Diameter (mm) | 87 |
Weight kg/km | 5660 |
Minimum allowed bending radius in installation (cm) | 103 |
Minimum allowed bending radius in final installation (cm) | 69 |
Maximum allowed pulling force when pulling from conductors (kN) | 20,00 |
Maximum DC resistance of phase conductor, +20°C (ohm/km) | 0,100 |
Minimum handling temperature (°C) | -20 |
Maximum conductor temperature (°C) | 90 |
Conductor short-circuit temperature, 5 s (°C) | 250 |
Product number | 1187019 |
GTIN code | 6438176300084 |
|
3x300+70 Cu | 1187009 | 500 K28 |
Voltage | 12/20 (24) kV |
Diameter (mm) | 87 |
Weight kg/km | 5950 |
Minimum allowed bending radius in installation (cm) | 103 |
Minimum allowed bending radius in final installation (cm) | 69 |
Maximum allowed pulling force when pulling from conductors (kN) | 20,00 |
Maximum DC resistance of phase conductor, +20°C (ohm/km) | 0,100 |
Minimum handling temperature (°C) | -20 |
Maximum conductor temperature (°C) | 90 |
Conductor short-circuit temperature, 5 s (°C) | 250 |
Product number | 1187009 |
GTIN code | 6410006224371 |
|